Flue gas system
Dimensioning
13
VERSION 1
Calculation base:
Total connection length in boiler room
≤
1.5 m;
2x 87°-bend
Maximum permissible height (h) of flue gas
system in m
Boiler type Ø 110
[mm]
Ø 130
[mm]
Ø 150
[mm]
Ø 200
[mm]
Ø 250
[mm]
6142
10
35
50
6190
17
34
50
6237
26
50
6285
16
50
6380
50
50
6475
39
50
6539
29
50
VERSION 2
Calculation base:
Total connection length in boiler room
≤
3 m;
4x 87°-bend
Maximum permissible height (h) of flue gas
system in m
Boiler type Ø 110
[mm]
Ø 130
[mm]
Ø 150
[mm]
Ø 200
[mm]
Ø 250
[mm]
6142
5
29
50
6190
11
27
50
6237
19
50
6285
9
50
6380
43
50
6475
31
50
6539
20
50
Dimensioning
When dimensioning a flue gas system,
it’s necessary to perform a calculation
check of the flue gas system in order to
verify if the choosen system is appli-
cable.
The following table shows two
examples of possible flue gas systems,
including the maximum possible height
of the system. These examples only
give an indication of the possible
heights, but they can not be used for
official flue gas layout calculation. Each
flue gas system must be calculated by
an authorized company.
The maximum negative flue gas pres-
sure, which doesn’t affect the burner
modulation ratio, is 30 Pa. Higher nega-
tive pressure will lead to limitation of
the burner modulation ratio.
The maximum horizontal flue gas way
is 20 m. With horizontal ways longer
than 20 m, a faultless burner start in
cold condition can not be guaranteed.