3.1.14 Tube Collector Function

If the controller measures an increase of 4 °F compared to 
the collector temperature which was last stored, the solar 
pump is switched-on for about 30 seconds. After the solar 
pump is deactivated the current collector temperature is 
stored as new reference value. If the measured temperature 
(new reference value) is again exceeded by 4 °F, the solar 
pump again switches-on for 30 seconds. If the switch-on 
differential is reached during any of these processes the 
controller automatically switches over to solar charging.

If the collector temperature drops by 4 °F while the system 
fluid is stagnant, the switch-on value for the special tube 
collector function will be recalculated.

O TC:

 

Tube Collector Function   
Adjustment range: 
OFF / ON 

 

Factory setting: OFF

3.1.13 Recooling Function

This setting is designed to be used in conjunction with the 
System Cooling Function, which overrides the maximum 
store temperature (

S MX

) when used. This function will 

cool the tank back down to its maximum temperature when 
the collector temperature becomes low enough to facilitate 
such. This prevents a cumulative overheating condition if the 
cooling function needs to be used multiple days in a row. 
In order to utilize this function with tube collectors, a heat 
rejection loop (heat dump) is necessary. 

OREC:

 

Recooling Option 
adjustment range 
OFF / ON 

 

Factory setting: OFF

For control and service work the operating mode of the 
controller can be manually adjusted by selecting the ad-
justment value HAND, in which the following settings are 
available.

3.1.15 Circulator Pump Operating Mode

•  HAND

 

Operating mode 
OFF 

relay off 

 (flashing) + 

  

AUTO  : 

relay in automatic operation 

ON 

relay on 

 (flashing) + 

 

HAND:

Operating Mode 
Adjustment range:  
OFF/AUTO/ON
Factory setting: AUTO

3.1.16  Language

The menu language can be adjusted in this channel.

• 

dE  :  German

  En  :  English

•  It  :  Italian
•  Fr  :  French

LANGUAGE

Language Setting
A d j u s t m e n t   r a n g e : 
d E ,   E n ,   I t ,   F r 
Factory setting: En

3.1.17  Units for Temperature Display

The menu units can be adjusted in this channel:

• 

°FAH

  °CEL

UNIT:

Temperature Display Units
A d j u s t m e n t   r a n g e : 
FAH, CEL
Factory setting: FAH

Содержание SOM 6 SI

Страница 1: ...SOM 6 SI Thanks for buying this product Read this manual carefully to get the best perfomance from this unit SOM 6 SI Installation Configuration andTroubleshooting Manual manual...

Страница 2: ...ELTRON Inc Important notice Your own calculations and plans under consideration of the current norms and DIN directions should only be basis for your projects We don t offer a guarantee for the comple...

Страница 3: ...ing control lamp Operation by 3 pushbuttons in the front of the housing Functions Temperature differential controller with optional add on system funtcions Function control according to BAW guidelines...

Страница 4: ...s is 130 mm 4 Fasten the housing at its lower point 1 Installation Warning Switch off power supply before opening the housing 1 2 Electrical wiring The power supply to the controller must only be made...

Страница 5: ...ard solar system with 1 store 1 pump and 3 sen sors The sensor S4 TRF can optionally be used for energy production measurement R1 S3 Symbol Specification S1 Collector sensor S2 Lower tank sensor S3 Up...

Страница 6: ...r using keys 1 and or 2 The abbreviation for the parameter is displayed on the right side of the screen with the setting directly below and the set icon solid not blinking on the extreme right 2 Press...

Страница 7: ...xchanger Sensor Collector with collector sensor Pump Store 1 with heat exchanger Temperature sensor 2 2 3 System screen only system screen Constantly green Normal operation Red green blinking Power up...

Страница 8: ...ensor 3 Temperature 9 TRF Return Sensor Temperature 9 S4 Sensor 4 Temperature 9 h P x Operating Hours Counter 9 kWh Energy Production kWh 10 MWh Energy Production MWh 10 DT O x Switch On Temperature D...

Страница 9: ...eratures if applicable Shows the current temperature of the sensor TRF return flow temperature TRF Return Flow Tempe rature Display range 40 482 F 3 1 5 Operating Hours Counter h P Number of hours whi...

Страница 10: ...tion of the volume of heat exchanger fluid moved through the system and a comparison of the temperature of the fluid leaving the collector S1 with that of the fluid exiting the storage tank s heat exc...

Страница 11: ...ector Emergency Shutdown Temperature If the collector emergency shutdown temperature EM is reached the solar pump R1 is deactivated in order to avoid damaging the solar components The default setting...

Страница 12: ...This function will cool the tank back down to its maximum temperature when the collector temperature becomes low enough to facilitate such This prevents a cumulative overheating condition if the cool...

Страница 13: ...nction is activated OCN Minimum Collector Temperature p 11 Off The T between DT O and DT F achieves the requisite effect for most situations OCF Antifreeze Option p 11 Off Unless the system is located...

Страница 14: ...stead of the temperature SOM unit is sensing an open circuit condition Measure the resistance between the two terminals to which 1 the relevent sensor is attached If it measures infinite resis tance c...

Страница 15: ...age is close to the nominal voltage of 120VAC continue to step 2 If the voltage is not correct the problem lies with the power supply to the unit Remove the unit s can fuse and measure its resistance...

Страница 16: ...section 3 2 2 Make sure that all system components are properly insulated 3 Circulator pump is running collector is much hotter than store but the tank fails to heat up Make sure that the controller...

Отзывы: