D2441-01-05 CN5281 SEM1610 User Guide
IMPORTANT - CE & SAFETY REQUIREMENTS
Product must be DIN rail mounted, inside a suitable enclosure providing environmental protection to IP65 or greater.
To maintain CE EMC requirements , input wires must be less than 30 metres.
The product contains no serviceable parts , or internal adjustments. no attempt must be made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure all supplies are switched off.
ABSOLUTE MAXIMUM CONDITIONS ( To exceed may cause damage to the unit):-
Supply Voltage
± 30 V dc (Protected for over voltage and reverse connection)
Current with over voltage
± 200 mA
Input Voltage
± 5 V between any terminals
Input Current
± 100 mA between terminals 7 & 10
Ambient
Temperature
(-30 to 75) °C Humidity (10 to 95) % RH (Non condensing)
Status Instruments Ltd, Status Business Park, Gannaway Lane, Tewkesbury, Gloucestershire, UK, GL20 8FD
Web Page: www.status.co.uk Tel : +44 (0) 1684 296818 Fax: +44 (0) 1684 293746 email : [email protected]
SEM1610 USER GUIDE
DIN RAIL MOUNTED TRANSMITTER
UNIVERSAL INPUT
TWO WIRE (4 to 20) mA OUTPUT
Every effort has been taken to ensure the accuracy of this document, however we do not accept responsibility for damage, injury, loss or expense resulting from errors and omissions, and we reserve the right of amendment without notice.
Important - Please read this document before any installing.
PRODUCT SPECIFICATION
RECEIVE AND UNPACKING
CONFIGURATION
Please refer to the product data sheet for full specification, available to down load at www.status.co.uk.
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.
SEM1610
USB LINK SOFTWARE
USB CABLE
Download @
www.status.co.uk
COMPUTER
IMPORTANT The SEM1610 can be configured whilst connected and powered, but a portable battery powered computer must be used to avoid the effects of ground loops.
The following parameter can be configured by simply entering as prompted by the software package.
· Input type (K,J,E,N,T,R,S,mV,PT100,mA)
· Low range
· High range
· Units (°C, °F, mV, mA)
· Burnout (direction of output current on sensor burnout)
· User Adjust (option to lock out front panel adjust function)
Factory default:
Input type
= P
Units
= °C
High Range
= 100
Low Range
= 0
Burnout
= UPSCALE
User Adjust
= ON
+
+
-
-
PT100
+
-
Vs
Loop
Load
USB
+
-
+
-
10
9
8
7
mV
mA
SEM1610
5
4
Universal
Input
2 Wire (4 to 20) mA Output