Make sure the gas supplied is the same type listed on 
the model rating plate. The inlet gas pressure must not 
exceed 14 inch w.c. for natural gas and propane gas. The 
minimum inlet gas pressure shown on the rating plate is 
that which will permit 

fi

 ring at rated input.

All gas piping must comply with local codes and ordinances 
or with the 

National Fuel Gas Code (ANSI Z223.1/ NFPA-

54)

. Copper or brass tubing and 

fi

 ttings (except tin lined 

copper tubing) should not be used.
If the gas control valve/thermostat is subjected to 
pressures exceeding 1/2 psi, the damage to the gas 
control valve/thermostat could result in a 

fi

 re or explosion 

from leaking gas.

If the main gas line shut-off serving all gas appliances is 
used, also turn “OFF” the gas at each appliance. Leave 
all gas appliances shut “OFF” until the water heater 
installation is complete.

A gas line of suf

fi

 cient size must be run to the water heater. 

Consult the current edition of 

National Fuel Gas Code 

(ANSI Z223.1/NFPA 54)

 and your gas supplier concerning 

pipe size.

There must be:

• 

A readily accessible manual shut-off valve in the gas 
supply line serving the water heater, and

• 

A sediment trap (dirt leg) ahead of gas control valve/
thermostat to help prevent dirt and foreign materials 
from entering the gas control valve/thermostat.

• 

fl

 exible gas connector or a ground joint union between 

the shut-off valve and gas control valve/thermostat to 
permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting 
the water heater. Use a soapy water solution, not a match 
or open 

fl

 ame. Repair and retest as required. When 

fi

 nished, rinse off soapy solution and wipe dry.

 Use joint compound or tape 

compatible with propane.

 Leak test before operating 

heater.

 Disconnect gas piping and 

shut-off valve before pressure 
testing system.

Fire and Explosion Hazard

WARNING

Use pipe joint compound or Te

fl

 on tape marked as being 

resistant to the action of gases.

The appliance and its gas connection must be leak tested 
before placing the appliance in operation.

The appliance and its individual shut-off valve should be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 

excess of 1/2 psi. It should be isolated from the gas supply 
piping system by closing its individual manual shut-off 
valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psi.

Connecting gas piping to the gas control valve/thermostat 
of water heater can be accomplished by either of two 
methods shown in Figure 25 & Figure 26.

Figure 25.  

Figure 26.  

 SEDIMENT TRAPS/DIRT LEG

• 

Contaminants in gas lines can 

cause fire or explosion.

• 

Clean all gas piping before 

installation.

• 

Install sediment trap in accor-

dance with NFPA54.

Fire and Explosion Hazard

WARNING

A sediment trap should be installed as close to the inlet of 
the water heater as practical at the time of water heater 
installation. The sediment trap should be either a tee 

fi

 tting 

with a capped nipple in the bottom outlet or other device 
recognized as an effective sediment trap. If a tee 

fi

 tting is 

used, it should be installed in conformance with one of the 
methods of installation shown in Figure 25 & Figure 26.
Contaminants in the gas lines may cause improper 
operation of the gas control valve/thermostat that may 
result in 

fi

 re or explosion. Before attaching the gas line be 

sure that all gas pipe is clean on the inside. To trap any 
dirt or foreign material in the gas supply line, a sediment 

 www.statewaterheaters.com 

25

Содержание GS 6

Страница 1: ...ER VENTED GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE CONTACT THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER www statewaterheaters co...

Страница 2: ...ltitude Installation 24 Gas Piping 24 Sediment Traps Dirt Leg 25 Filling The Water Heater 26 Venting 26 Termination Clearances Sidewall Power Vent 27 Blower Assembly Installation 28 Installation Of Vent System 28 Planning The Vent System 28 High Ambient Temperature Installations 28 Polypropylene Vent Systems 29 Condensate 29 Exhaust Venting 30 Important Notes and Warnings Venting terminations and ...

Страница 3: ...warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances listed in the Act IMPORTANT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing ...

Страница 4: ...GENERAL SAFETY 4 www statewaterheaters com ...

Страница 5: ... 2 are heavier than air 3 go a long way on the floor and 4 can be carried from other rooms to the the electodes by air currents Flammable Vapors FLAMMBLE DANGER Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Install vent system in accordance with codes Do not operate water heater if flood damaged For operation above 10 100 a high altitude or...

Страница 6: ...This manual contains instructions for installation operation and maintenance of the gas fired water heater It also contains warnings throughout the manual that you must read and be aware of All warnings and instructions are essential to proper operation of the water heater and your safety Since we cannot put everything on the first few pages READ ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERA...

Страница 7: ...ontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and si...

Страница 8: ...ON REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPING LOOP SHUT OFF VALVE 2 ALL WATER PIPING MUST BE INSTALLED AND INSULATED IN ACCORDANCE WITH MASSACHUSETTS CODE 248 CMR 780 CMR 3 PIPING LOOP BETWEEN WATER HEATER AND AIR HANDLER MUST BE INSTALLED IN COMPLIANCE WITH 248 CMR REQUIRED ...

Страница 9: ...ing see Figure 6 26 Rubber Coupling see also Figure 6 27 Gear Clamp see also Figure 6 28 Flue Collector 29 Hot Water Outlet Nipple 30 Anode under cap 31 Control Harness 32 Flexible Manifold Tube see Figure 3 Figure 4 33 Viewport see Figure 3 Figure 4 34 Flame Sensor Rod see Figure 3 Figure 4 35 Gas Orifice see Figure 3 Figure 4 36 Sheet Metal Burner see Figure 3 Figure 4 37 Gas Manifold see Figure...

Страница 10: ...ss has 120 VAC In operation See Planning The Vent System Condensate and Blower Assembly Installation for more information REPLACEMENT PARTS AND DELIMING PRODUCTS Replacement parts and recommended delimer may be ordered through authorized servicers or distributors When ordering parts provide complete model and serial numbers see rating plate quantity and name of part desired Standard hardware items...

Страница 11: ...RT 9001262 CAN BE ORDERED THROUGH THE MANUFACTURER NOTE THE T P VALVE DISCHARGE PIPE MUST BE PIPED DIRECTLY TO THE DRAIN OR EXTERNAL TO THE BUILDING MASSACHUSETTS INSTALL A VACUUM RELIEF IN COLD WATER LINE PER SECTION 19 MGL 142 Figure 8 his appliance has been design certified as complying with American National Standard CSA Standard for water heaters and certain models with side plumbing connecti...

Страница 12: ... 8 Figure 9 or at hot water taps to further reduce system water temperature Mixing valves are available at plumbing supply stores Consult a Qualified Installer or Service Agency Follow mixing valve manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Operating The Temperature Control System section in this manual WATER HEATER OPE...

Страница 13: ...for the correct electrical connections After making all electrical connections completely fill the tank with water and check all connections for leaks Open the nearest hot water faucet and let it run for 3 minutes to purge the water lines of air and sediment and to ensure complete filling of the tank The electrical power may then be turned on Verify proper operation after servicing See also Instal...

Страница 14: ...ble vapors before they enter the combustion chamber this water heater is equipped with a flammable vapor sensor FVS It is a chemical absorption based sensor that is connected to the gas control thermostat see Figure 13 When exposed to flammable vapors it will trigger the control to stop the flow of gas and enter the FVS lockout state While in the FVS lockout state the LED on the control will flash...

Страница 15: ...to an adequate drain The pan must have a maximum depth of 1 75 Water heater life depends upon water quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a metal drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak ...

Страница 16: ... every direction or if the appliance is installed in an alcove or closet the entire floor must be covered by the panel Failure to heed this warning may result in a fire hazard Clearance for servicing Adequate clearance of 24 for servicing this appliance should be considered before installation such as changing the anodes etc A minimum clearance of 5 5 must be allowed for access to replaceable part...

Страница 17: ...r safe operation an adequate supply of fresh uncontaminated air for combustion dilution and ventilation must be provided Note Contaminated or dusty air may cause build up on the blower wheel resulting in nuisance shut downs An insufficient supply of air can cause recirculation of combustion products resulting in contamination that may be hazardous to life Such a condition often will result in a ye...

Страница 18: ...frigerants swimming pool chemicals calcium and sodium chloride water softener salt waxes bleach and process chemicals are typical compounds which are potentially corrosive A ALL AIR FROM INSIDE BUILDINGS See Figure 16 The confined space shall be provided with two permanent openings communicating directly with an additional room s of sufficient volume so that the combined volume of all spaces meets...

Страница 19: ...nt free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation 7 Special Conditions Created by Mechanical Exhausting or Fireplaces operation of exhaust fans ventilation systems clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of in...

Страница 20: ...tting on thermostat read Operating The Temperature Control System section in this manual This water heater should not be connected to any heating systems or components previously used with a non potable water heating appliance All piping components connected to this unit for space heating applications should be suitable for use with potable water Toxic chemicals such as those used for boiler treat...

Страница 21: ...t loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Combo Heating Systems require higher water temperatures than other applications When the system is used to supply water for Combo Heating applications a means such as mixing valve must be installed to temper the water in order to reduce scald hazard potent...

Страница 22: ...sed systems to control the harmful effects of thermal expansion Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank Note To protect against untimely corrosion of hot and cold water fittings it is recommended that di electric unions or couplings be installed on this water heater when connected to copper pipe Avoid water heater damage Inst...

Страница 23: ...h over 30 feet or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between the T P valve and the tank Do not connect discharge piping directly to the drain unless a maximum of 6 air gap is provided To prevent bodily injury hazard to life or property damage the relief valve must be allowed to discharge wa...

Страница 24: ... heater 4 Locate the slit running the length of a section of pipe insulation 5 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure along the length of the insulation to ensure that it is fully seated around the pipe Also ensure that the base of the insulation is flush with the water heater Once seated secure the insulation with duct tape electrical tap...

Страница 25: ... tape compatible with propane Leak test before operating heater Disconnect gas piping and shut off valve before pressure testing system Fire and Explosion Hazard WARNING Use pipe joint compound or Teflon tape marked as being resistant to the action of gases The appliance and its gas connection must be leak tested before placing the appliance in operation The appliance and its individual shut off v...

Страница 26: ... between the heater and the faucets are the open position 4 Open the cold water supply valve to the water heater Notes The cold water supply valve must be left open when the water heater is in use Avoid water leakage when filling the tank Do not allow the insulation of the water heater to get wet as water can reduce the effectiveness of the insulation 5 To ensure complete filling of the tank allow...

Страница 27: ...ow or to side of opening 1 foot above opening D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft from the center line of the terminal 12 in K Clearance to a mechanical air supply inlet 3 ft above if within 10 ft horizontally E Clearance to unventilated soffit 12 in L Clearance above paved sidewalk or paved driveway located on public property 7...

Страница 28: ...ipe To start off with an elbow a short section of the straight pipe must be cut and glued into the end of the elbow that will mount on the discharge boot INSTALLATION OF VENT SYSTEM Before beginning installation of piping system thoroughly read the Vent Pipe Preparation section of this manual PLANNING THE VENT SYSTEM Plan the layout of the vent system from the vent termination to the water heater ...

Страница 29: ...connection is required and is available through your supplier Optional wall plates that fit the polypropylene venting are also available through your supplier Carefully inspect the entire venting system for any signs of cracks or fractures particularly at joints between elbows and other fittings and straight runs of vent pipe Check system for signs of sagging or other stresses in joints as a resul...

Страница 30: ...y use approved material All venting material and components must be joined with the approved primer cleaner and solvent cement Do not common vent this heater with any other appliance During operation the plastic piping will expand as it heats up and contract as it cools down This is normal for this type of venting Rigidly fastening the vent piping can cause undue stress that may result in the crac...

Страница 31: ...ing to attach the venting to the blower and a 3 45 vent termination elbow Supplied with this heater are several vent termination screens see Figure 31 Figure 32 Installed in the vent termination elbow the vent screen is required to keep foreign objects rodents and small birds from entering the venting system These screens have been sized to ensure maximum energy efficiency of the vent system based...

Страница 32: ... Long Sweep Long Radius Notes 1 Use long radius elbows where possible Minimum distance between 90º elbows should be 6 wherever possible 2 Venting systems may use a maximum of five 5 90 elbows 3 Use proper screen termination see Figure 31 Figure 32 2 3 4 90 elbow 8 ft 5 ft 2 3 4 45 elbow 4 ft 2 5 ft Table 2 Example for calculating equivalent feet Section A 0 5 ft 90 elbow 8 0 ft Section B 1 0 ft 45...

Страница 33: ...the vent piping through this hole and secure into position Connect the vent pipe to the end termination elbow as shown in Figure 34 thru Figure 36 10 Dry fit all vent pipes elbows connectors and fittings before joining any parts with solvent cement PARTS MUST FIT WITHOUT STRESS OR BENDING OF ANY SECTION and each connection must overlap a minimum of 1 2 Do not force fit any of the connections Use o...

Страница 34: ...ubber coupling Check that there is no stress on the connection or the vent piping that may be caused by twisting or bending 6 Tighten the upper clamp so that the vent piping is firmly secured in the coupling and is gas tight Do not over tighten or cause distortion of any of the parts Ensure the bottom of the rubber coupling is firmly seated on the blower outlet and that the lower gear clamp is als...

Страница 35: ...you have any questions about the application or installation of PVC and CPVC pipe Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up By far the majority of failures in PVC and CPVC systems are the result of shortcuts and or improper joining techniques 2 SELECTION OF MATERIALS PCV and CPVC VENTING Cutting Device Saw or Pipe Cutter Deburri...

Страница 36: ...proper interfacing of the pipe end and the fitting socket bottom This can be accomplished with a miter box saw or wheel type cutter Wheel type cutters are not generally recommended for larger diameters since they tend to flare the corner of the pipe end If this type of cutter is used the flare on the end must be completely removed Note Power saws if used should be specifically designed to cut plas...

Страница 37: ...ing socket Avoid puddling Apply a second coat of cement to the pipe end Cans of cement and primer should be closed at all times when not in use to prevent evaporation of chemicals and hardening of cement They are also very flammable and should be kept away from heat or flame Fire Hazard WARNING Figure 45 F Joint assembly Working quickly insert the pipe into the fitting socket bottom and give the p...

Страница 38: ...Located as close to gas piping and vent pipe system as possible 2 Located indoors and in a vertical position Protected from freezing temperatures 3 Proper clearances from combustible surfaces maintained and not installed directly on a carpeted floor 4 Provisions made to protect the area from water damage Metal drain pan installed and piped to an adequate drain 5 Installation area free of corrosive...

Страница 39: ...ight manually 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go the next step 7 Turn on all electric power to the appliance 8 Set the switch on the control to the ON position 9 Turn thermostat to desired setting DANGER Hotter water increases the risk of scald injury Consult the instruction manual b...

Страница 40: ...iring certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs a means such as a mixing valve should be used at the hot water taps used by these people or at the water heater Mixing valves are available at plumbing supply or hardware stores see Figure 8 Figure 9 Follow manu...

Страница 41: ...nds HOT 120 More than 5 minutes LOW 110 Normal shower temp VAC 70 N A Table 4 Note The temperatures indicated are approximates The actual temperature of the heated water may vary The Vacation Setting VAC sets the controller at approximately 70 F This setting is recommended when the water heater is not in use for a long period of time This effectively turns the controller temperature setting down t...

Страница 42: ...cy or your retail supplier regarding the installation of a thermal expansion tank Closed water systems See Closed Water Systems section elsewhere in this manual Smoke odor It is not uncommon to experience a small amount of smoke and odor during the initial start up This is due to burning off of oil from metal parts and will disappear in a short while Strange sounds Possible noises due to expansion...

Страница 43: ... explosive To prevent the possibility of injury under these conditions it is recommended that the hot water faucet located farthest away be opened for several minutes before any electrical appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there will probably be an unusual sound similar to air escaping through the pipe...

Страница 44: ...all the local gas utility to correct the problem and clean or replace the flue and venting before resuming operation of the water heater BLOWER MAINTENANCE Inspect the top of the heater and around the ventilation openings of the blower motor and the rear blower dilution air intakes for any lint and dust that may have accumulated Depending on the location of the heater significant quantities of lin...

Страница 45: ...NG BLOWER FLUE COLLECTOR HOOD 11 32 NUTS MOUNTING PLATE GEAR CLAMP VENT PIPE MOTOR Figure 49 BURNER OPERATION AND INSPECTION Flood damage to a water heater may not be readily visible or immediately detectable However over a period of time a flooded water heater will create dangerous conditions which can cause death serious bodily injury or property damage Contact a qualified installer or service a...

Страница 46: ...Artificially softened water can be exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions The use of a excessively soft water may decrease the life of the water heater tank The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode rod dictates its replacement Note Artificially softened water r...

Страница 47: ... DANGER It is recommended that the temperature pressure relief valve be checked to ensure it is in operating condition at least once a year When checking the temperature pressure relief valve operation make sure that 1 no one is in front of or around the outlet of the T P valve discharge line and 2 that water discharge will not cause any property damage as water may be extremely hot Use care when ...

Страница 48: ...heater is going to be shut down and drained for an extended period the drain valve should be left open with hose connected allowing water to terminate to an adequate drain 6 Close the water heater drain valve when all water in the storage tank has drained 7 Follow instructions in the Filling the Water Heater section 8 Turn ON the gas supply at the main gas shut off valve 9 Follow the lighting inst...

Страница 49: ...m temperature pressure relief valve may be due to thermal expansion or high water pressure in your area E The temperature pressure relief valve may be leaking at the tank fitting F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Combustion products contain water vapor which can condense on the cooler surfaces of the tank...

Страница 50: ...et Snorkel 20 Combo Heating System Supply Outlet Optional 21 Blower with Power Cord see also Figure 61 22 Air Switch inside box see Figure 61 23 Junction Box see Figure 61 24 Junction Box Cover see Figure 61 25 Air Tubing see Figure 61 26 Rubber Coupling see also Figure 61 27 Gear Clamp see also Figure 61 28 Flue Collector 29 Hot Water Outlet Nipple 30 Anode under cap 32 Flexible Manifold Tube see...

Страница 51: ...al gas and Propane main burner with igniter assembly for 60k to 75k Btu hr models Flare Nut Figure 59 17 Figure 60 25 23 24 22 5 26 27 21 Figure 61 Notes Natural gas models have Right hand thread Propane models have Left hand thread For Natural gas models the Flare Nut has Right hand thread For Propane models the Flare Nut has Left hand thread www statewaterheaters com 51 ...

Страница 52: ...ve gas control valve thermostat 1 Turn temperature knob to lower setting 2 Replace the gas control valve thermostat SLOW HOT WATER RECOVERY 1 Insufficient air flue blockage 2 Low gas pressure 3 Orifice too small 4 Thermostat set too low 5 Heater too small 6 Wrong piping connection 7 Wasted hot water 8 Flue clogged 9 Air inlets blocked 1 Provide ventilation to water heater Check flue way flue baffl...

Страница 53: ...ice see rating plate 5 Clean locate source and correct 6 Replace gas control valve thermostat 7 Provide fresh air ventilation UNABLE TO LIGHT THE BURNER 1 Air in gas line 2 Pressure switch 3 Blocked exhaust 4 Wire connection 5 Defective gas control valve thermostat 1 Purge the air from gas line 2 Check the pressure switch make sure the pressure switch hose is not kinked 3 Check vent pipe for block...

Страница 54: ...ncrease ventilation to lower room temperature 4 Install correct orifice RESETTING THE HEATER CONTROL Soft lockouts as diagnosed by the system error codes require the gas control to be reset To reset the control slide the ON OFF switch to the OFF position Wait for 10 seconds and move the switch back to the ON position If the problem that caused the control to lock out has not been corrected the con...

Страница 55: ...e the problem before attempting corrective action See also Flammable Vapor Sensor LED Flash Sequence Control Status Short flash once every four seconds IDLE no call for heat no fault conditions Heartbeat alternates bright dim Call For Heat no fault conditions One Flash three second pause Low Flame Signal control continues to operate Two Flash three second pause Pressure Switch Failed Closed Three ...

Страница 56: ...This page intentionally left blank May be used for notes or to record other installation information 56 www statewaterheaters com ...

Страница 57: ...This page intentionally left blank May be used for notes or to record other installation information www statewaterheaters com 57 ...

Страница 58: ... the working pres sure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale deposits used in a non corrosive and non contaminated atmo sphere used with factory approved anode s installed in its original installation location in the United States its territories or possessions and Canada sized in accordance with prop...

Страница 59: ...nd City TN 37015 phone 1 800 821 2017 The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor Dealer replacements are made subject to in warranty validation by warrantor PROOF OF PURCHASE AND PROOF OF INSTALLATION DATE ARE REQUIRED TO SUPPORT WARRANTY CLAIM FROM ORIGINAL OWNER THIS FORM DOES NOT CONSTI...

Страница 60: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 821 2017 Fax 800 644 9306 Website www statewaterheaters com ...

Отзывы: