Water Supply 

Unlike other iron filters that do not use chemicals to oxidize the iron, the OXY3 iron filter does not require 
additional plumbing such as solenoid valves, pressure switches or pressure tanks.  This filter will function 
properly when the water supply is furnished by a jet pump, submersible pump, variable speed (constant 
pressure) pump or community water supply.  As with all other filter systems, however, it is imperative that the 
well pump provides enough flow rate for the filter to adequately backwash.  In order to ensure sufficient 
backwash flow rate the following pumping rate test should be performed prior to installing the iron filter. 

1.  Make certain no water is being drawn in the house. 

2.  Open spigot nearest pressure tank. 

3.  When well pump starts, close spigot and measure time (in seconds) to refill pressure tank (well pump 

turns back off).  This is 

Cycle Time

 

4.  Using a container of known volume, draw water from pressure tank and measure how many gallons 

until the pump turns back on again.  This is 

Draw Down

 

5.  Calculate pumping rate by dividing draw down by cycle time and multiplying by 60. 

 

Draw Down 

(gallons)

 

X  60 

Pumping Rate (gallons per minute) 

Cycle Time

 (seconds)

 

 
 

Example: 

Draw down is 8 gallons 
Cycle time is 65 seconds 

 

 

 

Location Considerations 

 

The proper location to install the OXY3 filter will ensure optimum filter performance and satisfactory 

water quality.  The following factors should be considered in selecting the location of the iron filter. 

1.  The filter should be installed after the pressure tank (private well system only). 

 

2.  The filter should be installed as close as possible 

(preferably within 15’) 

to an adequate floor or 

laundry drain capable of handling the backwash cycle volume and flow rate (refer to unit 
specifications). 

 

3.  All water conditioning equipment should be installed prior to the water heater.  Water temperatures 

exceeding 100°F can damage the internal components of the control valve and filter tank. 

 

4.  The filter should not be subject to freezing temperatures. 

 

5.  The filter should be installed before a water softener (if required). 

 

6.  Never install a cartridge type filter prior to the OXY3 iron filter.  Any cartridge or in-line filter (if 

desired) should be installed after the OXY3 filter.  This will prevent restricting the water flow and 
pressure available for backwash. 

 

7.  Appliances requiring extended periods of continuous or high flow water use (i.e. geothermal heat 

pumps, swimming pools, lawn irrigation, outside hose bibs, etc.) should bypass the filter and a 
spring check valve should be installed on the filter inlet to prevent backflow from the filter (see 
installation diagram Fig. 1).   

 

8.  An expansion tank may need to be installed in the line to the water heater in order to allow for 

thermal expansion and comply with local plumbing codes. 

8 gallons

 

  X  60  = 

7.4

 gpm  (gallons per minute) 

65 seconds

 

Содержание OXY3 Series

Страница 1: ...t 12630 US Highway 33 N Churubusco IN 46723 Phone 260 693 1972 Fax 260 693 0602 www sterlingwatertreatment com OXY3 Instruction Manual 112310 docx OXY3 Series Iron Reduction System Installation Instructions and Owner s Manual ...

Страница 2: ...turally exists in some water sources in either clear water ferrous state red water ferric state or bacterial form The OXY3 iron filter can reduce any of these forms of iron Manganese A naturally occurring metallic element Manganese concentrations as low as 0 05 milligrams liter mg l can combine with oxygen to cause dark brown or black staining on fixtures Additionally manganese can cause an odor i...

Страница 3: ...nsure optimum filter performance and satisfactory water quality The following factors should be considered in selecting the location of the iron filter 1 The filter should be installed after the pressure tank private well system only 2 The filter should be installed as close as possible preferably within 15 to an adequate floor or laundry drain capable of handling the backwash cycle volume and flo...

Страница 4: ...s Do not reinstall the fillport cap until Step 9 STEP 4 Place filter tank on right side with inlet outlet facing left Place aeration tank on left with inlet outlet facing right STEP 5 Attach the control valve assembly to the front inlet opening of the aeration tank and outlet opening of the filter tank Attach the straight pipe adapter to the back outlet of the aeration tank and inlet of the filter...

Страница 5: ...r less AVOID OVERHEAD DRAINS STEP 9 Use a garden hose or bucket to fill the media tank with water through the fillport Ensure media has been cleaned from fillport threads and install cap securely with wrench provided STEP 10 Be sure the control valve is in the Service position refer to timer operation for instructions The bypass valve should be in the Bypass position Open main supply valve or turn...

Страница 6: ...he metal tabs outward on the desired days of regeneration The OXY3 Filter should be set to backwash a minimum of every third day Ensure the filter does not backwash for the first two days of operation to prevent media from being backwashed to the drain How to Manually Initiate a Backwash Cycle 1 Grab the manual regeneration knob and turn clockwise 2 The drive gear will engage the program wheel and...

Страница 7: ... pins does not decrease air draw time 4 AIR DRAW cycle may be lengthened by increasing the number of holes between the two sets of pins Each hole represents 2 minutes of air draw time The air draw time should only be increased by moving the backwash pins to an earlier point on the program wheel Ensure that lengthening the air draw time does not decrease either the backwash or rapid rinse times 5 R...

Страница 8: ...7 Control Valve Wiring ...

Страница 9: ...pm Backwash 5 0 5 0 7 0 9 0 10 0 Air Draw and Slow Rinse 0 9 0 9 0 9 0 9 0 9 Rapid Rinse 5 0 5 0 7 0 9 0 10 0 FACTORY REGENERATION SETTINGS Backwash minutes 8 8 8 8 8 Air Draw Rinse minutes 14 14 14 14 14 Rapid Rinse minutes 8 8 8 8 8 Total Water Used gallons 93 93 125 157 173 DIMENSIONS in Mineral Tank diameter x height 10 x 54 10 x 54 12 x 48 14 x 65 16 x 65 Overall length x width x height 24x 1...

Страница 10: ...9 Component Parts Breakdown A B C D 2 8 9 1 3 4 5 6 9 7 5 ...

Страница 11: ...des backtube assy for OXY3 30 and OXY3 40 2 CD1400 Distributor Head 3 CD1220 01 Distributor Head w Fillport 4 D100S 54 Distributor Tube 1 x 54 OXY3 10 OXY3 15 D100S 48 Distributor Tube 1 x 48 OXY3 20 D100S 65 Distributor Tube 1 x 65 OXY3 30 OXY3 40 5 MTP1054N Mineral Tank 10 x 54 OXY3 10 OXY3 15 MTP1248N Mineral Tank 12 x 48 OXY3 20 MTP1465N Mineral Tank 14 x 65 OXY3 30 MTP1665N Mineral Tank 16 x ...

Страница 12: ...11 Control Valve Breakdown ...

Страница 13: ... H FV2510 1PH Powerhead Assembly 2510 TC 18 18303 Tank O Ring 2510 Valve I 60050 21 Drive Motor Assembly 19 13304 Distributor O Ring 121 J 60160 10 Drive Cam Assembly STF 20 13030 Distributor Retainer K 60304 13 Timer Assembly 3200 12 Day STF 120 60 21 40027 J tube for 2510 valve 1 14105 Bypass Valve Seal Single Lever 22 13911 Main Drive Gear 2 13305 Coupling O Ring 019 23 18743 1 Timer Motor 120v...

Страница 14: ...13 ...

Страница 15: ...14 ...

Страница 16: ...r malfunction occur contact the dealer that you purchased the product from If you are unable to contact the dealer contact First Sales LLC 260 693 1972 We will require a full description of the problem model number date of purchase and selling dealer s business name and address We assume no warranty liability in connection with this water conditioner other than specified herein This warranty is in...

Отзывы: