If on start up nothing happens,

Auto pause switch off.

WHAT CABLE TO USE IN mm sq
A charger or inverter up to        cable run distance 0-1.5 mtr           1.5  4 mtr
          0-25 amps                                 6 mm sq                                      10 mm sq
        25-45 amps                               16 mm sq                                      25 mm sq
        45-85 amps                               25 mm sq                                      35 mm sq   
      85-125 amps                               35 mm sq                                      50 mm sq
   125- 180 amps                               50 mm sq                                      70 mm sq
    180-330 amps                               70 mm sq                                      90 mm sq 
Please note that if there is a problem obtaining for example 90 mm sq cable, simply
Use 2 x 50 mm sq , or 3 x 35 mm sq , the cable is simply copper, and all you require
Is the copper , it does not matter if it is one cable or 10 cables as long as the square 

a

rea adds up.   Performance of any product can be improved by thicker cable, so if in doubt round up 

 then 

1) 

test the battery voltage. It should be above 11 volts, to see the unit working start up the engine and ensure you are 

getting at least 13.5 volts at the battery.

 The units has a automatic program cycle which works 3 minuets off and 20 minuets on etc etc  

until the batteries are charger, this cycle is to ensure the engine start system is well looked after and is bias in the engine 
starter battery's favour. If you wish to remove the 3 minuet rest period ( which is o.k. and the engine start battery will be 
o.k., then simply push button 1 and 2 at the same time ( this can only be done on the remote ) bold the two buttons until 
you hear a beep, the screen will then say auto pause off. this will auto reset on system restart.

The LED meanings and functions fig8

 

BATTERY TYPE 

Tri Coloured LED: This simply displays the battery type that the processor has been set to. This is a 

tri coloured LED. Yellow = open lead acid, Green = gel /sealed lead acid . Red = AGM..

 

ALT OVER TEMP 

: Yellow: This monitors the temperature of the alternator and disengages the unit in the event of 

the alternator reaching 90 deg C, which waits for the alternator to cool down then automatically re-engages. 

 

CONSTANT CURRENT:

 Green: This should be on from start up( slow flash shows unit on but on rest mode, for the 

first 2.5 min. On start up and approx. every 20 min after, see graph  ) and shows that the alternator should be working 
at it’s maximum. It should remain on until the green float  comes on and this  shows the high charge rate is complete.

 

TIMER ON 

: Yellow: Timer Activated: This comes on, when the voltage reaches about 13.9 - 14 volts ( x 2 for 24 v ) 

and depending on how long it took to come, will dictate how long the timing cycle will remain on. The software will 
calculate the timing for the high charge rate. This will vary from 1 - 6 hours and the time will be displayed on the 
remote panel and a count down . This light will remain on until the high charge rate is over, and will go out at the 
same time as the high charge rate between 1-6 hrs after activation.

 

FLOAT: 

Green Float Mode: This indicates that all the high charge cycles are now over and should remain on after all 

the high charge lights are out. The system is now running at a standard charge rate only (about 14 volts) regulated on 
the battery.

 

BATTERY INPUT OVER VOLTS

: This will warn you and switch off the boost section, this means that your 

alternators own regulator has failed and the alternator will now boil and destroy your batteries, there is simply nothing 
we can do about this except warn you:

a

o

t

 

 

BATTERY INPUT LOW  VOLTS 

 yellow:  Low Voltage Warning: This is simply saying that there is a low voltage at 

the main battery bank and has no active function. For information only, this usually indicates a defective alternator

 

BATTERY OUTPUT  OVER VOLTS:

 This will warn you and switch off the boost section, this means that either out 

unit has failed and was in the process of overcharging your battery bank, or you have some other charging source on 
your output battery bank which is overcharging the batteries and our unit thinks it is out unit 

 

BATTERY OUTPUT LOW  VOLTS 

 yellow:  Low Voltage Warning: This is simply saying that there is a low 

voltage at the output battery bank and that the charing unit is unable to keep up with your demand on the battery bank, 
or the unit has failed and is not working.

please take this warning very seriously  nd stop your engine as so n as possible, remove the alternator input cable 

hen continue your journey and have the alternator repaired.

14

14

14

14

15

15

15

15

16

16

16

16

17

17

17

17

18

18

18

18

19

20

21

22

Содержание BATTERY-to-BATTERY CHARGER

Страница 1: ...Instructions manual Installations und Bedienungsanleitung BB121250 BB122430 REMOTE CONTROL OPTION ORDER NO BBDRC Battery Battery Charger Sterling power products CE on off 1 2 3 4 light alarm alarm Ala...

Страница 2: ...11 12 13 fig 8 NON SEALED LEAD ACID OR TRACTION LED YELLOW GEL EXIDE SPEC LED GREEN GEL USA SPEC LED OFF SEALED ACID AGM LED ORANGE ON 1 2 ON 1 2 ON 1 2 ON 1 2 BATTERY TYPE SELECTOR SWITCH SETTINGS S...

Страница 3: ...ng split charging system ie a bow thruster battery bank The dotted line shows the original system and how simple it is to connect the d c battery charger Standard simple installation for auxiliary cha...

Страница 4: ...stem o k 2 1 3 4 InBat v 13 7v Current 38A 20min ON 17min CHARGE BATTERY IN 13 7V 38A BATTERY OUT 14 2V 31A in 13 7V 23A out 14 4V BULK Remote control panel A B C fig 5 fig 6 WET OPEN BULK CHARGER Cas...

Страница 5: ...ruster then 2 of these can be used to run the bowthruster and the domestic system There internal programs will adjust their charger patterns to accept the other unit Ensure only the excess power is us...

Страница 6: ...unit senses all the control voltages at the unit however if you want to sense the voltage at the domestic battery direct to over come the voltage drops in the cable run drops then simply connect a ca...

Страница 7: ...s that the alternator should be working at it s maximum It should remain on until the green float comes on and this shows the high charge rate is complete TIMER ON Yellow Timer Activated This comes on...

Страница 8: ...bank by charging with as many other auxiliary charging systems as you can For example if you are running a gen set for 4 hrs per day you may as well put as much power as possible into your main large...

Страница 9: ...the temperature sensors are not fitted it will default to 20 deg C Temp 4a b There are 2 x screens on this button Push once for screen a then again for screen b Screen b shows the box heat sink tempe...

Отзывы: