background image

20

8.  Burner may not be firing at proper rate.
  •  Check nozzle size.
  •  Check fuel pump pressure setting.
  •  GPO-199 . . . . . . . . . . . 110 psig (758 kPa)

  •  All others . . . . . . . . . . . 100 psig (689.5 lPa)

9.  Burner may be short cycling.  Short cycling (too frequent off and on) 

of burner will cause sooting.  If unit or burner become dirty at frequent 

intervals,  after  correcting  the  dirt  condition  also  correct  the  control 

settings (or other cause of the short cycling).

10. Oil burner fan wheel may be dirty.

  •  Clean fan wheel with a stiff brush.

11. Draft regulator may be stuck.

  •  Check to see if valve swings freely.  Clean, if vane is stuck.

12. Priming control safety reset is open.

  •  Reset safety switch on burner mounted primary control, see

 SAFETY 

PRIMARY CONTROL, page 21.

13. Burner motor safety reset is open.

BURNER STARTS-WON'T OPERATE

1.  No oil in tank.

2.  Oil line valve closed.

3.  Loose connection in primary control.

  •  Check and tighten all wire connections, see SAFETY PRIMARY

 

CONTROL -page 21.

4.  Electrode out of adjustment.

  •  Clean firing head and readjust electrodes.

5.  Clogged burner nozzle.

  •  Replace with new nozzle, see nozzle chart, page 9, table 8.

  •  Nozzle should be replaced semiannually.

6.  Dirty filter.

  •  Replace element in oil filter.

WATER IS TOO HOT

1.  Refer to WATER TEMPERATURE, page 10.

WATER HEATER MAKES SOUNDS

1.  Sediment or lime scale accumulations cause noises when the tank 

bottom should be cleaned.  Refer to MAINTENANCE, page 11-13 for 

details.

2.  Some of the electrical components of the water heater makes sounds

 

which are normal.

  •  Contacts click or snap as the heater starts and stops.
  •  Transformers often hum.

WATER LEAKAGE IS SUSPECTED

1.  Check to see if the water heater drain valve is tightly closed.

2.  The  apparent  leakage  may  be  condensation  which  forms  on  cool 

surfaces of the heater and piping.

3.  If the outlet of the relief valve is leaking it may represent:

  •  Excessive water pressure.

  •  Excessive water temperature.

  •  Faulty relief valve.

Excessive  water  pressure  is  the  most  common  cause  of  relief  valve 

leakage. It is often caused by a "closed system". If a check valve is in the 

inlet system it will not permit the expanded hot water volume to equalize 

pressure with the main. The relief valve must release this water or the 

water heater or plumbing system will be damaged. This condition is not 

covered by the limited warranty. The solution is to add a thermal expansion 

tank between the check valve and the water heater.

BURNER WON'T START

When  the  thermostat  calls  for  heat  but  the  burner  won't  start, 

check to make sure that you have proper voltage to the primary 

control.

 

CAUTION

When checking the low voltage circuit at the control, DO NOT TOUCH 

THERMOSTAT WIRES TO FLAME DETECTOR TERMINALS AS THIS 

WILL BURN OUT THE SENSOR IN THE SAFETY PRIMARY CONTROL.

If the voltage checks normal:

1.  Flame detector may be sooted or seeing false light and will not let the 

motor relay pull in.

2.  Loose wiring.

3.  Bad flame detector (mounted inside housing beneath transformer).

4.  Reset red safety button (primary control).

5.  Defective primary control.

6.  Reset motor protector.

BURNER STARTS BUT FAILS TO RUN

When the burner starts (motor running) but flame is not established, the 

control will lock out on safety in about 15 seconds. If the control does not 

lock out on safety, then the control is defective and should be replaced. 

When the motor is running but flame is not established, then the problem 

becomes:

1.  There is insufficient or no oil getting into the combustion chamber.

2.  There is no spark to ignite the oil.

If the problem is insufficient or no oil getting into the combustion chamber, 

check for the following:

1.  Dirt or water in the supply line.

2.  Slipping coupling between motor and pump.

3.  Defective pump.

4.  Clogged, defective or too small a nozzle.

5.  Oil tank empty.

6.  Clogged filter in oil line.

7.  Restriction or kink in fuel line.

8.  Ice in fuel line.

9.  Air leak in inlet connections.

Содержание GPO 69-700A

Страница 1: ...ER FOR HOT WATER SUPPLY Installation Operation Service Maintenance MODELS GPO 86 199 THRU GPO 69 700 A CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS INFORMATION RELATIVE TO YOUR SAFETY PLEASE READ THOROUGHLY BEFORE USING APPLIANCE 500 Tennessee Waltz Parkway Ashland City TN 37015 www statewaterheaters com Phone 1 800 821 2017 Fax 1 800 433 2515 ...

Страница 2: ...50 2357 2063 1833 1650 1500 1375 1269 1179 GPO 700 000 69 80 GPH 1677 1341 1118 958 838 745 671 610 559 516 479 69 700 A 205 261 LPH 6347 5077 4231 3627 3173 2821 2539 2308 2116 1953 1813 ALL DIMENSIONS IN INCHES mm Model numbers followed by the suffix A indicates the optional A S M E tank construction TABLE 1 NOMINAL MODEL DIMENSIONS GPO 86 199 GPO 86 245 GPO 84 315 A GPO 75 385 A GPO 75 455 A GP...

Страница 3: ...burner and controls are listed by Underwriters Laboratories Inc Accordingly the burner bears one of the UL labels indicating periodic inspection of the production of this equipment All ASME tanks are built to the standards of Section IV of the American Society of Mechanical Engineers code and are stamped with their symbol The National Board of Boiler and Pressure Vessel Inspectors papers are furni...

Страница 4: ...AL COMPONENTS WITH WET HANDS OR WHEN STANDING IN WATER WHEN REPLACING FUSES ALWAYS USE THE CORRECT SIZE FUSE FOR CIRCUIT If it is necessary to reset the safety primary control depress red button one time only If burner does not operate after depressing red button one time call service agent INSTALLATION REQUIRED ABILITY INSTALLATION OF SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO TH...

Страница 5: ...e inches 2 All Air From Outdoors The confined space shall be provided with two permanent openings one in or within 12 of the top of the enclosure and one in or within 12 of the bottom The openings shall communicate directly or by means of ducts with outdoors or such spaces that freely communicate with outdoors If the appliance room is located against an outside wall and the air openings communicat...

Страница 6: ... or if a suitable draft cannot be obtained additional make up air must be provided to the room to assure proper venting and combustion Note A negative draft must be maintained in the vent piping The barometric draft regulator must be installed in the same room as the heater fig 6 Locate the regulator as close as possible to the heater and at least 18 457 2 mm from a combustible ceiling or wall A m...

Страница 7: ... diagrams on pages 14 18 Contact the local plumbing authority DRAIN VALVE AND ACCESS PANELS The heaters are equipped with a 3 4 NPT drain valve mounted above and to the left of the oil burner see FEATURES page 2 An access panel is located above and to the left of the oil burner and covers the flame observation port fig 7 A plug is inserted into the flame observation port and must be removed in ord...

Страница 8: ...g runs which includes lift as shown in Table 7 TABLE 7 Distance Max Distance Max Tank Run length Tank Run Length Bottom Ft M Bottom Ft M Below Below Pump 3 8 1 2 Pump 3 8 1 2 Plug O D O D Plug O D O D Ft M Tubing Tubing Ft M Tubing Tubing 1 0 3 74 22 5 100 30 4 9 2 7 51 15 5 100 30 4 2 0 6 71 21 6 100 30 4 10 3 0 48 14 6 100 30 4 3 0 9 69 21 0 100 30 4 11 3 3 45 13 7 100 30 4 4 1 2 66 20 1 100 30 ...

Страница 9: ...for single pipe or two pipe installations either lift or gravity feed On gravity feed installations the inlet pressure is not to exceed 3 psig On one pipe lift installations the lift is not to exceed 8 ft The two stage pumps are for two pipe lift installations where the inlet vacuum does not exceed 20 hg vacuum AIR BLEED PROCEDURE Refer to oil burner manual OPERATION GENERAL Never operate the heat...

Страница 10: ...during heavy draws FIGURE 18 THERMOSTAT adjustable set for desired water temperature It is suggested the thermostat be turned to the lowest setting which satisfies the hot water requirements of the system This helps minimize scale formation in the heater HIGH LIMIT not adjustable manual reset factory set to cutout at 195 F 90 5 C If the high limit is actuated the safety primary control will cause ...

Страница 11: ...be shut down and exposed to freezing temperatures Maintenance and service procedures may also require draining the heater 1 Turn off the oil burner electrical disconnect switch If required for draining the heater turn off the oil line supply valve 2 Open a nearby hot water faucet until the water is no longer hot 3 Close the cold water inlet valve 4 Open the heater drain valve 5 If the heater is be...

Страница 12: ...3 16 vent hole in handle A stainless steel screw is included with the Flo Jug kit This screw is to be installed in the vent hole when Flo Jug is not in use Remove drain valve from heater and insert a 3 4 x 4 drain nipple Connect the clamp 1 I D x 3 hole to Flo Jug and drain nipple 3 Lift the Flo Jug to the POUR POSITION and permit the UN LIME to flow into the heater as rapidly as possible Be sure ...

Страница 13: ...n chamber lining 4 Remove oil burner assembly and using a vacuum cleaner remove all loose soot from combustion chamber area Avoid contact with combustion chamber as it can be damaged quite easily If flange gasket is damaged replace with State Part No 24165 5 Upon completion of cleaning reassemble the heater It may be necessary to apply new sealer tape to the top cover to ensure proper venting New ...

Страница 14: ...TION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES NOTE WHEN USING A STATE T 140 200 350 OR 400 STORAGE TANK USE LOWER 3 4 19 mm OPENING FOR TANK...

Страница 15: ...E TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES WIRING DIAGRAM FOR 180 F 82 2 C LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER SUPPLY LINE IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY INSET B VACUUM R...

Страница 16: ...FE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES WIRING DIAGRAM FOR 180 F 82 2 C LOOP IF USED INSTALL IN ACCORDANCE WITH LOCAL CODES WIRING DIAGRAM FOR TEMPERED WATER LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER S...

Страница 17: ...FE TEMPERATURESAT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES INSET B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES INSET A INSTALL THERMAL EXPANSION TANK IN COLD WATER SUPPLY LINE IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY WIRING DI...

Страница 18: ...OL IN AN UNINSULATED TEE BEYOND THE DISHWASHING MACHINE TAKEOFF IN THE SANITIZING LOOP CONTROL SHOULD BE SET AT 185 F 85 C NOTE 3 ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE TANK NOTE 4 IF TEMPERED WATER IS RECIRCULATED RETURN LINE SHOULD BE CONNECTED AT POINT A WIRING DIAGRAM FOR 180 LOOP IF USED INSET A INSTALL THERMAL EXPANSION TANK IN COLD WAT...

Страница 19: ...nits with the higher water flow may have a shortened life Unions and T P valves shown in piping diagrams are not included in the manifold kits Dimensions shown are for minimum space occupied by complete assemblies Service space in front of units must be added DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURES AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 10 IF HIGHER PREHEA...

Страница 20: ...xcessive water pressure Excessive water temperature Faulty relief valve Excessive water pressure is the most common cause of relief valve leakage It is often caused by a closed system If a check valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the water heater or plumbing system will be dama...

Страница 21: ...ust be reset before trying again for ignition When this occurs allow about 5 minutes for safety heater to cool before depressing the red safety button Depress red button one time only If burner does not operate after depressing red button one time check combustion chamber If combustion chamber is soaked with oil the combustion chamber must be replaced Some of the possible reasons for flame failure...

Страница 22: ...nting screws slightly and shift Noisy fuel pump in different positions until noise is eliminated Operation Retighten mounting screws Air in inlet line Check all connections Use only good flare fittings Tank turn on two line pipe system and inside tank Install return line hum eliminator Partially clogged strainer or filter Remove and clean strainer Air leak in intake line Tighten all fittings Air l...

Страница 23: ...199 245 315 385 455 700 AND GPO 315A 385A 455A 700A ITEM NO 6 ITEM NO 11 REPLACEMENT PARTS LIST CLEANOUT ASSEMBLY OIL STATE WATER HEATERS 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 821 2017 Fax 800 644 9306 www statewaterheaters com ...

Страница 24: ...260 181260 181260 181260 181260 8Plug Observation 41377 1 41377 1 41377 1 41377 1 41377 1 41377 1 9Reducer Flue 99767 2 76707 1 10 Valve Drain 9003906015 9003906015 9003906015 9003906015 9003906015 9003906015 11 Valve Relief 9005899205 9005903205 9005903205 9005903205 9005903205 9006187205 12 Instruction Manual 195092 003 195092 003 195092 003 195092 003 195092 003 195092 003 13 Thermostat with E ...

Отзывы: