INSTALLATION
Installation
18
| SB-VTI www.stiebel-eltron.com
9. Installation
9.1 Heat exchanger connection
f
f
Flush the indirect coil with water before connection.
9.1.1 Oxygen diffusion
!
Material losses
Avoid open vented heating systems and underfloor
heating systems with plastic pipes that are permeable
to oxygen.
In underfloor heating systems with plastic pipes that are per-
meable to oxygen and in open vented heating systems, oxygen
diffusion may lead to corrosion on the steel components of the
heating system (e.g. on the indirect coil of the DHW cylinder, on
buffer cylinders, steel radiators or steel pipes).
!
Material losses
The products of corrosion (e.g. rusty sludge) can set-
tle in the heating system components, which may re-
sult in a lower output or fault shutdowns due to reduced
cross-sections.
9.2 Installing the flanged immersion heater
(accessory) if required
Removing the blank flange
D
00000
82
22
4