background image

30

MaIntenance

General

Water  heater  maintenance  includes  inspection  and  testing  of  the 

Temperature  Pressure  Relief  valve,  periodic  tank  flushing  and 

cleaning, and removal of lime scale from the heating elements. Where 

used, water heating system circulating pumps should be oiled.

Tank flushing and circulating pump lubrication should be performed in 

accordance with the maintenance schedule, see Table 7. Tank sediment 

removal  and  element  lime  scale  removal  must  be  performed  when 

needed as determined by periodic inspections.

teMperature-pressure relIef ValVe operatIon

DANGER

• 

Burn hazard.

• 

Hot water discharge.

• 

Keep clear of Temperature

  Pressure Relief Valve

  discharge outlet.

It is recommended that the Temperature-Pressure Relief valve should 

be checked to ensure that it is in operating condition every 6 months.

When  checking  the  Temperature-Pressure  Relief  valve  operation, 

make sure that (1) no one is in front of or around the outlet of the 

Temperature-Pressure  Relief  valve  discharge  line,  and  (2)  that  the 

water discharge will not cause any property damage, as water may be 

extremely hot. Use care when operating valve as valve may be hot.
To check the relief valve, lift the lever at the end of the Temperature-

Pressure Relief valve several times, see Figure 6. The valve should 

seat properly and operate freely.
If after manually operating the valve, it fails to completely reset and 

continues to release water, immediately close the cold water inlet to 

the water heater and drain the water heater, see Draining And Flushing 

on page 15. Replace the Temperature-Pressure Relief valve with a 

properly rated/sized new one, see Temperature-Pressure Relief valve 

on page 8 for instructions on replacement.

fIGure 6.

If the Temperature-Pressure Relief valve on the water heater weeps or 

discharges periodically, this may be due to thermal expansion.

note:

  Excessive  water  pressure  is  the  most  common  cause  of 

Temperature-Pressure Relief valve leakage. Excessive water system 

pressure  is  most  often  caused  by  “thermal  expansion”  in  a  “closed 

system.”  See  Closed  Water  Systems  and  Thermal  Expansion  on 

page 9. The Temperature-Pressure Relief valve is not intended for the 

constant relief of thermal expansion.

Temperature-Pressure Relief valve leakage due to pressure build up in 

a closed system that does not have a thermal expansion tank installed 

is  not  covered  under  the  limited  warranty.  Thermal  expansion  tanks 

must be installed on all closed water systems.

do not pluG the teMperature-pressure relIef ValVe 

openInG. thIs can cause property daMaGe, serIous 

Injury or death.

Explosion Hazard

Temperature-Pressure Relief Valve

must  comply  with  ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized Temperature-Relief

Valve must be installed in opening

provided.

Can  result   in  overheating  and

excessive  tank  pressure.

Can cause serious injury or death.

Component

Operation

Interval

Required

Tank

Flushing

Monthly

Sediment 

Removal

As Needed

Elements

Lime Scale 

Removal

As Needed

UN-LIME 

delimer and 

element gaskets

taBle 7. MaIntenance schedule.

flushInG

To flush the water heater:

1.  Turn off the electrical supply to the water heater at the breaker or 

 

disconnect switch.

2.  Turn off the pilot toggle switch on the water heater.

3.  Ensure the cold water inlet valve is open.

4.  Open a nearby hot water faucet and let the water run until the 

 

water is no longer hot. Then close the hot water faucet.

5.  Connect a hose to the water heater drain valve and terminate it

 

 

to an adequate drain.

6.  Ensure the drain hose is secured before and during the entire 

 

flushing  procedure.  Flushing  is  performed  with  system  water

 

 

pressure applied to the water heater.

7.  Open the water heater drain valve to flush.

8.  Flush the water heater to remove sediment and allow the water

 

 

to flow until it runs clean.

9.  Close the water heater drain valve when flushing is completed.

10. Remove the drain hose.

11.  Fill the water heater – see the Filling The Water Heater section

 

 

in this manual on page 15.

12. Turn on the electrical supply to the water heater.

13. Turn on the pilot toggle switch on the water heater.

14.  Place the water heater back in operation. Allow the water heater to

 

 

complete several heating cycles to ensure it is operating properly.

sedIMent reMoVal

Water borne impurities consist of fine particles of soil and sand 

which settle out and form a layer of sediment on the bottom of 

the  tank.  In  time,  if  not  removed,  the  level  of  sediment  might 

reach the heating elements and cause their failure.

For  convenience,  sediment  removal  and  element  lime  scale 

removal should be performed at the same time as follows.

Содержание SSED 120

Страница 1: ...future reference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS SSED 5 THRU SSED 120 FOR DEIONIZED WATER...

Страница 2: ...quires the Governor of California to publish a list of substances known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential...

Страница 3: ...y may also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must...

Страница 4: ...nds or when standing in water When replacing fuses always use the correct size for the circuit See page 12 through 14 The principal components of the heater are identified on page 6 The model and rati...

Страница 5: ...480 mm 28 711 2 mm 35 889 mm 7 177 8 mm 354 160 6 120 450 90 63 1 4 1 607 mm 30 762 mm 37 939 8 mm 7 1 2 190 5 mm 420 190 5 RECOVERY RATE IN GALLONS PER HOUR Temperature Rise F STANDARD KW INPUT BTU H...

Страница 6: ...AND COMPONENTS Below is an illustration of the water heater with its features called out The text of this manual will refer to the items shown FIGURE 1 UIM USER INTERFACE MODULE on front of hinged ac...

Страница 7: ...erature and pressure relief valve must terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at an...

Страница 8: ...acturer s instructions for installation of these valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual CONTAMINATED WATER Toxic chemicals...

Страница 9: ...damage because the water may be extremely hot If after manually operating the Temperature Pressure Relief Valve it fails to completely reset and continues to release water immediately close the cold w...

Страница 10: ...and pages describe the water heater circuits and includes wiring diagrams Control Circuits The water heater is equipped with an electronic control system The system includes a CCB Central Control Boa...

Страница 11: ...actor to determine the maximum allowable load current Ambient Temperature F 82 58 88 75 58 35 90 80 67 52 30 91 82 71 58 41 82 58 88 75 58 35 90 80 67 52 30 91 82 71 58 41 86 104 105 122 123 141 142 1...

Страница 12: ...12 WIRING DIAGRAMS WIRING DIAGRAMS DIAGRAM 1 SMALL COMMERCIAL WIRE DIAGRAM 208 240V 3PH DIAGRAM 2 SMALL COMMERCIAL WIRE DIAGRAM 208 240V 3 1PH...

Страница 13: ...ust be added according to the phase of the supply voltage See the diagram below For single phase connection jumpers A C and B D must be added For three phase connection jumper B C must be added 3 1 PH...

Страница 14: ...14 DIAGRAM 4 SMALL COMMERCIAL WIRE DIAGRAM 300 600V 3PH DIAGRAM 5 SMALL COMMERCIAL ELECTRIC 300 600V 3ph Linear or Progressive...

Страница 15: ...when the water heater is placed into operation for the first time 1 Check all factory and field made water and electrical connections for tightness Also check connections on top of the heater Repair...

Страница 16: ...ion of exposure The slower response time of children the elderly or disabled persons increases the hazards to them Never allow small children to use a hot water tap or draw their own bath water Never...

Страница 17: ...lay detailed operational and diagnostic information LCD screen on the front of the water heater displays theSequenceofOperationinrealtime FaultorAlertmessagesaredisplayed when operational problems occ...

Страница 18: ...ting element This animated icon DOES NOT indicate current has been sensed from the heating elements only that there is a call for heat present and the control system has initiated heating element oper...

Страница 19: ...n board SPDT single pole double throw relay contacts for building EMS Energy Management System notification of operational conditions such as Fault Conditions and heating mode status This menu feature...

Страница 20: ...ed with 3 heating elements with an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating elements would be as follows TABLE 6 ELEMENT NUMBER DIFFERENTIAL S...

Страница 21: ...eratures is not selected use the Up and Down buttons to select this menu item With the Operating Set Point selected highlighted in black in the Temperatures Menu press the Operational Button underneat...

Страница 22: ...wiring between the J7 socket on the CCB and a set of dry contacts on the external control per all applicable building codes This is a switching circuit only DO NOT apply any external voltage or conne...

Страница 23: ...or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of the Economy Mode Setup menu There are 3 Operating Modes in each sub menu Normal Operation All...

Страница 24: ...ss the Operational Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The Setpoin...

Страница 25: ...s to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm th...

Страница 26: ...NGE buttons to enter the Mon sub menu as described above Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to cha...

Страница 27: ...al notification when current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification...

Страница 28: ...menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will be at the top o...

Страница 29: ...actory Defaults ACTION DISPLAY From the Main Menu use the Up Down buttons to select highlight in black the Restore Factory Defaults menu Press the Operational Button underneath SELECT The Restore Fact...

Страница 30: ...al expansion Temperature Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty Therm...

Страница 31: ...move the elements and gaskets from the openings Use a twisting pulling action to remove elements scaled beyond the size of the tank openings Brush loose scale from elements 7 Lime scale removal Place...

Страница 32: ...nual on page 30 for sediment and lime scale removal procedures Water Is Too Hot Refer to the TEMPERATURE REGULATION section of this manual Water Heater Makes Strange Sounds 1 Sediment or lime scale ac...

Страница 33: ...ement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a labor charges for service removal repair or reinstallation of the water...

Страница 34: ...34 NOTES...

Страница 35: ...35 NOTES...

Страница 36: ...Technical Support and Parts 800 365 0577 www statewaterheaters com www statewaterheaters com www statewaterheaters com...

Отзывы: