USER ADJUST

UNIVERSAL INPUT CONNECTION
For cable length  < 3 Metres no screen or twist pair required.
Thermocouple inputs must use correct compensation cable.
PT100 inputs all three wire must be equal length (resistance).
Use  recommended  types for cable length  (3 to 30) metres.

m

V

+

+

-

-

PT10

0

m

A

+

-

Ø 3mm

ELECTRICAL  INSTALLATION

Screw Driver

Screened Cable

Twisted Pair Cable

10

7

7

8

9

8

7

7

8

TC Compensation Cable

Screened 

TURN  OFF  SUPPLY  BEFORE      WORKING  ON  ANY 
ELECTRICAL CONNECTION

Ø 3mm

Screw Driver

20

20

20

20....000    

000    

000    

000    

Digital mA meter

Power supply (24V dc)

Input Simulator

User  adjust  function  allows  manual  adjustment  of  the  output  current, 
this  is  useful  for  minor  calibration  adjustment  or  trimming  out  any 
sensor  error,  ±  5%  of  range  adjustment  is  available  at  both  offset  and 
span.    Raise  and  lower  buttons  are  provided  on  the  front  panel,  of  the 
transmitter,  accessed  using  a  3  mm  flat  blade  screw  driver.  Insert  the 
screw driver into the appropriate  slot  to operate the button. The button 
has a click action. 

METHOD
1.0  Connect  transmitter to a suitable input simulator or sensor. Connect 
output to a 24V dc supply, connecting a digital mA current meter in series  
with  the  output.    Turn  supply  on,  set  input  to  either  offset  or  span 
calibration point. 

+

-

20

20

20

20....000    

000    

000    

000    

+

-

SEM1610

or

2.0 Enter adjust menu by pressing "raise" button for > two  seconds.
When the adjust menu is open the range LED will flash :-

 > 3 s

State LED will indicate Adjust action

Offset slow toggle 

Span fast toggle 

Out of trim range

Input out of range

3.0 Adjust output current by 
pressing  either  the  raise  or 
lower  button,  single  click  to 
step  advance  ,  or  press 
continuously 

to 

auto 

advance.

Raise

Lower

4.0  Once  adjust  is  complete 
allow  30  seconds  with  no 
button  press,  the  transmitter 
will  time  out  and  return  to 
normal operation.

D2441-01-05 CN5281 SEM1610 User Guide

Escape

> 30 s

Enter

The 

transmitter 

will 

automatically detect the correct 
adjust  point  (offset  or  span) 
based  on  the  output  current 
drive.  Offset  will  be  adjusted 
when  the  current    is  between 
(3.8  to  6)  mA,    span  when  the 
current  is  between  (18  to  22) 
mA.  No  trim  action  occurs  at 
any other current.

offset

span

3.8

6

18

22 mA

MECHANICAL INSTALLATION

SEM1610 Enclosure

Style

DIN 43880 (1 module width)

Material       

Polyamide 6.6 self extinguishing

Terminals

Screw terminal

Cable

2.5 mm Max

Colour

Grey

Ø 3  mm

90 mm

MOUNTING

Screw driver

EN50022 DIN RAIL

56.4 mm

17.5 mm

1
2

11

12

10

9

8

7

4

5

6

1

2

3

To fit or release module

Insert screw driver into

slot and lever latch

away from body

1

2

+ 70 °C Max

- 20 °C Min

1

2

T/C

 or sensor

Vs

Loop 
Load

USB

+

-

+

-

10

9

8

7

SEM1610

5

4

OUTPUT
2 Wire (4-20) mA 
Max cable length 1000 metres
Use twisted pair cable > 30 metres

SUPPLY (Vs)  = (11 to 30) V dc

MAX  LOAD

Ohms  = (Vs - 11) / 0.021

ADJUST

STATE

ADJUST

STATE

ADJUST

STATE

ADJUST

STATE

ADJUST

STATE

ADJUST

STATE