background image

9

8) ELECTRICAL CONNECTIONS

INTERNAL CONNECTION WIRING DIAGRAM — Direct Spark Ignition

STERLING “RSG” SERIES 

INFRARED RADIANT TUBE HEATER         

Содержание RSG 25

Страница 1: ...RIES Chain Mounting Kit Thermostat Gas Pressure Regulator Gas Shut Off Valve Vent Cap Combustion Air Cap Other Other EQUIPMENT USED STERLING RSG SERIES INFRARED RADIANT TUBE HEATER RSGS 2 PROJECT UNIT...

Страница 2: ...t 10 feet above the upper surfaces of wings or engine enclosures of the highest aircraft that may be housed in the hangar and at least 8 feet above the floor in shops offices and other sections of han...

Страница 3: ...35 45 48 36 with deflector The clearance is 33 with deflector The clearance is 42 with deflector 30 side clearance with deflector NOTE 1 The clearances specified above must be maintained to combustib...

Страница 4: ...IGH AS POSSIBLE Minimums are shown as a guideline for human comfort and uniform energy distribution for complete building heating applications Consult your Sterling representative for the particulars...

Страница 5: ...5 4 DIMENSIONS STERLING RSG SERIES INFRARED RADIANT TUBE HEATER...

Страница 6: ...2 B Deflector Kit Part 43504010 The Deflector Kit is available for use to reduce the clearances to combustibles below the heater Refer to the Minimum Clearances to Combustibles Table in Section 2 whe...

Страница 7: ...be installed as shown above in one plane and without sharp bends kinks or twists CANADA ONLY A Type I hose connector should be used that is certified as being in compliance with the Standard for Elast...

Страница 8: ...ply pressure for purpose of input adjustment This appliance is equipped with a step opening combination gas valve The maximum supply pressure to the appliance is 14 W C or 1 2 P S I If the line pressu...

Страница 9: ...9 8 ELECTRICAL CONNECTIONS INTERNAL CONNECTION WIRING DIAGRAM Direct Spark Ignition STERLING RSG SERIES INFRARED RADIANT TUBE HEATER...

Страница 10: ...NECTION WIRING DIAGRAMS B LINE VOLTAGE 120V THERMOSTAT CONNECTIONS MULTIPLE HEATERS PER THERMOSTAT A LINE VOLTAGE 120V THERMOSTAT CONNECTIONS SINGLE HEATER PER THERMOSTAT STERLING RSG SERIES INFRARED...

Страница 11: ...riginal wire as supplied with the appliance must be replaced it must be replaced with wiring material having a temperature rating of at least 105 C 18 Ga CSA 600V Type TEW b When connecting the supply...

Страница 12: ...y observed A safety switch in the heater is designed to shut the heater off before excessive flue restriction causes bad combustion Refer to the Vent Sizing Table for maximum vent lengths and vent pip...

Страница 13: ...in the National Fuel Gas Code or the authority having jurisdiction 9 Single wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic inside w...

Страница 14: ...ing elbows in the first 5 feet of vent pipe whenever possible Limit the quantity of 90 elbows to two 2 When vent pipe is in a horizontal run it must be pitched downward 1 4 inch per foot towards the v...

Страница 15: ...eter should be no less than that shown in the following Vent Sizing Table b The connector length should be no more than 75 of the vertical portion of vent above the connector c Where possible use a Y...

Страница 16: ...ocated at the highest point above and in the vicinity of the heaters and the inlet vents must be located below the level of the heaters An exhaust hood Part 42924000 must be placed on the outlet colla...

Страница 17: ...l and heat exchanger lengths This is attached to the 4 diameter starting collar The starting collar is fitted to the top of the control box cabinet after first removing and discarding the perforated c...

Страница 18: ...18 STERLING RSG SERIES INFRARED RADIANT TUBE HEATER...

Страница 19: ...f operation for the normal operating cycle If the flame is not sensed during sequence T3 then the burner will automatically begin ignition sequence T2 If the flame is not re established the heater wil...

Страница 20: ...ing removal or reinstallation of the Product c To any damage due to corrosion by chemicals including halogenated hydrocarbons precipitated in the air d To any workmanship of the installer of the Produ...

Отзывы: