hIGh tEMpEraturE lIMIt Controls (ECo)

This  water  heater  is  equipped  with  an  ECO  (energy  cut  off). This 

switch  is  adjustable,  up  to  190  degree  F.  An  ECO  is  a  normally 

closed switch that opens (activates) on a rise in temperature. If the 

ECO switch contacts open (activate) due to abnormally high water 

temperatures  the  control  system  will  lock-out  and  disable  further 

heating  element  operation.  It  is  important  that  a  qualified  service 

agent be contacted to determine the reason for the ECO activation 

before  resetting  the  ECO.  Once  the  reason  has  been  determined 

and corrected the ECO can be reset as follows:

When the ECO switch contacts open (activate) the electronic control 

system  locks  out  and  displays  a  Fault  message.  Voltage  to  the 

contactor coils and heating elements is terminated to prevent further 

heating operation. Should the ECO activate, the water temperature 

must drop below 120°F/49°C before the control system can be reset. 

Once the water temperature has cooled below this point the power 

supply to the water heater must be turned off and on again to reset 

the control system.

thErMostat Controls

The water heaters covered in this instruction manual are equipped 

with adjustable thermostat controls to control water temperature. Hot 

water temperatures required for automatic dishwasher and laundry 

use can cause scald burns resulting in serious personal injury and/

or  death.  The  temperature  at  which  injury  occurs  varies  with  the 

person’s age and duration of exposure. The slower response time 

of children, the elderly or disabled persons increases the hazards to 

them. Never allow small children to use a hot water tap or draw their 

own bath water. Never leave a child or disabled person unattended in 

a bathtub or shower. The water heater should be located in an area 

where the general public does not have access to set temperatures.

Setting  the  water  heater  temperatures  at  120°F  will  reduce  the 

risk  of  scalds.  Some  States  require  settings  at  specific  lower 

temperatures.

See Figure 1 which shows the approximate time-to-burn relationship 

for normal adult skin.

MIXInG ValVEs

DANGER

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the physically 

or mentally disabled are at highest risk 

for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as 

mixing valves must be installed when 

required by codes and to ensure safe 

temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing, 

dish  washing,  and  other  sanitizing  needs  can  scald  and  cause 

permanent  injury  upon  contact.  Short  repeated  heating  cycles 

caused by  small  hot  water  uses  can cause temperatures at  the 

point of use to exceed the water heater’s temperature setting by 

up to 20°F (11°C).

Some people are more likely to be permanently injured by hot water 

than others. These include the elderly, children, the infirm and the 

physically/mentally disabled. Figure 1 shows the approximate time-

to-burn relationship for normal adult skin. If anyone using hot water 

provided by the water heater being installed fits into one of these 

groups or if there is a local code or state law requiring a certain 

water temperature at the point of use, then special precautions 

must be taken.

In  addition  to  using  the  lowest  possible  temperature  setting  that 

satisfies the demand of the application a Mixing Valve should be 

installed at the water heater (see Figure 2) or at the hot water taps 

to further reduce system water temperature.

Mixing valves are available at plumbing supply stores. Consult a 

Qualified Installer or Service Agency. Follow mixing valve manufacturer’s 

instructions for installation of the valves.

Water Temperature

Time to Produce 2nd & 3rd

Degree Burns on Adult Skin

180°F (82°C)

Nearly instantaneous

170°F (77°C)

Nearly instantaneous

160°F (71°C)

About 1/2 second

150°F (66°C)

About 1-1/2 seconds

140°F (60°C)

Less than 5 seconds

130°F (54°C)

About 30 seconds

120°F (49°C)

More than 5 minutes

fIGurE 1.

tEMpEraturE rEGulatIon

Содержание SEH-200

Страница 1: ...nstruction Manual place these instructions adjacent to heater and notify owner to keep for future reference COMMERCIAL ELECTRIC WATER HEATER MODELS SEV 150 THRU SEV 10000 SEH 200 THRU SEH 10000 UP TO...

Страница 2: ...about the type of hazard what can happen if you do not follow the safety message and how to avoid the risk of injury The California Safe Drinking Water and Toxic Enforcement Act requires the Governor...

Страница 3: ...perly may also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor m...

Страница 4: ...It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the water heater It also contains warnings throug...

Страница 5: ...ter circuits and includes wiring diagrams Control Circuits The water heater is equipped with an electronic control system The system includes a CCB Central Control Board circuit board an immersion tem...

Страница 6: ...C1 C5 C4 C3 C2 C1 N GRN GRN BLK BLK X FMR ECO TEMP 120V BLK BLU RED RED RED RED SDI 24V X FMR PRIMARY FUSES X FMR 120V SEC SEC FUSE PILOT SWITCH BLK BLK JUMPER TO DISPLAY LWCO 5 4 3 2 1 FUSES CNTCTR...

Страница 7: ...f scalds Some States require settings at specific lower temperatures See Figure 1 which shows the approximate time to burn relationship for normal adult skin MIXING VALVES DANGER Water temperature ove...

Страница 8: ...water temperature This is an adjustable user setting in the control system s Temperatures Menu This and all control system menus are accessed through the UIM User Interface Module located on the front...

Страница 9: ...irectly above each button on the LCD screen The function will change depending on what menu is currently displayed or what menu item is selected When no text appears on the LCD screen above an Operati...

Страница 10: ...used the fault is corrected Power to the water heater must be cycled off and on to reset the control system Note cycling power will not reset the control system if the condition that caused the fault...

Страница 11: ...peration total heating cycle time heating cycle count heating element s cycle count and on time along with UIM and CCB software revisions can be viewed in this menu Current Fault Alert Displays any cu...

Страница 12: ...equipped with 3 heating elements with an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating elements would be as follows ELEMENT NUMBER DIFFERENTIAL SET...

Страница 13: ...eratures is not selected use the Up and Down buttons to select this menu item With the Operating Set Point selected highlighted in black in the Temperatures Menu press the Operational Button underneat...

Страница 14: ...ontacts on the external control per all applicable building codes This is a switching circuit only DO NOT apply any external voltage or connect any load IE relay coil to either circuit Element On Disp...

Страница 15: ...or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of the Economy Mode Setup menu There are 3 Operating Modes in each sub menu Normal Operation All...

Страница 16: ...ss the Operational Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The Setpoin...

Страница 17: ...s to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm th...

Страница 18: ...E buttons to enter the Mon sub menu as described above Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to chang...

Страница 19: ...ternal notification when current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notificat...

Страница 20: ...menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will be at the top o...

Страница 21: ...actory Defaults ACTION DISPLAY From the Main Menu use the Up Down buttons to select highlight in black the Restore Factory Defaults menu Press the Operational Button underneath SELECT The Restore Fact...

Страница 22: ...it switch may have activated See the Temperature Regulation section of this manual for more information on how to reset the ECO high limit controls Repeated activation of the ECO high limit switch sho...

Страница 23: ...NOTES...

Страница 24: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Parts 800 433 2545 Fax 800 644 9306 www statewaterheaters com Copyright 2010 A O Smith Corporation All rights reserved...

Отзывы: