PERFORMANCE GUIDE FOR E3A300 RANGE(PRIMARY TEMPERATURE 82

O

C , COLD FEED 10

O

C )

ECONOPLATE MODEL

323

325

327

329

331

333

335

337

339

341

343

SECONDARY FLOW  RATE

103.8

112.2

118.8

125.4

132

138

144.6

149.4

154.8

159.6

165

AT 60

O

C  l/min

SECONDARY PRESSURE DROP 

34

34

33

32

31

30

30

29

28

27

27

AT PEAK OUTPUT  kPa
PRIMARY FLOW  RATE  l/sec

2.40

2.55

2.66

2.76

2.85

2.95

3.05

3.10

3.17

3.23

3.3

HEAT LOAD REQUIRED  kW

361

391

414

437

460

481

503

520

539

556

575

SELECTION GUIDE FOR E3A300 RANGE

TOURIST HOTELS BY NUMBER OF

55

61

67

73

78

84

90

96

102

106

112

ROOMS
LUXURY HOTELS BY NUMBER OF

36

41

45

50

54

58

62

65

68

71

75

ROOMS
NUMBER OF STANDARD FLATS

85

96

106

117

127

137

150

160

170

178

188

NUMBER OF LUXURY FLATS

56

64

72

80

89

97

107

115

122

130

137

HOSPITALS & NURSING HOMES

100

113

127

141

158

170

186

196

209

220

235

BY NUMBER OF ROOMS
SPORTS CENTRES OR STADIUMS

27

31

35

38

42

46

50

54

58

60

64

BY NUMBER OF SHOW ERS

Available pump head in kPa from optional secondary recirculation pump, at various flow rates

RECIRCULATION RATE OF 1/2m

3

/hr

38

38

38

38

38

38

38

38

38

38

38

RECIRCULATION RATE OF 1m

3

/hr

32

32

32

32

32

32

32

32

32

32

32

RECIRCULATION RATE OF 2m

3

/hr

14

15

16

16

17

17

17

17

18

18

18

NOTES:The extra primary pump head available to overcome pipework resistance is 6 kPa (variable on request).
             :Models with lower secondary resistance can be produced on request.
             :Output figures vary with primary temperature E.g. capacity is increased by approx. 33% with a primary of 105OC.
             :The selection guide uses diversity factors . For simultaneous operation of outlets calculate separately.
             :For applications not listed or temperatures other than those above , contact Stokvis for a selection.
             :Tourist hotels assume a shower and wash hand basin are available in each room.
             :Luxury hotels assume a bath or shower and wash hand basin are available in each room.
             :Standard flats are classed as having 1 sink, 1 wash hand basin and 1 shower.
             :Luxury flats are classified as having 1 sink, 2 wash hand basins, and 1 bath.
             :Standard fittings are assumed in all cases.
             :There is a slight reduction in output when using 1 phase primary pump. 

 
 
 

Содержание ECONOPLATE E3 Series

Страница 1: ...ATE HEAT EXCHANGER INSTALLATION OPERATION MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL 08707 707 747 FAX 08707 707 767 E MAIL info stokvisboilers co...

Страница 2: ......

Страница 3: ...hed to the heat exchanger with an allowance of 6 kPa for pipework losses also included Systems which utilise an existing primary feed pump when connected to a unit with its 3 port valve require an add...

Страница 4: ...PS32 55B optional dependent upon model Control valve 3 port Cast Iron DN40 PN10 Valve Actuator 240V modulating motor open motor close CONTROL PANEL Polycarbonate enclosure Electronic PID temperature c...

Страница 5: ...740 mm 140 mm 1110 mm 101 mm 10mm SECONDARY RECIRC 1 BSP F 85 mm 80 mm 151 mm 80 mm 75mm E3A100 1R INSTANTANEOUS MECHANICAL DETAILS WITH SECONDARY HWS RE CIRCULATION PUMP AVM124 OUTLET 11 2 BSP F PRI...

Страница 6: ...mm 75mm 250 mm 305 mm 555 mm 500 mm 400 mm 200 mm 740 mm 140 mm 310 mm 1110 mm 55 mm 108 114 375mm 116 124 420mm E3A100 1T SEMI INSTANTANEOUS MECHANICAL DETAILS WITH PUMP ON ANGLED SECONDARY CONNECTIO...

Страница 7: ...rol valve 3 port Cast Iron DN40 PN10 Valve Actuator 240V modulating motor open motor close CONTROL PANEL ABS enclosure Electronic PID temperature controller 7 day time clock control of 2 temperature s...

Страница 8: ...mm 1130 mm 100 mm 75mm 250 mm 408 mm 140 mm 101 mm 555 mm 151 mm 10mm 85 mm 80 mm 75mm E3A300 1R INSTANTANEOUS MECHANICAL DETAILS WITH SECONDARY HWS RE CIRCULATION PUMP AVM234 OUTLET 2 BSP F PRIMARY I...

Страница 9: ...00 mm 400 mm 200 mm 740 mm 1130 mm 100 mm 75mm 250 mm 408 mm 140 mm 130 mm 555 mm 151 mm 10mm 85 mm 400 mm 420 mm 55 mm E3A300 1T SEMI INSTANTANEOUS MECHANICAL DETAILS WITH UPS32 80B ON ANGLED SECONDA...

Страница 10: ...various flow rates RECIRCULATION RATE OF 1 2m3 hr 30 34 36 36 37 37 38 38 38 38 RECIRCULATION RATE OF 1m3 hr 7 20 25 28 29 30 31 31 32 32 RECIRCULATION RATE OF 2m3 hr 2 5 7 10 12 13 14 15 NOTES The e...

Страница 11: ...ptional secondary recirculation pump at various flow rates RECIRCULATION RATE OF 1 2m3 hr 38 38 38 38 38 38 38 38 38 38 38 RECIRCULATION RATE OF 1m3 hr 32 32 32 32 32 32 32 32 32 32 32 RECIRCULATION R...

Страница 12: ...Electronic PID temperature controller 7 day time clock control of 2 temperature settings and or 1 temperature night off per day Safety extra low voltage circuit for external clock control of 2 temper...

Страница 13: ...PN10 SECONDARY OUTLET 2 BSP F 135mm 330mm 140mm 75mm 500mm 865mm 151mm 275mm 1165mm 590mm 87mm E3C 1R INSTANTANEOUS MECHANICAL DETAILS WITH SECONDARY PUMP AVM124 SECONDARY RECIRC SECONDARY INLET 2 BSP...

Страница 14: ...BSP F 330mm 140mm 75mm 500mm 865mm 151mm 275mm 1165mm 590mm 85mm 452mm 420mm 130mm 135mm E3C 1T SEMI INSTANTANEOUS MECHANICAL DETAILS WITH UPS40 60 2 FB TRANSFER PUMP AVM234 SECONDARY INLET DN40 PN6...

Страница 15: ...STADIUMS 63 80 100 120 133 148 163 180 193 207 220 230 240 BY NUMBER OF SHOWERS RECIRCULATION RATE OF 1m 3 hr 48 49 49 49 49 49 49 49 49 49 49 49 49 RECIRCULATION RATE OF 3m 3 hr 39 40 41 41 42 42 42...

Страница 16: ...mand for hot water occurs the boiler would be unable to respond fast enough to prevent temperatures dropping On systems with a sealed secondary circuit operating with primary temperatures over 900 C w...

Страница 17: ...es should be fitted to all circuits SEMI INSTANTANEOUS HOT WATER APPLICATIONS When hot water is drawn from a storage vessel into the distribution system to the taps and the vessel is heated directly b...

Страница 18: ...LVE PROHIBITED BY U K REGULATIONS Semi Instantaneous Application LEGEND SAFETY VALVE DOUBLE NRV SINGLE NRV ISOLATION VALVE AUTO AIR VALVE DRAIN VALVE HWS DRAW OFF EXPANSION VESSEL RECIRC PUMP COLD WAT...

Страница 19: ...erlock An external safety device or switched circuit can be connected to the Econoplate which will shut the unit down in case of a fault it is a safety extra low voltage circuit an open circuit should...

Страница 20: ...by simulating a load no load situation There are three different types of 3 port valve actuator combinations used on E3 series units Current units are fitted with a Sauter BUE valve with an AVM124F13...

Страница 21: ...e until the valve plug is fully seated this is checked by inserting a small screwdriver into the spindle and testing for any rotation of the valve spindle when the spindle cannot rotate the lower nut...

Страница 22: ...pper LED lit red upper limit stop or CLOSED position reached Lower LED lit red lower limit stop or OPEN position reached Upper LED flashing green drive running moving towards CLOSED position Upper LED...

Страница 23: ...rwise refer to the following notes and separate instruction sheets A plate pack always has a 4 hole first plate which has a gasket around all 4 ports This plate sits against the fixed chassis plate Ne...

Страница 24: ...ed intermediate plates On GL13 plates the letter O is stamped into either the top or bottom of each plate and alternate left and right top ports have a gasket around their circumference These sequence...

Страница 25: ...e secondary side of the unit and remove the sensor clean as appropriate If heavily scaled the Plate Heat Exchanger will probably be similarly affected strip and clean as necessary see maintenance proc...

Страница 26: ...y hand using the fold out lever on the outside of the actuator as shown below On AVM124 actuators the single LED will flash off and on rapidly this is to indicate manual override is in operation On AV...

Страница 27: ...w investigate the effect of turning off HWS recirculation pumps where they are installed on the HWS return If it improves water flow try operating the pump on a lower speed or reinstall it on the HWS...

Страница 28: ...nsfer Pump UPS40 120 2FB 1 Phase E3C Primary Pump Motor UPS50 120 1 Phase 96406015 E3C Primary Pump Motor UPS50 120 3 Phase 96406017 E3C Secondary Recirculating Pump UPS32 55B 1 Phase 52001097 Telemec...

Страница 29: ...valve Sauter type BXE050F300 for E3C only Sauter actuator type AVR32 W30 F001 for BXE valve Sauter actuator type AVM234SF132 5 for BXE valve Integral E series controller complete yellow facia red disp...

Страница 30: ...STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL 08707 707 747 FAX 08707 707 767 E MAIL info stokvisboilers com WEBSITE www stokvisboilers com...

Отзывы: