INSTALLATION
ELECTRICAL CONNECTION
9. Electrical
connection
WARNING:
Electrocution
Before beginning any work on the electric installation,
be sure that main breaker panel switches are "Off"
to avoid any danger of electric shock. All mounting
and plumbing must be completed before proceeding
with electrical hook-up. Where required by local,
state or national electrical codes the circuits should be
equipped with a "ground fault interrupter".
The unit must be properly grounded in accordance
with state and local codes, or in absence of such
codes, in accordance with national electric code or the
Canadian electric code. Failure to electrically ground
the product could result in serious personal injury or
death.
The Tempra should be connected to properly grounded dedicated
branch circuits of proper voltage rating. Ground must be brought
to the "Ground" at the circuit breaker panel.
9.1 Circuit
Layout
9.1.1 Tempra 12 Trend / Plus
OFF
ON
OFF
ON
26_02_02_0568
CKT 1
Tempra 12 Trend / Plus:
These units can be connected to a single circuit.
Use a supply cable protected by a double pole breaker.
9.1.2 Tempra 15, 20, 24 Trend / Plus
OFF
ON
OFF
ON
OFF
ON
OFF
ON
26_02_02_0568
CKT 1
CKT 2
Tempra 15, 20 or 24 Trend / Plus:
These units require two independent
circuits. Use two supply cables protected by two separate double
pole breakers.