background image

6

UNDESIRABLE OPENINGS,  CAUSING POOR COMBUSTION.
SOOTING MAY RESULT WITH AN INCREASED RISK OF
ASPHYXIATION.

THERMAL EXPANSION (CLOSED SYSTEM)

Thermal expansion occurs in any hot water system when system
water is heated or “recovered” during periods of non-use.

If the system is operated in an “open” condition such as being
connected directly to the city main, the volume of expanded water
generated during the recovery periods can be dissipated back
through the “open” connection to the city main so pressure cannot
increase.

However, once a back flow preventer is installed to isolate system
water from the public supply; or a pressure reducing valve is
installed to protect a water meter; or any device preventing flow
back into the cold water supply, the “open” condition becomes
“closed”.  During periods of temperature recovery and no usage,
water expands and the pressure increases until a relief valve
opens spilling hot water.

A relief valve opening on pressure will flow small amounts of water,
whereas relieving on temperature releases large amounts of water.
Consult the section under “High Water Temperature” to determine
the cause of the relief valve to open due to temperature.

Since the water is not compressible, some provision must be made
for THERMAL EXPANSION to protect the system from excessive
pressures.  Two options are:

1. Install an expansion tank properly and adequately sized for

the expanding volume of water.

2. Install a pressure relief valve in the cold water supply line having

a setting of at least 10lbs.  below the system working pressure,
located at or near a suitable drain.  This valve will open at
each heat cycle when there is no hot water demand on the
system.

Service problems or parts failure due to excessive pressure are
NOT covered under warranty.

The pressure and temperature relief valve supplied with the water
heater IS NOT considered to be protection against thermal
expansion.

VENTING

 WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES.  SUCH CONDITIONS
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts during
shutdown periods.

Remove all soot or other obstructions from chimney, which will
retard free draft.

Venting materials used for this category 1 appliance must be in
accordance with the National Fuel Gas Code and all state and
local requirements.

NOTE:  A NEGATIVE DRAFT MUST BE MAINTAINED IN VENT
PIPING (-0.02 to -0.06).

VENT CONNECTOR

The chimney vent connector diameter should be the same size
as the heater flue outlet, see table 1.  A minimum rise of 1/4” per
foot of horizontal connector length must be maintained between
the heater and chimney opening, fig. 2.  The connector length
should be kept as short as possible.

TABLE 1

     TPG/TPX/TPO/TPD

FLUE OUTLET

INPUT (KBTUh)

 (INCHES)

140, 199

5

255, 270, 300

6

400

7

540, 600

8

720, 800, 1000

10

1250, 1500

12

1750, 2000

14

2250, 2500

16

BAROMETRIC DRAFT CONTROL ASSEMBLY

A double-acting barometric draft control assembly is provided with
each unit. This assembly must be attached to the heater as shown
in figure 2.  The direction in which the outlet to the draft control
assembly faces is arbitrary.  This assembly must be fitted to the
jacket cover such that it is plumb and level to the ground. Fasten
the draft control assembly to the top cover using sheet metal
screws at three locations, or more, as required.

Refer to the instructions provided with the barometric damper for
complete installation requirements.

Dampers or other obstructions must not be installed between the
heater and the barometric draft control assembly.

Barometric draft control counterweights can be adjusted for
installation conditions by an authorized State Start-Up Agent. Any
readjustment must be by authorized State Start-Up agent.

       

PROPER DRAFT CONTROLLER AND

VENT PIPE INSTALLATION - FIGURE 2

VENT CONNECTION

Vent connections must be made to an adequate stack or chimney.
Refer to the National Fuel Gas Code or to the vent pipe
manufacturer’s gas vent and chimney sizing table to properly
design and size the venting system.  Refer to Table 2 for the vent
pipe size required for installation to the barometric draft control
assembly outlet.

Содержание TPD-140-140

Страница 1: ...USING APPLIANCE ASME WARNING PROPANE MODEL Water heaters for propane gas are different from natural gas models A natural gas heater will not function safely on propane gas and no attempt should be ma...

Страница 2: ...an Gas Association Laboratories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 TABLE OF CONTENTS This manual is supplemented by the power burner manual All information including start up and maint...

Страница 3: ...THE FLOW OF COMBUSTION AND VENTILATING AIR ADEQUATE AIR FOR COMBUSTION AND VENTILATION MUST BE PROVIDED FOR SAFE OPERATION LIQUID PETROLEUM MODELS Water heaters for propane or liquefied petroleum gas...

Страница 4: ...American Insurance Association 85 John Street New York NY 11038 Note Some gas utility companies derate the heating value of the supplied gas at high elevations Your authorized State Start Up Agent mus...

Страница 5: ...18 Inches FRONT 18 Inches BACK 0 Inches Back 6 Inches TOP 5 Inches Top 12 Inches LEFT SIDE 0 Inches LEFT SIDE 6 Inches RIGHT SIDE 0 Inches RIGHT SIDE 6 Inches NOTE If a chimney connector is used the m...

Страница 6: ...STION OR RECIRCULATION OF FLUE GASES SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION Heater must be protected from freezing downdrafts during shutdown periods Remove all soot or other...

Страница 7: ...OCATED IN FREEZING AREAS DO NOT THREAD OR CAP THE END OF THIS LINE RESTRICTED OR BLOCKED DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE AND IS UNSAFE DISCHARGE LINE SHALL BE INSTALLED TO ALLOW COMPLET...

Страница 8: ...UAL GAS SHUTOFF VALVE BEFORE PLACING THE HEATER IN OPERATION CHECK FOR GAS LEAKAGE USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE FOR THE PURPOSE OF LOCATING GAS LEAKS DO NOT USE MATCHES CAN...

Страница 9: ...9 TYPICAL WIRE DIAGRAM TPG 270 2 500 KBTUH TPO 800 2 500 KBTUH TPD 400 2 500 KBTUH TYPICAL WIRE DIAGRAM TPG 140 255 KBTUH...

Страница 10: ...10 TYPICAL WIRE DIAGRAM TPO 140 720 KBTUH TYPICAL WIRE DIAGRAM TPD 140 300 KBTUH...

Страница 11: ...ired should be performed by an Authorized State Service Agent GENERAL NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTAL...

Страница 12: ...Inspect Quarterly non detergent motor oil Power Burner Combustion and Ignition Inspection Semi Annually test kit Device 2 test specifications Main Burner Check Flame Annually Flue Baffle Pipe 3 Cleani...

Страница 13: ...ary 9 Replace outer jacket cover plate RELIEF VALVE At least twice a year the temperature and pressure relief valve should be checked to ensure that it is in operating condition To check the relief va...

Страница 14: ...n incoming water temperature was warm colder water creates the effect of less hot water 5 Look for hot water wastage and leaking or open hot water faucets 6 Sediment or lime scale may be affecting wat...

Страница 15: ...ist of Installation of a second relief valve with lower setting than the primary relief valve An expansion tank of suitable size and pressure rating and provision to avoid water logging REPLACEMENT PA...

Страница 16: ...evice acting as a backflow prevention device check valves etc is installed in the cold water supply the heater is connected to unless an effective method of controlling thermal expansion is also insta...

Отзывы: