Sterling Power Pro Batt Ultra BB122470 Скачать руководство пользователя страница 13

Sterling Power Products

Copyright 

Sterling Power Products

H Charge

Float

In / Unit

Out / Rem

Batt.

V

12.2

Temp
Menu

Change

Volts

Select

Audible alarm on/off 

hold > 3 sec

On / Off

hold>3 sec

Fault

Absorption

Cond.

menu 

scroll

(unidirection)

6

7

5

1

2

3

4

8

9

Volts Select Button (left)

Quick push = back light on.
Short press ~1 second = input 
voltage, press again for output 
voltage, press again for remote 
sense voltage.

Hold for 4 seconds to toggle 
between buzzer on/off, 

bu2

 

should appear. 

Remote control: 

cut hole diameter 
54mm

1) Volts select button.
2) Voltage displayed is voltage into product.
3) LCD screen with backlight.
4) Fast charge led indicator. 
5) Condition battery stage. 

Temp  Menu  Change  (right 
button)

Quick press = back light on.
Short hold ~1 second = switch 
between  unit’s  temperature 
and temperature sensor. If 

nc

 

appear  it  means  that  the 
temperature  sensor  is  not 
connected. 

Hold  for  2  seconds  to  toggle 
night mode on / off, 

nn

 should 

appear. 1/2 power for 8 hours.

Hold  button  for  4  seconds 
to  enter  the  Setup  Menu  - 
“rt” shall appear.

3

3

Both Left and Right buttons

Hold both buttons for 2 seconds 
to force to float 

FtF

, toggle on / off.

Press and hold both buttons for 4 
seconds to enter standby mode, 

Stb 

should appear. Repeat to turn 

unit on.

Press and hold both buttons for 6 
seconds to turn unit off. 

oFF 

shall 

appear. Repeat to turn unit on.
 

Volts

Select

Volts

Select

 Temp

Menu

Change

Then the actual value. Press “change” button to increase value. 
Hold “change” button to accelerate. When max. value reached 
it will start with lowest value. Press “select” again to confirm 
setting. Press “change” button to increase value. Hold “change” 
button to accelerate. When max. value reached it will start with 
lowest value. Press “select” again to confirm setting. 

“b9b”

  change  voltage  from  green  to  blue  backlight   12.4  - 

*

16.0V (default 13.4V). Press “select” .First the lowest and the 
hightest value will be displayed. Then the actual value. Press 
“change”  button  to  increase  value.  Hold  “change”  button  to 
accelerate. When max. value reached it will start with lowest 
value. Press “select” again to confirm setting.

“Led”

   change LED on time   1 - 600 seconds, 0 = always on, 

(default = 60). Press “select” .First the lowest and the hightest 
value will be displayed. Then the actual value. Press “change” 
button to increase value. Hold “change” button to accelerate. 
When max. value reached it will start with lowest value. Press 
“select” again to confirm setting.

“uId”

 display Unit ID. Press “select”. Value will be displayed for 

5 sec.

“uSW”

 display unit software version. Press “select”. Value will 

be displayed for 5 sec.

“rSW”

 display remote software version.  Press “select”. Value 

will be displayed for 5 sec.

“Loc” 

 Unit lock code = 1 to 999 (default = 00 = unlocked). 

WARNING

 This mode shall lock menu setting options of the 

unit by virtue of a pass code, be careful. Press “select” to enter 
“Loc” setting. Press “change” button to increase value, hold to 
accelerate. Stop when on the number you require and press 
“select” button to confirm. The software shall store this number, 
then the display shall read: 

loc

 -> on -> #. # = number you have 

stored. To remove 

loc

, return to 

loc

 and re-enter the number, 

Press “select” button   and the display should read: 

loc

 -> off 

(green  back  light). 

Please  make  a  note  of  this  loc  code 

here:_______

.

“rSt” 

Resets remote to default values*. Press “select”. “NO” 

will be displayed. Press “change” to toggle between “YES” and 
“NO”. Confirm by pressing “select”. rSt will display if resetting.

“rSu”

  Resets  the  battery  charger  to  default  settings.  Press 

” “NO”

select . 

  will  be  displayed.  Press  change   to  toggle 

between  YES  and 

“NO” Confirm by pressing “select”. rSt will 

display if resetting.

“rt”

 

displays  remaining  absorption  or  conditioning  time 

Press “select” button to see value.

“btY”

  displays  battery  profile  type  (0-9).  This  number 

denotes which charging profile the charger is set to. Press 
“select” to see value. (Ref: table labelled ‘Battery Chemistry 
Selection’ on).

“coU”

 displays input cut off voltage (the voltage at which the 

unit stops charging) (13.4V). Press “select” to see value.

“IoU” 

display input / output base voltage (12/24V). Press 

“select”. First input voltage will be displayed with “in” LED on 
for 3 sec. then output voltage with “out” LED on for 3 sec.

 change from celcius to fahrenheit or back  (default = 

“C/F” 

*

celcius). Press “select” button to enter setting. Then press 
right  button  to  change  between  Fahrenheit  (FAH)  and 
Celsius (CEL). Confirm setting by pressing “select” button.

