24
Kit G: plate heat exc con-
nection kit
The kit contains a plate heat ex-
changer including connection mate-
rial, automatic de-aerator and expan-
sion vessel. For multiple assembly
variations two 90º bends are in-
cluded, to enable a connection possi-
bility to the right or the left. (see also
section “connection possibilities”).
The following data can be used for
the dimensioning of the secundary
system.
Data secundary circuit plate heat
exchanger
Typ
∆
T=10K
∆
T=15K
∆
T=20K
[m
3
/h] [kPa] [m
3
/h] [kPa] [m
3
/h] [kPa]
R
6142
12.2 30.4 -
-
6.1 8.1
R6
190
16.2 28.8 -
-
8.1 14.0
R6
237
20.4 44.0 -
-
10.2 21.5
R6
285
-
-
16.3 28.8 12.2 16.6
R6
380
-
-
21.7 48.7 16.3 28.9
R6
475
-
-
27.2 15.6 20.4 14.3
R6
539
-
-
30.8 19.7 23.1 18.0
Kit H: low loss connection
kit
Mono header
The kit contains a low loss header in-
cluding connection material, automatic
de-aerator, plunge (for header sensor)
and fill/drain valve on the bottom con-
nection. For multiple assembly varia-
tions two 90º bends are included, to
enable a connection possibility to the
right or the left. (see also section
“connection possibilities”).
Duo header
The kit contains a duo header inclu-
ding automatic de-aerator, plunge (for
header sensor) and fill/drain valve on
the bottom connection. The duo
header kit doesn’t contain connection
material, because of the wide varia-
tion of positioning possibilities. The
connections have to be made on site.
R6
142
-R6
237
(DN150)
R6
285
-R6
539
(DN200)
Accessories