background image

17

control systeM operatIon

heatInG eleMent operatIon

fIGure 3.

Depending on tank size and how they were ordered from the factory 

the water heaters covered in this manual may be equipped with 1 

to 5 electric heating elements. The illustration here shows how the 

heating elements are numbered for control purposes and how the 

openings  for  each  heating  element  are  physically  located  on  the 

water heater’s storage tank.

control options

The  water  heaters  covered  in  this  manual  are  factory  ordered 

with 1 of 3 different heating element control options as follows:

on/off control:

 This is the only configuration available on models 

equipped with a single heating element and the standard configuration 

on models equipped with more than one element. All elements are 

cycled on simultaneously with each call for heat, however there is 

a one second delay between elements being energized to reduce 

starting current. All elements are cycled off at the same time at the 

end of each heating cycle.

progressive sequencing:

 Only available on models equipped 

with  multiple  heating  elements.  Elements  are  energized  

and  de-energized  according  to  adjustable  (1  to  20°F) 

Differential set points for each element. Element Rotation - first 

 

element  on  is  rotated  with  each  successive  call  for  

heat. First On/First Off - the first heating element energized at 

the beginning  of a heating cycle is the first element de-energized  

at  the  end  of  the  heating  cycle.  Successive  heating 

 

cycles would progress as follows on a model equipped with 3 

heating elements:

•  First heating cycle: Elements come on [1, 2, 3] and cycle off [1, 2, 3].

•  Second heating cycle: Elements come on [2, 3, 1] and cycle off [2, 3, 1].

•  Third heating cycle: Elements come on: [3, 1, 2] and cycle off [3, 1, 2].

•  Fourth heating cycle: pattern repeats - same as first.

control systeM features

advanced diagnostics

Plain  English  text  and  animated  icons  display  detailed  operational  and 

diagnostic information. LCD screen on the front of the water heater displays 

the Sequence of Operation in real time. Fault or Alert messages are displayed 

when operational problems occur. Advanced Service menu displays a list of 

possible causes for current Fault and Alert conditions to aid in servicing.

economy Mode operation

Control  system  automatically  lowers  the  Operating  Set  Point  by  a 

programmed value during user defined time periods. Helps reduce 

operating costs during unoccupied or peak demand periods.

control systeM naVIGatIon

The UIM (User Interface Module) is located on the front cabinet of the water 

heater. All operational information and user settings are displayed and 

accessed using the UIM. The UIM includes five snap acting (momentary) 

user input buttons; an Up, Down and 3 Operational Buttons.

fIGure 4.

up & down Buttons

Used to navigate (up and down) and to select (highlight) menu items. 

Also used to adjust or change (increase/decrease, on/off, set time) 

various user settings.

operational Buttons

The 3 Operational Buttons are multifunctional. Their current function is 

defined by the text that appears directly above each button on the LCD 

screen. The function will change depending on what menu is currently 

displayed or what menu item is selected. When no text appears on the 

LCD screen above an Operational Button there is no function assigned.

the desktop screen

The illustration below shows the control system “Desktop Screen.” 

This  is  the  default  screen.  If  there  are  no  active  Fault  or  Alert 

conditions and no user input for approximately 10 minutes the control 

system will return to this screen automatically.

Model Information:

 Model information and menu titles are shown in 

the black bar at the top of the Desktop Screen.

tank temperature:

 Current water temperature as sensed from the 

immersion Temperature Probe.

operating set point:

 Temperature at which the control system will 

maintain tank (water) temperature in the Normal Mode. This line of 

text  will  read  Economy  Set  Point  whenever  the  control  system  is 

operating in the Economy Mode.

Содержание SSED 120

Страница 1: ...future reference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS SSED 5 THRU SSED 120 FOR DEIONIZED WATER...

Страница 2: ...quires the Governor of California to publish a list of substances known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential...

Страница 3: ...y may also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must...

Страница 4: ...nds or when standing in water When replacing fuses always use the correct size for the circuit See page 12 through 14 The principal components of the heater are identified on page 6 The model and rati...

Страница 5: ...480 mm 28 711 2 mm 35 889 mm 7 177 8 mm 354 160 6 120 450 90 63 1 4 1 607 mm 30 762 mm 37 939 8 mm 7 1 2 190 5 mm 420 190 5 RECOVERY RATE IN GALLONS PER HOUR Temperature Rise F STANDARD KW INPUT BTU H...

Страница 6: ...AND COMPONENTS Below is an illustration of the water heater with its features called out The text of this manual will refer to the items shown FIGURE 1 UIM USER INTERFACE MODULE on front of hinged ac...

Страница 7: ...erature and pressure relief valve must terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at an...

Страница 8: ...acturer s instructions for installation of these valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual CONTAMINATED WATER Toxic chemicals...

Страница 9: ...damage because the water may be extremely hot If after manually operating the Temperature Pressure Relief Valve it fails to completely reset and continues to release water immediately close the cold w...

Страница 10: ...and pages describe the water heater circuits and includes wiring diagrams Control Circuits The water heater is equipped with an electronic control system The system includes a CCB Central Control Boa...

Страница 11: ...actor to determine the maximum allowable load current Ambient Temperature F 82 58 88 75 58 35 90 80 67 52 30 91 82 71 58 41 82 58 88 75 58 35 90 80 67 52 30 91 82 71 58 41 86 104 105 122 123 141 142 1...

Страница 12: ...12 WIRING DIAGRAMS WIRING DIAGRAMS DIAGRAM 1 SMALL COMMERCIAL WIRE DIAGRAM 208 240V 3PH DIAGRAM 2 SMALL COMMERCIAL WIRE DIAGRAM 208 240V 3 1PH...

Страница 13: ...ust be added according to the phase of the supply voltage See the diagram below For single phase connection jumpers A C and B D must be added For three phase connection jumper B C must be added 3 1 PH...

Страница 14: ...14 DIAGRAM 4 SMALL COMMERCIAL WIRE DIAGRAM 300 600V 3PH DIAGRAM 5 SMALL COMMERCIAL ELECTRIC 300 600V 3ph Linear or Progressive...

Страница 15: ...when the water heater is placed into operation for the first time 1 Check all factory and field made water and electrical connections for tightness Also check connections on top of the heater Repair...

Страница 16: ...ion of exposure The slower response time of children the elderly or disabled persons increases the hazards to them Never allow small children to use a hot water tap or draw their own bath water Never...

Страница 17: ...lay detailed operational and diagnostic information LCD screen on the front of the water heater displays theSequenceofOperationinrealtime FaultorAlertmessagesaredisplayed when operational problems occ...

Страница 18: ...ting element This animated icon DOES NOT indicate current has been sensed from the heating elements only that there is a call for heat present and the control system has initiated heating element oper...

Страница 19: ...n board SPDT single pole double throw relay contacts for building EMS Energy Management System notification of operational conditions such as Fault Conditions and heating mode status This menu feature...

Страница 20: ...ed with 3 heating elements with an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating elements would be as follows TABLE 6 ELEMENT NUMBER DIFFERENTIAL S...

Страница 21: ...eratures is not selected use the Up and Down buttons to select this menu item With the Operating Set Point selected highlighted in black in the Temperatures Menu press the Operational Button underneat...

Страница 22: ...wiring between the J7 socket on the CCB and a set of dry contacts on the external control per all applicable building codes This is a switching circuit only DO NOT apply any external voltage or conne...

Страница 23: ...or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of the Economy Mode Setup menu There are 3 Operating Modes in each sub menu Normal Operation All...

Страница 24: ...ss the Operational Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The Setpoin...

Страница 25: ...s to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm th...

Страница 26: ...NGE buttons to enter the Mon sub menu as described above Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to cha...

Страница 27: ...al notification when current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification...

Страница 28: ...menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will be at the top o...

Страница 29: ...actory Defaults ACTION DISPLAY From the Main Menu use the Up Down buttons to select highlight in black the Restore Factory Defaults menu Press the Operational Button underneath SELECT The Restore Fact...

Страница 30: ...al expansion Temperature Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty Therm...

Страница 31: ...move the elements and gaskets from the openings Use a twisting pulling action to remove elements scaled beyond the size of the tank openings Brush loose scale from elements 7 Lime scale removal Place...

Страница 32: ...nual on page 30 for sediment and lime scale removal procedures Water Is Too Hot Refer to the TEMPERATURE REGULATION section of this manual Water Heater Makes Strange Sounds 1 Sediment or lime scale ac...

Страница 33: ...ement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limited to a labor charges for service removal repair or reinstallation of the water...

Страница 34: ...34 NOTES...

Страница 35: ...35 NOTES...

Страница 36: ...Technical Support and Parts 800 365 0577 www statewaterheaters com www statewaterheaters com www statewaterheaters com...

Отзывы: