Voltage  leakage  down  earth  wires  from  transformer  casings,  due  to 
failing transformer insulation. 

• 

Patrolman  work  where  energised  high  voltage  conductors  maybe 
hazardous to personnel. 

• 

Ground step potentials. 

Limitations: 
LiveTester  is  a  non-contact  detector  and  as  such  depends  on  sensing  an 
electric  field  generated  by  an  energized  conductor.  Electric  fields  are  easily 
modified,  and  in  some  cases  completely  eliminated,  in  certain  situations  by 
the  presence  of  conductors  other  then  the  energised  conductor  under  test. 
These other conductors can be either earthed or energised by another phase 
in the system . Operators should be aware of these effects, and take steps to 
ensure the conductor to be tested is approached in a part of the line where no 
other  conductors  are  close  by.    A  good  rule  of  thumb  is  to  ensure  all  other 
metal  objects  are  at  least  twice  the  distance  from  the  LiveTester,  as  the 
distance  from  the  LiveTester  to  the  conductor  to  be  tested.  Also  it  should  be 
noted  that  an  energised  conductor  laying  on  wet  or  dew  covered  or 
submerged ground may still be energised, but possibly will not be detected by 
a non-contact detector. The moisture dissipates the electric field. LiveTester is 
not  suitable  for  detecting  armoured  or  shielded  conductors,  because  the 
shielding prevents any electric field from escaping. 
LiveTester is not suitable for detecting conductors energised with D.C. voltage 
or at frequencies other than 50 or 60 Hz. That is it would not be suitable for 
400Hz aircraft systems, or D.C. railway systems.  
LiveTester is not recommended for detecting buried conductors.  
 

 
13. Intellectual Property

 

The  contents  of  this  document,  LiveTester  front  panel  artwork,  printed  circuit 
board  artwork,  and  firmware  (programs  contained  in  integrated  circuits)  are 
subject  to  copyright  and  can  not  be  reproduced,  transmitted  in  any  language 
or  computer  language,  in  any  form  or  any  means,  electronic,  mechanical, 
optical,  chemical,  manual,  or  otherwise,  without  prior  written  consent  from 
StarLogixs Pty. Ltd.  
The  Electric  Field  Detection  System  in  the  LiveTester  is  protected  by 
international  patents.  The  Static  Discriminator  System  is  also  protected  by 
patent applications. 

  

 