“CL” 

set current limit to 1/2 or 1/1 (full). Press “select” button 

to  see  actual  setting.  Press  “change”  (right)  button  to 
change setting. Press “select” to confirm setting.

“buC”

 turn Buzzer on / off  (default = on). Press “select” to 

*

see  actual  setting.  Press  “change”  button  to  change 
between  settings.  Press  „select“  again  to  confirm  setting

 Autoscroll on  / off (default = off). Press “select” to see 

“Asc”

actual  setting.  Press  “change”  button  to  change  between 
settings. Press “select” again to confirm setting.

“Von” 

 Voltage / temp display during standby and sleep. 

Toggle between on and off, press “select” (left) button to 
select.

“con” 

  change  contrast   value  from  0  to  7  (default  =  3). 

*

Press “select”. First the lowest and the hightest value will be 
displayed. Then the actual value. Press “change” button to 
change  settings.  Press  “select”  again  to  confirm  setting. 

change backlight colour . off <- auto -> green -> red -

“bLc”  

*

> blue (default = auto). Press “select” to see actual setting. 
Press “change” button to change between settings. Press 
“select” again to confirm setting

“bLt”

 change backlight time . 1 - 600 seconds, 0 = always 

*

on, (default = 60). Press “select”. First the lowest and the 
hightest value will be displayed. Then the actual value.

“br9”

 

change remote display colour red to green voltage 

threshold.*

 8.0V-13.3V (default 12.4V). When below 12.4V 

display is red and when 12.4V or above the remote goes 
green. When Press “select”. First the lowest and the highest 
value will be displayed. 
    

6) Charge complete on float.
7) Voltage displayed is volts out of product. 
8) Scroll menu button. 
9) Screen display showing a unit fault.

 Temp

Menu

Change

 Temp

Menu

Change

Setup - Menu:

Toggling is unidirectional 

to escape menu hold both buttons down until ‘END’ 
appears. Or, just leave the remote for 10 seconds.

Remote Error Codes
E00 

= high input voltage

E01

 = high output voltage

E02

 = high unit temp

E03

 = high batt. temp

E04

 = no output voltage

13

 Remote Control

Содержание Pro Batt Ultra BB122470

Страница 1: ...nsor USERS MANUAL Sterling Power Products H Charge Float In Unit Out Rem Batt V 12 2 Temp Menu Change Volts Select Audible alarm on off hold 3 sec On Off hold 3 sec Fault Absorption Cond Optional Remo...

Страница 2: ...e Unit on off Display annotations Page 4 5 Force Unit to half pow er mode Front Label display annotated Sleep timer Off timer adjust Under the lid annotation Custom Battery Profile Selection Pages 11...

Страница 3: ...rrent limiting With fuses protecting the DC cables In a well ventilated dry dust free and condensation free environment When instruction manual has been read through Safety Symbols Example WARNING Nev...

Страница 4: ...r bottom red LED is on then the voltage is outside the parameters off the voltmeter 16 High voltage if on solid it is high output voltage if flashing it is high input voltage 10 11 13 8 9 7 6 5 4 3 12...

Страница 5: ...ed Models BB1260 BB122470 BB123670 BB124870 BB242435 BB241235 Models BB1230 BB122440 Front Panel II 8 1 2 3 4 6 7 10 11 12 13 9 5 14 5 3 4 1 6 BB122470 BB123670 BB124870 BB1260 BB242435 BB241235 4 60...

Страница 6: ...on default setting if temperature sensor not fitted Ignition Force mode For true ignition on off mode the Link should be removed As soon as there is a signal 4V on this connector the unit will wake u...

Страница 7: ...UP SELECT to toggle between types Both to confirm 20 30 Change operational on off voltages use both buttons to scroll between voltages 30 Reset unit to default press and hold both buttons for 2 second...

Страница 8: ...gger voltages only a 10V 20V at 24V low voltage trip With the link wire connected and the ignition feed connected the BB shall operate when the ignition is live However it shall also operate when ther...

Страница 9: ...old both buttons for 30 seconds and let go The LED columns shall alternatively flash To confirm factory default press BOTH buttons again for 2 seconds Once confirmed 3 green LEDs on both columns shall...

Страница 10: ...hen falls below 13 0V x2 for 24V the auto regen timer starts to count If the voltage does not rise above 13 2V the timer will not reset and the unit will switch off however as soon as the voltage rise...

Страница 11: ...s ________ Absorption Maximum 0 960 minutes ________ STERLI G POWER Operation Press and hold both buttons for 10 20 seconds All Left LEDs shall flash Press the setup select button to move LED down to...

Страница 12: ...ck mode constant voltage full current accessibility Stage 4 Backlash voltage If charger power exceeded and battery discharge unit resets to stage 1 Stage 5 Time Depending on battery size type state of...

Страница 13: ...e display shall read loc on number you have stored To remove loc return to loc and re enter the number Press select button and the display should read loc off green back light Please make a note of th...

Страница 14: ...ltage is 0 13V starter battery voltage then alternator may have failed Or requires increase rpm of engine possible belt slip Is your output voltage slightly higher or lower than expected even with no...

Страница 15: ...does not apply for shipping organised by yourself Please do not throw out any shipping or packaging materials All returns for any reason will require a proof of purchase with the purchase date The pr...

Страница 16: ...eitshinweise und allgemeinen Bedingungen Auch empfehlen wir Ihnen die Installation durch einen Fachbetrieb durchf hren zu lassen Bestell Nr BB1230 12V 12V 30A BB1260 12V 12V 60A BB122470 12V 24V 70A B...

Страница 17: ...Deckel Techn Daten Emfpohlene Kabelst rken und Sicherungen Schnell Installationshilfe Seite 6 Standard Anschluss Skizze Basis Operations Modus Ausf hrliche Installationshilfe Seite 7 8 Installations D...

Страница 18: ...n Sicherheits Symbole Beispiel WARNUNG Benutzen Sie das Produkt niemals in Umgebungen wo die M glichkeit einer Gas oder Staub Explosion besteht oder brennbare Produkte sind Generelle Wartung und Repar...

Страница 19: ...len Batterietyps dienen die LEDs zur Anzeige des Wertes Status und Fehleranzeigen 16 berspannung Zu hohe Eingangsspannung blinken zu hohe Ausgangsspannung an 10 11 13 8 9 7 6 5 4 3 12 14 15 16 17 18 2...

Страница 20: ...m 5m Empf Sicherung 30A Ger t 6mm 10mm 16mm 16mm 25mm 50A 60A Ger t 16mm 25mm 25mm 35mm 35mm 100A Technische Daten bei 24V x2 36V x3 48V x4 Max Eingangsspannung 20V Spannungs Arbeitsbereich 11 19V Aus...

Страница 21: ...g entladen wird Automatische Aktivierung und bei Signal eingang mit tiefer Eingangsspannunsregelung Dieses ist eine Kombination der Modi 1 und 3 Automatik und zus tzlich bei Signaleingang bis zu 10V E...

Страница 22: ...ES SIGNAL z B Z ndung 7 F r 24V alle Spannungen x 2 f r 36V alle Spannungen x3 und f r 48V alle Spannungen x4 Installationsanleitung 1 3 Direktaktivierung ber externes Signal und sehr tiefe Eingangssp...

Страница 23: ...ngs und Ausgangskabel an den Kabelklemmen 5 3 an Achten Sie darauf dass die Kabel entsprechend abgesichert sind Nachdem beide Kabel angeschlossen sind verbinden Sie das Ausgangs Ladekabel mit dem Posi...

Страница 24: ...en LEDs 16 24 Es gilt die gr ne Spannungsspalte Einstellung und Abschluss wie 8 10 8 13 Ausgleichsladungszeitfaktor ausw hlen Dieser Faktor bestimmt die berechnete Zeit der Aus gleichsladung Dabei wir...

Страница 25: ...Enter Select Das Ger t kann hiermit in den Werk Auslieferzustand zur ckgesetzt werden Alle linken und rechten LEDs blinken abwechselnd Innerhalb von 10 Sekunden muss diese Aktion durch gleichzeitiges...

Страница 26: ...ns nicht aktiv Nach 8 Std oder durch Standby oder im Schlafmo dus schaltet das Ger t automatisch wieder zur ck 9 13 Standby ein aus 5 Sekunden Select Durch Dr cken der Select Taste f r mehr als 5 Seku...

Страница 27: ...chaltet worden Leuchtet die LED ist das Ger t entweder aktiv in den 1 2 Leistungsmodus geschaltet worden oder die Lei stung wurde aufgrund einer zu hohen Ger tetempe ratur 85 C reduziert In diesem Fal...

Страница 28: ...annungen und Zeiten W hlen Sie dann den Batterietyp welcher den Empfehlungen am N chsten ist Aber immer von den Spannungen nach Unten am N chsten Z B empfiehlt der Hersteller 14 5V muss ein Batteriety...

Страница 29: ...sGer tnichtimSchlafmodusist Wichtig Ist das Ger t mit der Fernbedienung ausgeschaltet worden geht es zwar in den Schlafmodus wenn die Eingangsspannung abf llt steigt die Spannung wieder an Motor wird...

Страница 30: ...bLt Zeit der Hintergrundbeleuchtung 1 600 Sekunden 0 st ndig an Standard 60 br9 Farbwechsel Spannung von rot zu gr n 8 0 13 3V Standard 12 4V b9b Farbwechsel Spannung von gr n zu blau 12 4 16 0V Stand...

Страница 31: ...Sicherungen funktionieren und nicht durchgebrannt sind Auch Korrosion kann erheblichen Einfluss auf den Stromfluss haben Ein und Ausschalten des Ger tes mit einer Pause von mindestens 10 Sekunden kom...

Отзывы: