background image

SET ROOM THERMOSTAT TO

HIGH STOP POSITION

Check voltage across fan high limit switch

terminals (56).

MODEL: EXT

FUNCTION:  Air Delivery

PROBLEM:  Fan(s) do not operate.

Before starting any procedures listed below, check room thermostat and circuit breaker settings.

Make sure there is appropriate line voltage between F1/F3 terminal block positions in the heater.

The room temperature cannot exceed 85 degrees when performing the following test procedures.

NOTE:  For cross reference to number coded components, refer to the Exploded View Diagram.

Check room thermostat (23) for

possible miscalibration.

Check voltage across F2 & F3

terminal block positions (24).

Fan(s) Do Not

Operate

Fan(s) Operate

Voltage

Present

Remove the purple wires from

the room temperature control

thermostat (23) and jumper

them together.

No Voltage Present

Replace

thermostat (23).

Fans Run

Check unit wiring.

Fans Do

Not Run

Fix Unit Wiring.

Replace Circuit

Board (29).

Incorrect

Correct

Replace fan limit

switch (56).

Remove fan assembly

(47) and check voltage

to fan motor(s) (53).

Voltage Present

No Voltage

Present

Check units

internal wiring.

Check fan impeller for

debris that could cause

jamming.  Replace if

necessary.

No Voltage

Present

Voltage

Present

Page 4

Содержание 212EXT

Страница 1: ...9 7528 6 227 1 8 25 5220 7 1 81 76 02 6 7 7 7 7 7...

Страница 2: ...RUV RU PLVFDOFXODWLRQV FRQWDLQHG KHUHLQ RU DQ UHYLVLRQV KHUHRI RU ZKLFK UHVXOW ZKROH RU LQ SDUW IURP WKH XVH RI WKLV JXLGH RU DQ UHYLVLRQ KHUHRI I WKHUH DUH DQ TXHVWLRQV FRQWDFW 6WHIIHV RUSRUDWLRQ 7HF...

Страница 3: ...unit wiring Place the charge level switch in the Med position Does the charging light turn on Remove the jumper between the yellow and gray wire Does the charging light turn off Place the charge level...

Страница 4: ...ded components refer to the Exploded View Diagram UNIT CHARGES UNEVENLY Check unit amperage Check fans 53 and dampers for smooth operation Check heating elements 54 charge control sequencer 49 and cor...

Страница 5: ...er to the Exploded View Diagram Check room thermostat 23 for possible miscalibration Check voltage across F2 F3 terminal block positions 24 Fan s Do Not Operate Fan s Operate Voltage Present Remove th...

Страница 6: ...ostat and circuit breaker settings NOTE For cross reference to number coded components refer to the Exploded View Diagram DISCHARGE AIR TOO WARM Check for damper jamming or obstruction Check bimetalli...

Страница 7: ...the Exploded View Diagram NOTE To test the bimetallic coil assembly it must be completely cold Either allow room unit to cool completely or remove fan assembly and cool to room temperature Once the co...

Страница 8: ...board 29 Fix unit wiring Incorrect Yes Fix or replace peak control device time clock etc Fix field wiring Incorrect Correct No Correct MODEL EXT FUNCTION Peak Control PROBLEM Green Off Peak light does...

Страница 9: ...Page 8 EXPLODED VIEW DIAGRAM...

Страница 10: ...Std Output 5941116 5941118 5941120 5941122 5941124 20 Painted Panel Bottom 5942030 5942031 5942032 5942033 5942034 21 Brick Support Assembly Std Output 5941106 5941108 5941110 5941112 5941114 22 Grill...

Страница 11: ...Front 5942047 5942047 5942047 5942047 5942047 61 Charge Control Assy 130o 1040282 1040282 1040282 1040282 1040282 62 Charge Control Assy 265o 1040305 1040305 1040305 1040305 1040305 63 Charge Control...

Отзывы: