STOBER
10 | Connection
02/2019 | ID 442728.05
115
For connecting wiring, observe the terminal specifications in the chapter
.
Cable requirements
Feature
All sizes
Max. cable length
30 m
Tab. 95: Cable length [m]
10.4.8
Connecting the supply module
DANGER!
Electrical voltage! Risk of fatal injury due to electric shock!
▪
Always switch off all power supply voltage before working on the devices!
▪
Note the discharge time of the DC link capacitors. You can only determine the absence of
voltage after this time period.
Tools and material
You will need:
§
A suitable terminal set for the supply module
§
Tool for tightening the fastening screws
Requirements and connection
Bottom of the device:
ü
You have a system circuit diagram describing the connection of the supply module.
1. Connect the braking resistor to terminal X21 and attach the terminal. Ensure that the
connection lines are twisted pairs.
2. Attach the X22 terminal of the Quick DC-Link module. Ensure that the connection lines are
twisted pairs.
3. Connect the temperature monitoring of the braking resistor to terminal X23 and attach the
terminal.
Top of the device:
ü
You have a system circuit diagram describing the connection of the supply module.
1. Connect the 2nd grounding conductor to the ground bolt. Note the instructions and
requirements in the chapters
CE-compliant housing grounding [
2. Connect the power supply to terminal X10 and attach the terminal.
3. Connect the 24 V
DC
power supply for the control electronics to terminal X11 and attach the
terminal.
4. Connect the status output to terminal X100 and attach the terminal.