14

S3 ON, S4 OFF

Outputs 1, 2 and 3 work in sequence (according to splitting time), and output 4 works continuously.

Note:

 Do not use this configuration with more than two snow sensors connected.

S3 ON, S4 ON

All 4 outputs work in sequence (according to splitting time).

Note : 

Do not use this configuration with more than two snow sensors connected.

Notes:
1. 

The illustrations above show the heater operation for 
PYROBOX5. The logic remains the same for PYROBOX3C, 
without heaters 3 and 4, and for PYROBOX3, without 
heater 4.

2. 

Heater 5, for all models, will be activated with or without 
heater 4, depending on the “Heater output logic” parameter 
set in section P07.

3. 

The logic will ignore disabled zones.

TEMPERATURE READING ERRORS

Ambient temperature sensor readings (on snow sensor) are outside reliable 
 measuring range.

Ambient temperature < -9°F/-23°C, ambient temperature > 54°F/12°C
The system will continue to operate using constant predefined values. In addition, the display 
will alternate between “LO” and -11°F/-24°C for low temperature readings and between “HI” 
and 55°F/13°C for high temperature readings.

“SensErr 1” will appear on the display.
If the system is configured to work with more than one snow sensor, the faulty snow 
 sensor number will appear on the display: P01, P02, P03 or P04.
The system will use readings from snow sensor 1 instead of the missing readings from 
the faulty snow sensor.

Communication error  

with snow sensors

1

COMMUNICATION ERROR WITH ONE (OR MORE) SNOW SENSORS

ERROR

Содержание PYROBOX3

Страница 1: ...he circuit amperage draw as specified in the NEC CEC table 1 8 Ensure that the main breakers fuses are suitable for the heat ing systems rating 80 load Grounding means must comply with local regulatio...

Страница 2: ...al applications include driveways sidewalks loading docks stairs pavements and gutters The backlit LCD screen provides full interface and information of the system status The use of several zones stag...

Страница 3: ...actors C1 C2 C3 and C4 with up to 600 VAC 50 AMP maximum per pole Provide contactor C5 with up to 277 VAC 30 AMP Make sure the wire gauge AWG is suitable for the circuit amperage draw as specified in...

Страница 4: ...manual 2 1 A C C R C B R L1 N1 R F 5A R IN IN 1 2 A 1 A C1 B 1 B C A 1 A C1 B 1 B C IMPORTANT If the heaters are connected in a star configuration the neutral must pass through the internal current tr...

Страница 5: ...000 ft 609 m using 12 AWG 3 wire shielded cable Up to 500 ft 152 m using 18 AWG 3 wire shielded cable CONNECTION TO SNOW SENSOR PYROSENSE Please refer to the PYROSENSE installation section of this ma...

Страница 6: ...3 4 5 4 1 1 2 2 3 3 4 4 5 Zone 5 optionnelle CONNECTING SNOW SENSORS TO THE SYSTEM Power cable R C 18 AWG Up to 500 ft 150 m 12 AWG Up to 1000 ft 300 m THE PYROSENSE COMES WITH 1 A plastic cap to prot...

Страница 7: ...ters are turned off The snowflake icon will disappear from the display as long as the heaters are turned off FONCTIONS Heater ON Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Heater OFF DISPLAY FONCTIONS TU...

Страница 8: ...missioning Test mode Restore defaults 1 Move DIP switch S1 located on the side of thermostat to ON position 2 Press the SELECT and buttons simultaneously to move forward to the next technician paramet...

Страница 9: ...20 5 C Default 4 F 20 C 3 Press the SELECT and buttons simultaneously again The word ON or OFF will appear on the display 4 Use the and buttons enable ON or disable OFF the P02 parameter If disabled t...

Страница 10: ...will continue during the time delay period 1 Press the SELECT and buttons simultaneously P05 On and the Manual ON mode time period will appear on the display The hours will blink The time delay parame...

Страница 11: ...l not show the ambient temperature and will remain blank 3 1 2 5 Snow on any of the sensors will trigger all zones PYROBOX5 Outputs 1 2 3 4 and 5 Value Outputs controlled by PYROSENSE Outputs controll...

Страница 12: ...urn ON test conditions to check the functionality of the system regardless of sensor parameters i e during the summer In test conditions the ambient temperature is always 5 C 23 F Note To trigger the...

Страница 13: ...e ON for 15 minutes 60 4 15 With 3 heaters enabled and 1 heater disabled Each heater will be ON for 20 minutes 60 3 20 ENABLE DISABLE ZONES Use DIP switch S2 to short the measuring times as follows ON...

Страница 14: ...section P07 3 The logic will ignore disabled zones TEMPERATURE READING ERRORS Ambient temperature sensor readings on snow sensor are outside reliable measuring range Ambient temperature 9 F 23 C ambie...

Страница 15: ...NTERNAL GFCI TIME DELAY ON time delay Turn clockwise to increase and counter clockwise to decrease Default Minimal time delay Tripped relay LED indicator Current trip full scale Model dependent see ta...

Страница 16: ...shed by it or any undertakings acts or omissions relating thereto Without limiting the generality of the foregoing Stelpro expressly dis claims any liability for property or personal injury damages pe...

Отзывы: