17
COMMISSIONING AND HANDOVER
On completion of the installation allow a suitable
period of time for any fire cement and mortar to dry
out, when a small fire may be lit and checked to
ensure the smoke and fumes are taken from the
stove up the chimney and emitted safely to the
atmosphere.
Do not run at full output for at least
24 hours.
Ensure that the operating instructions for the stove
are left with the customer. Ensure to advise the cus-
tomer on the correct use of the appliance with the
fuels likely to be used on the stove and warn them to
use only the recommended fuels for the stove.
Advise the user what to do should smoke or fumes
be emitted from the stove. The customer should be
warned to use a fireguard to BS 8423:2010 in the
presence of children, aged and/or infirm persons.
OPERATION
Check that all dampers and catches are operating
correctly and ensure that all flue connections are
thoroughly sealed.
Fig.18
Fig.19
AIR CONTROLS
The HPB model has two independent controls and
the NB/ DHW has three controls:
1.
The spin valve, located at the bottom end of
the door controls the primary air (see Fig.
18). Rotate anti-clockwise to open and
clockwise to close.
2.
The window wash is located above the door
(see Fig. 19). Push left to open and right to
close. The Non Boiler and DHW models
have an additional secondary air system
which is controlled by a push/ pull slider
located at the bottom right hand side of the
stove (See fig. 20), push to open and pull to
close.
NOTE:-
The controls may become hot when the stove is in
operation, use tools or glove provided to adjust the
controller when the stove is hot.
Push to open, pull to close
Fig.20
Primary Air Control
Window Wash
Secondary Air Control
(DHW/ NB Models)
Wood
Closed or slightly
open if required
Adjust as required
Adjust as required
Coal
Adjust as required
Open
Closed
Anthracite
Adjust as required
Closed
Closed
Содержание Tara
Страница 27: ...27 NOTES ...