Selection of dimmer location
The dimmer must be mounted on a connection
box on a wall at around 1.5 m (5 feet) above the
floor level, on a section of the wall exempt from
pipes or air ducts.
Dimmer mounting and connection
1.
Cut off power supply on lead wires at
the electrical panel in order to avoid
any risk of electric shock.
2. Ensure that the air vents of the dimmer are
clean and clear of any obstruction.
3.
Make the required connections using
the solderless connectors. Refer to the
following diagram. For connections with
aluminum wires, you must use CO/ALR
connectors. Please note that the dimmer
wires have no polarity, which means that
any wire can be connected to the other.
Make sure that line voltage (120 VAC, 208
VAC, or 240 VAC) is present. No other device
may be installed between this dimmer and the
power supply (such as a thermostat).
4. Using a screwdriver, loosen the screw at the
bottom of the dimmer. Separate the two parts
of the dimmer by lifting up the bottom.
5. Align and secure the back of the dimmer to the
connection box using the two screws supplied.
INSTALLATION
2-WIRE INSTALLATION