iNSTALLATiON 

 

Appliance handover

24

 | WPL-A  Premium 

www.stiebel-eltron.com

Version 1: reduced night mode

You can reduce the sound power level of the appliance through 

its output or through the fans. If the emergency/booster heater 

cuts in, this will result in higher running costs.

Version 2: appliance switched off

You can switch the appliance off. If the appliance is switched off, 

central heating and DHW heating will be supplied solely through 

the emergency/booster heater. If the emergency/booster heater 

cuts in, this will result in higher running costs.

13.3.1  Reduced night mode

 

Note

When reduced night mode is active, this may result in 

higher running costs.

The output and fan control are infinitely variable.
The table will tell you how the sound power level of the appliance 

changes as output and fan control are changed.

meaning

max. reduced night mode 

Output and fans cannot be reduced 

below these levels.

reduced night mode 

The appliance operates at the set re-

duced output or fan control.

WPL-A 05 HK 230 

Premium

WPL-A 07 HK 230 

Premium

max. reduced night mode
W55

Sound power level

dB(A)

47

47

Compressor speed

Hz

30

30

Fan control

%

42

42

Heating output

kW

2.7

2.7

reduced night mode 50 %

W55

Sound power level

dB(A)

47

51

Compressor speed

Hz

33

47

Fan control

%

44

51

Heating output

kW

3.2

4.9

 

f

Adjust the fan control and compressor output in the heat 

pump manager.

Parameter

OUTPUT (COMMISSIONING / SILENT MODE / OUTPUT REDUCTION)
FAN (COMMISSIONING / SILENT MODE / OUTPUT REDUCTION)

13.3.2  Appliance switched off

 

Note

If the appliance is switched off, central heating and DHW 

heating will be supplied solely through the emergency/

booster heater. This will result in higher running costs.

 

f

Switch the appliance off in the heat pump manager.

Parameter

HEAT PUMP OFF (COMMISSIONING / SILENT MODE)

13.4  Other settings

 

f

For operation with or without a buffer cylinder, observe the 

information in the WPM instructions and the BUFFER OPER-

ATION parameter in the SETTINGS / HEATING / STANDARD 

SETTING menu.

Using the heat-up program

If you use the heat-up program, make the following settings on 

the WPM:

 

f

Initially set the "DUAL MODE TEMP HZG" parameter to 30 °C.

 

f

Then set the "LOWER APP LIMIT HZG" parameter to 30 °C.

 

Note

After completing the heat-up process, reset the "DUAL 

MODE TEMP HZG" and "LOWER APP LIMIT HZG" parame-

ters to their respective standard values or to the respec-

tive system values.

14.  Appliance handover

Explain the appliance function to users and familiarise them with 

how it works.

 

Note

Hand over these operating and installation instructions 

to users for safekeeping.

All information in these instructions must be closely ob-

served. The instructions provide information on safety, 

operation, installation and maintenance of the appliance.

15.  Appliance shutdown

!

 

Material losses

Never interrupt the heat pump power supply, even out-

side of the heating season. Otherwise, system frost pro-

tection is not guaranteed. 

The heat pump manager automatically switches the heat 

pump to summer or winter mode. 

15.1  Standby mode

To shut the system down, simply set the heat pump manager to 

"Standby mode". This way, the safety functions that protect the 

system remain enabled, e.g. frost protection.

15.2  Power interruption

If the system is to be isolated from the power supply permanently, 

please observe the following:

!

 

Material losses

If the heat pump is completely switched OFF and there is 

a risk of frost, drain the system on the water side.  

Содержание WPL-A 05 HK 230 Premium

Страница 1: ...OPERATION AND INSTALLATION Air source heat pump WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium...

Страница 2: ...14 10 1 Transport 14 10 2 Heating water connection 14 10 3 Flow and return connection 15 10 4 Fitting the push fit connectors 15 10 5 Oxygen diffusion 16 10 6 Filling the heating system 16 10 7 Conden...

Страница 3: ...r gised for 2 minutes until the inverter capaci tors have discharged Never interrupt the power supply even out side the heating season The system s active frost protection is not guaranteed if the pow...

Страница 4: ...the system configuration the age of the system and the flow rates Confirmation of the specified output data can only be obtained if the test conducted for this purpose is also performed in accord ance...

Страница 5: ...ondenser transfers the heat to the heating circuit The refrigerant then expands again and the cycle restarts from the beginning At air temperatures below approx 7 C the humidity in the air condenses a...

Страница 6: ...e the dual mode temperature to 5 C After 1 to 2 years the dual mode temperature can be reset to e g 3 C Fault Cause Remedy There is a loss of pressure in the heating system Water drips from the safety...

Страница 7: ...B BE Remote control FET Remote control FE7 Ribbon heater HZB 1 Ribbon heater HZB 2 High limit safety cut out for area heating system STB FB Heating circuit pump UP 25 7 5 PCV T support SK 1 Wall mount...

Страница 8: ...air or other ventilation equipment In order to comply with the appliance s safety concept safety clearances to light wells must be observed Installation on foundation light well at ground level 1000 1...

Страница 9: ...liance and facilitate maintenance work D0000096921 f Never install the appliance in a recess Two sides of the ap pliance must remain exposed Material losses Please note that both the flow of outdoor a...

Страница 10: ...into the building to en sure that they are watertight The supply lines are all electric cables plus the flow and return lines To facilitate connection to the appliance we recommend using flexible supp...

Страница 11: ...ront and back Ensure you are using the correct brackets for the left and right hand slots respectively f Position the brackets so that the groove on the bracket is hooked into the appliance f Secure t...

Страница 12: ...ories with which the appliance was secured to the transport pallet D0000064201 f Hook two brackets respectively into the lateral slots on the front and back Ensure you are using the correct brackets f...

Страница 13: ...fer cylinder to ensure trouble free appliance operation The buffer cylinder provides hydraulic separation of the volume flows in the heat pump circuit and heating circuit and also serves as an energy...

Страница 14: ...nnected without removing the cover or side panels 10 1 Transport f When transporting the appliance be aware of its centre of gravity The centre of gravity is in the area where the compressor is locate...

Страница 15: ...17 0 5 mm Pipe diameter 28 mm 21 0 5 mm How the push fit connectors work The push fit connectors are equipped with a retainer with stain less steel serrations and an O ring for sealing The push fit co...

Страница 16: ...recommended in order to prevent corrosion Note Suitable appliances for water softening and desalinating as well as for filling and flushing heating systems can be obtained from trade suppliers Note Do...

Страница 17: ...to drain off 26_03_01_1868 1 1 Condensate drain f Observe chapter Electrical connection Ribbon heater f If the appliance is sited on foundations the condensate drips freely into the condensate drain p...

Страница 18: ...tion f Before working on the appliance isolate it from the power supply at the control panel Note The terminals are located in the terminal area of the ap pliance f Follow the instructions in the chap...

Страница 19: ...ation and the provision of high DHW temperatures Emergency mode If the heat pump shuts down due to a fault the heating output is covered by the electric emergency booster heater Heat up program only...

Страница 20: ...ated washer f Connect the following components to the heat pump manag er in accordance with the technical guides Circulation pump for the heat consumer side Outside temperature sensor Return sensor on...

Страница 21: ...safety cut out has tripped 26_03_01_1880 1 26_03_01_1880 1 Electric emergency booster heater f Remove the cause of the fault D0000035383 f Reset the high limit safety cut out by pressing the reset bu...

Страница 22: ...meter WP WATER FLOW RATE INFO HEAT PUMP PROCESS DATA f Compare the value with the minimum flow rate see chapter Specification Data table Minimum flow rate has been reached No further measures required...

Страница 23: ...you to adjust the heating curve cor rectly Fully open thermostatic or zone valves in a lead room e g living room and bathroom We do not recommend installing thermostatic or zone valves in the lead ro...

Страница 24: ...gh the emergency booster heater This will result in higher running costs f Switch the appliance off in the heat pump manager Parameter HEAT PUMP OFF COMMISSIONING SILENT MODE 13 4 Other settings f For...

Страница 25: ...ow and ice Remove any leaves or other foreign bodies from the evaporator fins periodically 17 Troubleshooting WARNING Electrocution f Before working on the appliance isolate it from the power supply a...

Страница 26: ...r If the appliance is operated in dual mode operation with an ex ternal second heat generator or as a module with a further heat pump set the DIP switch as shown WP Typ ON 1 2 3 4 D0000057055 DIP swit...

Страница 27: ...26_03_01_1880 1 Electric emergency booster heater f Remove the cause of the fault D0000035383 f Reset the high limit safety cut out by pressing the reset but ton f Check whether the heating water is...

Страница 28: ...270 1160 900 70 593 g01 g02 D0000034131 WPL A 05 HK 230 Premium WPL A 07 HK 230 Premium e01 Heating flow Type of connection Plug in connection Plug in connection Diameter mm 28 28 e02 Heating return T...

Страница 29: ...Installation Specification www stiebel eltron com WPL A Premium 29...

Страница 30: ...BF01 XE22 XD03 XD01 XD06 XD02 PE GND A B U V W MSD1 MSP3 L N PE 1 2 MP2 MSD8 XE19 PE N L Netzversorgung Inverter Abtauventil N Abtauventil L Verdichter ON PE Begleitheizung N Begleitheizung L lsumpfh...

Страница 31: ...1 N DHC 1 L DHC 2 N DHC 2 L 12 18V ND 4 20mA 12 18V HD 4 20mA CAN GND CAN L CAN H 12V Phase 4 Phase 3 Phase 2 Phase 1 12V Phase 4 Phase 3 Phase 2 Phase 1 Hei gastemperatur GND Hei gastemperatur Heizu...

Страница 32: ...5 Split ferrite RF06 Split ferrite RF07 Split ferrite XD01 External heat pump power supply terminal XD02 External NHZ terminal XD03 External control terminal XD05 External bus terminal XD06 External r...

Страница 33: ...4 6 8 10 12 25 20 15 10 5 0 5 10 15 20 2 3 4 5 7 8 9 10 D0000090274 X Outside temperature C 2 Max W65 4 Max W45 7 Min W65 9 Min W45 Y Heating output kW 3 Max W55 5 Max W35 8 Min W55 10 Min W35 DHW ou...

Страница 34: ...12 25 20 15 10 5 0 5 10 15 20 2 3 4 5 7 8 9 10 D0000090269 X Outside temperature C 2 Max W65 4 Max W45 7 Min W65 9 Min W45 Y Heating output kW 3 Max W55 5 Max W35 8 Min W55 10 Min W35 DHW output 0 2 4...

Страница 35: ...35 W18 partial load kW 3 37 4 94 Power consumption Power consumption at A7 W35 EN 14511 kW 0 61 0 61 Power consumption at A2 W35 EN 14511 kW 0 69 1 Power consumption at A 7 W35 EN 14511 kW 1 44 2 36 P...

Страница 36: ...48 148 IP rating IP 14B IP 14B Condenser material 1 4401 Cu 1 4401 Cu Dimensions Height mm 900 900 Width mm 1270 1270 Depth mm 593 593 Weights Weight kg 135 135 Connections Connection heating flow ret...

Страница 37: ...those subsidiaries Such guarantee is only grant ed if the subsidiary has issued its own terms of guarantee No other guarantee will be granted We shall not provide any guarantee for appliances acquire...

Страница 38: ...38 WPL A Premium www stiebel eltron com NOTES...

Страница 39: ...www stiebel eltron com WPL A Premium 39 NOTES...

Страница 40: ...TIEBEL ELTRON OY Kapinakuja 1 04600 M nts l Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 F...

Отзывы: