background image

– 20 –

START-UP (continued)

FINAL CHECKOUT

Run the unit  sequentially through its stages of heating.
One proper unit operation is verified, perform these final
steps:
1.

Inspect the unit for debris and/or misplaced tools
and hardware.

MAINTENANCE

 Open all disconnect switches and

secure in that position before servicing unit.
Failure to do so may result in personal injury or
death from electrical shock.

Rooftop duct furnaces have been developed for
outdoor installation. Should maintenance be required,
perform the following inspection and service routine:
Inspect area near the unit to be sure that there is no
combustible material located within minimum
clearance requirements (refer to Figures 1, 2 and 6).
Service panels provide easy access to the burner
controls. To remove the service door, refer to “Access
Panel Removal” section (at the beginning of this
manual).

The pilot burner can be serviced by removing the  pilot
plate from the main burner assembly.

To remove the main burner drawer assembly for
servicing the burners, proceed as follows:
1.

Shut off the main gas valve and electrical power to
the gas duct furnace.

2.

To slide out the burner drawer, the following two
procedures (a or b) may be chosen depending on
the complexity of the unit's controls:
a.) Disconnect the pilot burner gas tube. Break

the union between the automatic gas valve
and the burner manifold. Also break the union
on the discharge air end of the furnace (inside
the unit). Loosen the union located directly
outside of the furnace's bottom panel (refer to
figure 9b). Swing down this end of the piping
to clear the bottom of the burner drawer. The
control and piping assembly may be tied out of
the way of the pull-out drawer.

b.) Disconnect all wiring to the unit's controls.

Break the union located in the discharge
end of the furnace; loosen the external union,
and swing piping clear of the bottom of the
drawer (same procedure as a).

3.

Remove the locking screws holding the burner
drawer in position.

4.

Slide the drawer out of the furnace.

5.

Burners can be removed from the drawer by
raising the front of the burner and pushing it
against the hold-in spring until the front of the
burner comes out of the slot.

2.

Disable air handling blower. Fire unit and confirm
that high limit switch shuts gas off within
approximately 5 minutes. Re-enable   air handling
blower.

3.

Be sure all gas valves and controls are in the
operating position if the unit will be operating
immediately

4.

Secure all exterior panels in place.

6.

To clean or replace the main burners, slide out the
pullout drawer, and compress the spring by
moving the burner toward the manifold. Slide the
opposite end of the burner downward from the
locating slot while retaining spring is still
compressed. Pull the burners upward and out.

7.

Remove any dirt, dust or other foreign matter from
the burners using a wire brush and/or compressed
air. Ensure that all parts are   unobstructed.  Inspect
and clean pilot burner if necessary.

8.

Reassemble the gas duct furnace by replacing all
parts in order.

9.

Complete the appropriate unit start-up procedure
as given in the “Start-Up” section of this manual.

10. Check the burner adjustment. See the “Primary Air

Shutter Adjustment” section of this manual.

11. Check all gas control valves and pipe connections

for leaks.

 Under no circumstances should

combustible material be located within the
clearances specified in Figure 6. Failure to
provide proper clearance could result in
personal injury or equipment damage from fire.

12. Check the operation of the automatic gas valve by

lowering the setting of the thermostat, stopping the
operation of the gas duct furnace. The gas valve
should close tightly, completely extinguishing the
flame on the main burners.

13. Check the operation of all safety devices.
14. Inspect and service the blower section of the

system.

The outdoor unit should be thoroughly checked before
the start of the heating season. Check the air through-
put as an added precaution to stay within the specified
temperature limits.

If the unit is used with cooling equipment, periodic
maintenance should be scheduled throughout the
year.

Содержание outdoor rooftop gas-fired duct furnace

Страница 1: ...e units are certified by CSA International for operation on either natural or propane gas Read this manual and all labels attached to the unit carefully before attempting to install operate or service...

Страница 2: ...h clockwise The screw must turn freely one quarter turn before resistance is felt in order for the lock to engage If the latch does not hold turn the screw counter clockwise several turns and repeat t...

Страница 3: ...kit contains insulated curb rails hardware sealant self adhering rubber gasketing and installation instructions Roof insulation cant strips flashing roof felts caulking and nails must be furnished by...

Страница 4: ...1156 1326 40 60 3 8 45 13 16 26 17 1 2 26 11 16 51 57 11 16 3 4 1 2 OR 3 4 1534 1164 660 445 678 1295 1465 NOTE DIMENSIONS ARE IN INCHES DIMENSIONS IN PARENTHESIS ARE IN MILLIMETERS F DIMENSION IS TH...

Страница 5: ...4 603 17 50 0 50 984 184 198 100H 100 000 80 000 80 1 235 3 704 20 60 2 7 1 8 1 2 1 2 199 218 29 3 23 4 0 583 1 748 11 33 0 50 181 90 99 150H 150 000 120 000 80 1 852 5 556 20 60 2 11 1 4 1 2 1 2 226...

Страница 6: ...er 1 Select heater size based on heat loss of the building to be heated 2 Select temperature rise desired 3 Based on temperature rise the horizontal line inter sects heater temperature vs CFM curve 4...

Страница 7: ...t factory furnished and must be built on the job by the installer and a damper placed therin if required USE OF BYPASS CURVES The width of the by pass for CFM in excess of that provided through the he...

Страница 8: ...ications See figures 1 2 and charts 1 2 D3589 D3589A 18 457 5 16 8 Ductwork Natural or Power Vent Furnace Air Flow 5 16 8 18 457 18 457 36 914 36 914 Clearance For Drawer Pul out 18 457 5 16 8 Typ Duc...

Страница 9: ...d be produced Figure 7 Vent Cap Assembly Natural Vented Furnaces Only FIELD INSTALLATION INSTRUCTIONS 1 Remove Side Access Panel 2 Insert Vent Sleeve of Vent Cap Assembly Item 1 thru Top Panel Assembl...

Страница 10: ...de The location of this valve must comply with the local codes A 1 8 inch N P T plugged tapping accessible for test gauge connection must be installed immediately upstream of the gas supply connection...

Страница 11: ...for Determining Pipe Size GAS METER A 20 ft 6 56 m 20 ft 6 56 m 5 ft 1 64 m 5 ft 1 64 m 10 ft 3 48 m B C D F E 10 ft 3 28 m HEATER S 200 CFH HEATER S 150 CFH 3588 HEATER S 100 CFH D3588 NOTICE If more...

Страница 12: ...00 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280 78 311 218 177 150 135 122 110 105 97 7 92 0 83 5 75 0 69 4 64 6 4 4 026 23000 15800 12800 10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600...

Страница 13: ...D 3 AIR SHUTTERS 4 BURNER SPRINGS 5 MAIN BURNER ORIFICE 6 TRANSFORMER 7 PILOT TUBING CONTROLS 8A MAIN GAS VALVE HONEYWELL 8B MAIN GAS VALVE WHITE RODGERS 9 HONEYWELL IGNITOR 10 HONEYWELL PILOT BURNER...

Страница 14: ...iring diagram GAS CONTROLS SINGLE STAGE CONTROL Gas heating units are factory provided with an automatic single stage gas valve This valve is an on off type control typically activated by a low voltag...

Страница 15: ...int 1 2 3 4 5 6 7 8 9 60 100 F 60 65 70 75 80 85 90 95 100 75 200 F 75 91 106 122 138 150 NA NA NA NA Maximum furnace discharge temperature allowed 150 F The unit is also provided with an automatic el...

Страница 16: ...ased voltage closes a relay which closes the automatic gas valve 9 When the thermostat is satisfied the main and pilot valves close 10 The fan time delay relay remains closed keeping the fan motor ope...

Страница 17: ...fire If cycling on the high limit is noted corrective measures should be taken immediately Failure to do so could cause unit damage and possible fire The unit is furnished with an intermittent pilot i...

Страница 18: ...the National Fuel Gas Code ANSI Standard Z223 1999 N F P A no 54 or the latest edition When installed in Canada any references to deration at altitudes in excess of 2000 feet 610m are to be ignored At...

Страница 19: ...ization range 5 Inspect the interior of the unit remove any debris or tools which may be present START UP STARTING UNIT IN HEATING MODE 1 Close the unit disconnect switch s that provide current to the...

Страница 20: ...er in position 4 Slide the drawer out of the furnace 5 Burners can be removed from the drawer by raising the front of the burner and pushing it against the hold in spring until the front of the burner...

Страница 21: ...21 Figure 13 Natural Vent Duct Furance Figure 14 Power Vent Duct Furnace...

Страница 22: ...ng for heat 4 Defective limit switch 5 Improper thermostat or trans former wiring at gas valve 6 Defective gas valve 7 Defective thermostat CORRECTIVE ACTIONS 1 Inspect all gas piping and repair 2 Cle...

Страница 23: ...hen check for 24 volts at secondary terminal before replacing 9 Check and tighten all wiring connections 10 Replace 1 Reset manifold pressure Refer to operation 2 Replace regulator section of combinat...

Страница 24: ...3 Clean flue Refer to installation 4 Determine cause and repair accordingly Refer to installation 1 Relocate thermostat away from drafts 2 Replace thermostat 3 Check wiring diagrams 4 Check operation...

Страница 25: ...MPTOMS N Too much heat P Power venter motor will not start Q Noisy power venter R Power venter will not run S Power venter motor will not stop CORRECTIVE ACTION 1 Replace thermostat 2 a Check wiring p...

Страница 26: ...or neglect has been accidentally or intentionally damaged has not been installed maintained or operated in accordance with the furnished written instructions or has been altered or modified in any wa...

Страница 27: ...l field installed controls been installed Do you understand all the controls on this equipment DO NOT START this equipment unless you fully understand the controls GENERAL With power and gas off Make...

Страница 28: ...http www mestek com 260 NORTH ELM ST WESTFIELD MA 01085 TEL 413 564 5540 FAX 413 562 5311 HVAC PRODUCTS...

Отзывы: