A gas line of sufficient size must be run to the water heater.  Consult 

the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 

54) or the Natural Gas and Propane Installation Code (CAN/CSA 

B149.1) and your gas supplier concerning pipe size.
There must be:

•  A readily accessible manual shut off valve in the gas supply line 

serving the water heater, and

•  A drip leg (sediment trap) ahead of gas control valve to help prevent 

dirt and foreign materials from entering the gas control valve.

•  A flexible gas connector or a ground joint union between the shut 

off valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water 

heater. Use a soapy water solution, not a match or open flame. Rinse 

off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resistant 

to the action of petroleum [Propane (L.P.)] gases. 
The appliance and its gas connection must be leak tested before 

placing the appliance in operation.
The appliance and its individual Shut-off valve should be disconnected 

from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 pound per square inch (3.5 

kPa).  It should be isolated from the gas supply piping system by closing 

its individual manual Shut-off valve during any pressure testing of the gas 

supply piping system at test pressures equal to or less than 1/2 pound 

per square inch (3.5 kPa).
Connecting gas piping to the gas control valve of water heater can be 

accomplished by either of two methods shown in Figures 12 and 13.

fIGure 12.  Gas pIpInG wIth 

fleXIBle connector.

fIGure 13.  Gas pIpInG wIth all

BlacK Iron pIpe to Gas control.

sedIMent traps

A sediment trap should be installed as close to the inlet of the water 

heater as practical at the time of water heater installation. The 

sediment trap should be either a tee fitting with a capped nipple in 

the bottom outlet or other device recognized as an effective sediment 

trap. If a tee fitting  is used, it should be installed in conformance with 

one of the methods of installation shown in Figures 12 and 13. 

Contaminants in the gas lines may cause improper operation 

of the gas control valve that may result in fire or explosion. 

Before attaching the gas line be sure that all gas pipe is clean 

on the inside. To trap any dirt or foreign material in the gas 

supply line, a drip leg (sometimes called a sediment trap) must 

be incorporated in the piping. The drip leg must be readily 

accessible. Install in accordance with the “Gas Piping” section. 

Refer to the current edition of the National Fuel Gas Code (ANSI 

Z223.1/NFPA 54) or the Natural Gas and Propane Installation 

Code (CAN/CSA B149.1).

FIGURE 14.

fIllInG the water heater

Содержание SHE 50 76N

Страница 1: ...L AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEA...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...ilablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local code...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Страница 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Страница 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Страница 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Страница 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Страница 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 20 21 fo...

Страница 15: ...f code requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the...

Страница 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Страница 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syst...

Страница 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Страница 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Страница 21: ...ectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or frac...

Страница 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower...

Страница 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA...

Страница 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Страница 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Страница 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Страница 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Страница 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Страница 33: ...ve a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE...

Страница 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Страница 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Страница 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Страница 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 39: ...installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will...

Страница 40: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 365 0024 Parts 800 821 2017...

Отзывы: