13. Maintenance and cleaning
If heat meters are installed, clean their strainers frequently as
they block easily.
When the heat pump operation is impaired (high pressure lim-
iter trips) through deposits of corrosion by-products (rust sludge)
inside the condenser, only dissolving them by means of solvents
used by our service department will remove this problem.
14. Troubleshooting
Note
Please observe the heat pump manager operating and
installation instructions.
Note
The following inspection instructions may only be carried
out by a qualified contractor.
If you cannot locate the fault using the heat pump manager, use
the controls on the IWS.
f
f
Open the control panel.
f
f
Read the following sections on troubleshooting and carry out
the instructions.
14.1 IWS controls
The IWS (integral heat pump controller) helps you to troubleshoot
if the fault cannot be identified using the WPM.
3
4
1
2
BA
BA
26
�0
3�
01
�1
426
1 LEDs
2 Reset button
3 DIP switch (type WP)
4 DIP switch (BA)
14.1.1 Checking the “HP type” DIP switch on the IWS
f
f
Check whether the “HP type” DIP switch (3) [marked WP-Typ]
is set as follows:
WP - Typ
ON
1
2
3
4
D
00000
57
05
8
If the appliance is to be used as a module together with a further
WPF..M, the DIP switch must remain in the same position.
14.1.2 DIP switch “BA”
These DIP switches have no function.
14.1.3 LEDs
Red LED
Fault
Cause
“ Remedy
Appliance stops and
restarts after the idle
period has expired. Red
LED flashes.
Heat pump fault
Check the fault message
in the WPM. Find the solu-
tion in the WPM instruc-
tions (fault list). Perform
an IWS reset (see WPM
instructions).
Appliance stops perma-
nently. Red LED illumi-
nates.
Five faults within two
hours compressor
runtime.
Check the fault message
in the WPM. Find the solu-
tion in the WPM instruc-
tions (fault list). Perform
an IWS reset (see WPM
instructions).
Green LED centre
The LED flashes during initialisation, and illuminates constantly
after the BUS address has been assigned successfully. Only then
is communication with the WPM established.
14.1.4 Reset button
If the IWS was incorrectly initialised, the settings can be reset with
this button. For this also observe the chapter “Reinitialising IWS”
in the heat pump manager operating and installation instructions.
Содержание WPF 10 M
Страница 1: ...OPERATION AND INSTALLATION BRINE WATER HEAT PUMP WPF 10 M WPF 13 M WPF 16 M WPF 7 MS WPF 10 MS ...
Страница 17: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 17 INSTALLATION Specification ...
Страница 31: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 31 CONTENTS Specification ...
Страница 32: ...32 WPF M WWW STIEBEL ELTRON COM CONTENTS ...