background image

17

discharge opening must not be blocked or reduced in size under 

any circumstances. Excessive length, over 30 feet (9.14 m), or 

use of more than four elbows can cause restriction and reduce 

the discharge capacity of the valve.
No valve or other obstruction is to be placed between the 

Temperature-Pressure Relief Valve and the tank. Do not connect 

discharge  piping  directly  to  the  drain  unless  a  6”  (15.2  cm) 

air gap is provided. To prevent bodily injury, hazard to life, or 

property damage, the relief valve must be allowed to discharge 

water in adequate quantities should circumstances demand. If 

the discharge pipe is not connected to a drain or other suitable 

means, the water flow may cause property damage.

CAUTION

• 

Temperature-Pressure Relief Valve discharge

  pipe must terminate at adequate drain.

Water Damage Hazard

t&p valve discharge pipe requirements:

•  Should not be smaller in size than the outlet pipe size of the valve, or 

  have any reducing couplings or other restrictions.
•  Should not be plugged or blocked.
•  Should not be exposed to freezing temperatures.
•  Should be of material listed for hot water distribution.
•  Should be installed so as to allow complete drainage of both the 

  Temperature-Pressure Relief Valve and the discharge pipe.
•  Must terminate a maximum of six inches above a floor drain or external 

  to the building. In cold climates, it is recommended that the discharge 

  pipe be terminated at an adequate drain inside the building.
•  Should not have any valve or other obstruction between the relief 

  valve and the drain.

DANGER

• 

Burn hazard.

• 

Hot water discharge.

• 

Keep clear of Temperature-

  Pressure Relief Valve

  discharge outlet.

The Temperature-Pressure Relief Valve must be manually operated 

at least twice a year. Caution should be taken to ensure that (1) no 

one is in front of or around the outlet of the Temperature-Pressure 

Relief Valve discharge line, and (2) the water manually discharged 

will not cause any bodily injury or property damage because the 

water may be extremely hot. If after manually operating the valve, it 

fails to completely reset and continues to release water, immediately 

close the cold water inlet to the water heater, follow the draining 

instructions in this manual, and replace the Temperature-Pressure 

Relief Valve with a properly rated/sized new one.

note:

 The purpose of a Temperature-Pressure Relief Valve is to 

prevent excessive temperatures and pressures in the storage tank. 

The T&P valve is not intended for the constant relief of thermal 

expansion. A properly sized thermal expansion tank must be installed 

on all closed systems to control thermal expansion, see Closed Water 

Systems and Thermal Expansion on page 15.

If you do not understand these instructions or have any questions 

regarding the Temperature-Pressure Relief Valve call the toll free number 

listed on the back cover of this manual for technical assistance.

hIGh altItude InstallatIon

This heater is approved for operation up to 5,300 feet (1,615 m) 

without alteration. High altitude models are available from the factory 

for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079 

m).  For  elevations  above  10,100  feet  (3,079  m)  the  input  rating 

should be reduced at the rate of 4 percent for each 1,000 feet (305 

m) above sea level which requires replacement of the burner orifice in 

accordance with National Fuel Gas Code (ANSI Z223.1/NFPA  54) or 

the Natural Gas and Propane Installation Code (CAN/CSA B149.1).  

Contact your local gas supplier for further information.

Failure to replace standard orifice with a high altitude orifice when installed 

above 10,100 feet (3,079 m) could result in improper and inefficient 

operation of the appliance, producing carbon monoxide gas in excess of 

safe limits, which could result in serious injury or death. Contact your gas 

supplier for any specific changes which may be required in your area. 

Gas pIpInG

Fire and Explosion Hazard

Do  not   use  water heater with any

gas other than the gas shown on

the rating plate.

Excessive  pressure to gas control

valve can cause serious injury or death
Turn off gas lines during installation.

Contact qualified installer or 

service agency.

Make sure the gas supplied is the same type listed on the model rating 

plate. The inlet gas pressure must not exceed 14 inch  water column (3.5 

kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure 

shown on the rating plate is that which will permit firing at rated input.
All gas piping must comply with local codes and ordinances or with the 

National Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural 

Gas and Propane Installation Code (CAN/CSA B149.1) whichever 

applies. Copper or brass tubing and fittings (except tin lined copper 

tubing) should not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 

(3.5 kPa), the damage to the gas control valve could result in a fire 

or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also 

turn “off” the gas at each appliance.  Leave all gas appliances shut 

“off” until the water heater installation is complete.

Содержание SHE 50 76N

Страница 1: ...L AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEA...

Страница 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Страница 3: ...3 GENERAL SAFETY INFORMATION...

Страница 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Страница 5: ...ilablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local code...

Страница 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Страница 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Страница 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Страница 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Страница 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Страница 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Страница 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Страница 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 20 21 fo...

Страница 15: ...f code requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the...

Страница 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Страница 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syst...

Страница 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Страница 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Страница 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Страница 21: ...ectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or frac...

Страница 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower...

Страница 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Страница 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Страница 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA...

Страница 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Страница 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Страница 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Страница 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Страница 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Страница 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Страница 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Страница 33: ...ve a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE...

Страница 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Страница 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Страница 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Страница 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Страница 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Страница 39: ...installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will...

Страница 40: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 365 0024 Parts 800 821 2017...

Отзывы: