background image

10

locatInG the water heater

Carefully  choose  a  location  for  the  new  water  heater.  The 

placement is a very important consideration for the safety of the 

occupants in the building and for the most economical use of the 

appliance. 

Property Damage Hazard

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

Whether  replacing  an  existing  water  heater  or  installing 

the  water  heater  in  a  new  location  observe  the  following 

critical points:
1.  The water heater must be located indoors.
2.  The water heater must not be located in an area where 

it will be subject to freezing temperatures.

3.  Locate the water heater so it is protected and not subject 

to physical damage by a moving vehicle.

4.  Locate the water heater on a level surface.
5.  Locate  the  water  heater  near  a  floor  drain.  The  water 

heater  should  be  located  in  an  area  where  leakage  of 

the tank or connections will not result in damage to the 

area  adjacent  to  the  water  heater  or  to  lower  floors  of 

the structure. When such locations cannot be avoided, 

it  is  recommended  that  a  metal  drain  pan,  piped  to 

adequate drain, be installed under the appliance. Drain 

pan  should  be  fabricated  with  sides  at  least  2”  deep 

with diameter at least 2” greater than diameter of heater. 

Pan must not restrict combustion flow.

6.  Locate the water heater close to the point of major hot 

water usage.

7.  Locate  the  water  heater  close  to  a  120  VAC  power 

supply. See Power Supply on page 14 for requirements.

8.  Locate  the  water  heater  where  an  adequate  supply  of 

fresh air for combustion and ventilation can be obtained. 

See Combustion Air and Ventilation on page 11.

9.  Locate  the  water  heater  where  the  vent  and  intake  air 

piping, when installed, will remain within the maximum 

equivalent lengths allowed. See Venting on page 20.

10. Do  not  locate  the  water  heater  where  noise  (such  as 

the Combustion Blower) during normal operation will be 

objectionable in adjacent areas.

11. Do  not  locate  the  water  heater  where  the  subsequent 

installation  of  the  vent  (exhaust)  or  intake  air 

terminations  would  be  objectionable  due  to  noise  at 

the  termination(s).  This  includes  locations  close  to  or 

across  from  windows  and  doors.  See  Venting  starting 

on page 20.

DO NOT LOCATE WATER HEATER IN AREAS WHERE 

FLAMMABLE  LIQUIDS  (VAPORS)  ARE  LIKELY  TO  BE 

PRESENT  OR  STORED  (GAR AGES,  STOR AGE  AND 

UTILIT Y  ARE AS,  ETC.):  Flammable  liquids  (such  as 

gasoline, solvents, propane (LP or butane, etc.) and other 

substances (such as adhesives, etc.) emit flammable vapors 

which  can  be  ignited  by  a  gas  water  heater’s  hot  surface 

igniter or main burner. The resulting flashback and fire can 

cause death or serious burns to anyone in the area.
Also, the water heater must be located and/or protected so 

it is not subject to physical damage by a moving vehicle.

This  water  heater  must  not  be  installed  directly  on  carpeting. 

Carpeting  must  be  protected  by  metal  or  wood  panel  beneath 

the water heater extending beyond the full width and depth of the 

appliance by at least 3” (7.6 cm) in any direction, or if the water heater 

Содержание she100

Страница 1: ...TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEAT...

Страница 2: ...Filling the Water Heater 20 Venting 20 Installation Requirements Commonwealth of Massachusetts 22 Commonwealth of Massachusetts 22 Installation of Carbon Monoxide Detectors 22 Approved Carbon Monoxide...

Страница 3: ...birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birt...

Страница 4: ...ny electrical appliance connected to the hot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should...

Страница 5: ...5 General safety information...

Страница 6: ...h NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or service agency for installatio...

Страница 7: ...stallation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed a...

Страница 8: ...rface Igniter I Junction Box J Gas Valve Assembly K Display Board L Top Plastic Enclosure Z T P Relief Valve AA Rating Plate BB Labels CC Drain Valve DD Vent Terminal EE Drain Pan FF Anode Rod GG Insu...

Страница 9: ...W C 3 48kPa Minimum Supply Pressure for Natural Gas 3 50 87kPa Minimum Supply Pressure for Propane Gas 8 00 1 99kPa Minimum pressure must be maintained under both load and no load dynamic and static...

Страница 10: ...supply See Power Supply on page 14 for requirements 8 Locate the water heater where an adequate supply of fresh air for combustion and ventilation can be obtained See Combustion Air and Ventilation on...

Страница 11: ...r death Do not apply insulation to the top of the water heater as this will interfere with safe operation of the blower assembly Do not cover the outer door thermostat or temperature pressure relief v...

Страница 12: ...do not take in to account the presence of louvers grilles or screens in the openings The required size of openings for combustion ventilation and dilution air shall be based on the net free area of e...

Страница 13: ...nstalled in the enclosure When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum dimension of rectangular air ducts shall...

Страница 14: ...pply If the Hot and Neutral wires in the 120 VAC power supply are reversed the control system will declare a Fault condition and lock out heating operation will be disabled until the power supply is c...

Страница 15: ...ines meeting the National Sanitation Foundation requirements are designed to operate with water flow pressures between 15 and 25 pounds per square inch 103 kPa and 173 kPa Flow pressures above 25 poun...

Страница 16: ...overed under the limited warranty Thermal expansion can also cause intermittent temperature pressure relief valve operation water discharged from the valve due to excessive pressure build up This cond...

Страница 17: ...locked or reduced in size under any circumstances Excessive length over 30 feet 9 14 m or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or...

Страница 18: ...systems use pressures that exceed 14 W C 1 2 PSI Gauge These systems must use field supplied regulators to lower the gas pressure to less than 14 W C 1 2 PSI Gauge Appliances require gas regulators t...

Страница 19: ...utlet of the condensate drain does not create a slippery condition which could lead to personal injury CONDENSATION WARNING THIS WATER HEATER IS A CONDENSING UNIT AND REQUIRES A DRAIN TO BE LOCATED IN...

Страница 20: ...ided in Figures 15 16A 16B and 17 Plan the vent system layout so that proper clearances are maintained from plumbing and wiring Vent pipes serving power vented appliances are classified by building co...

Страница 21: ...and terminal location as detailed in this manual have been met Carefully inspect the entire venting system for any signs of cracks or fractures particularly at joints between elbows and other fitting...

Страница 22: ...ent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all ob...

Страница 23: ...to building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 36 i...

Страница 24: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30 kW...

Страница 25: ...ENT PIPE READ THE VENT PIPE MANUFACTURER S INSTALLATION INSTRUCTIONS 1 After the points of termination have been determined use the cover plates as templates to mark the holes for the vent pipes to be...

Страница 26: ...on must be no closer than 24 61cm The specifications are displayed in Figures 18 and 19 NOTE Exhaust vent terminal is installed using the same procedure Flat Roof Installation On flat roof installatio...

Страница 27: ...may cause intermittent operation INSTALLATION PROCEDURE 1 ROOF TERMINATION see Figure 24 1 Determine best location for termination kit NOTE Roof termination is preferred since it is less susceptible t...

Страница 28: ...nts shrubs or air conditioning equipment Termination kit positioned so it will not be affected by wind eddy that may allow recirculation of combustion products or airborne leaves or light snow Termina...

Страница 29: ...nsion more than 60 1 5 m See Figure 21 Do not use field supplied couplings to extend pipes Airflow restriction will occur and the heater pressure switch may cause intermittent operation 7 Cement heate...

Страница 30: ...distance is maintained The air intake screen can be removed for space heating at cold climate installation to prevent potential air intake freeze up If air intake screen is removed during winter to p...

Страница 31: ...inches 15 2cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitut...

Страница 32: ...distance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process so...

Страница 33: ...exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal Also verify that the vent length does not exceed the maximum allowed as shown in the Vent Section of this manual BLO...

Страница 34: ...RORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING Power Vent Wiring Schematic Figure 35 THIS WATER HEATER IS POLARITY SENSITVE BEFORE APPLYING ELECTRICITY TO THIS...

Страница 35: ...INSTRUCTIONS 1 Set the thermostat to the lowest setting 2 Set the ON OFF switch on the control panel to the OFF position 3 Turn off all electrical power to the appliance if service is to be performed...

Страница 36: ...supply to the water heater must be turned off and on again to reset the control system Contact your dealer or servicer if continued high limit switch operation occurs It is recommended that lower wate...

Страница 37: ...orage tank Heating cycles and ignition are managed by the control system The ECO energy cut out Flame Sensor pressure switches and Temperature Probe is monitored by the control system The Combustion B...

Страница 38: ...gniter is being energized The Igniter has been energized and the control system has sensed the required minimum igniter current The check mark icon is visual confirmation of minimum igniter current GA...

Страница 39: ...the control system Note Cycling power will not reset the control system if the condition that caused the Fault has not been corrected Control System Menus From the Desktop screen pressing the Operatio...

Страница 40: ...t and description of control system menus Use the Up and Down Buttons to view all control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen p...

Страница 41: ...rrent Operating State see Table 10 for a description of the various operational states ECO Contact Blocked Inlet PS Blocked Outlet PS Blower Prover PS displays the current state of the switch contacts...

Страница 42: ...he control system water heater has been energized Burner On Time Total accumulated time the control system has been in the heating operating state burner run time Cycle Count Total accumulated count o...

Страница 43: ...ew details for each Fault or Alert message stored Note fault history memory is cleared after 30 days 1 Blocked Air Intake A7 51 mins ago 2 Blocked Exhaust A8 54 mins ago 3 Low Gas Pressure A6 57 mins...

Страница 44: ...Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons select highlighte...

Страница 45: ...a A concentration of sulfate in the supply water b Little or no dissolved oxygen in the water c A sulfate reducing bacteria which has accumulated within the water heater this harmless bacteria is non...

Страница 46: ...d anode rod can extend the life of your water heater Inspection should be conducted by a qualified technician and at a minimum should be checked annually after the warranty period Artificially softene...

Страница 47: ...t 4 Connect a hose to the drain valve and terminate it to an adequate drain 5 Ensure the drain hose is secured before and during the entire flushing procedure Flushing is performed with system water p...

Страница 48: ...emperature Pressure Relief Valve on page 17 for instructions on replacement DISCHARGE PIPE TEMPERATURE PRESSURE RELIEF VALVE Figure 38 If the Temperature Pressure Relief Valve on the water heater weep...

Страница 49: ...drain valve may be due to the valve being slightly opened F The drain valve may be leaking at the tank fitting G Leakage from recirculation plug or pipe connection H Leakage from the plug under the cl...

Страница 50: ...rgized and will coast to a stop 13 Thecontrolsystemnowentersthestandbymodewhilecontinuing to monitor the internal storage tank water temperature and the state of other system devices If the tank tempe...

Страница 51: ...em Igniter is energized for warm up period 24 V Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks Out Dis...

Страница 52: ...a Fault condition it will display a Fault message on the control system s LCD with an exclamation mark The control system will lock out and disable heating operation until the condition is corrected T...

Страница 53: ...urface igniter is at ignition temperature causing delayed ignition which can cause a fire or explosion mark The water heater will continue to operate during an Alert condition but the water heater mus...

Страница 54: ...CHANGE BACK ADVANCED Ignition Failure Fault occurred 2 mins ago The water heater has failed to ignite the burner Call a service professional Your Company Name Here press DOWN for more The control syst...

Страница 55: ...e tube Combustion Blower is not running when energized Loose or open wiring to Combustion Blower CHANGE BACK ADVANCED Blower Prover Open Fault occurred 2 mins ago The blower prover switch remains open...

Страница 56: ...56 Notes...

Страница 57: ...57 Notes...

Страница 58: ...58 Notes...

Страница 59: ...e heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed...

Страница 60: ...60 www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2012 State Water Heaters All rights reserved...

Отзывы: