background image

 

 

31 

3. Check EEV step.  

4. Check the compressor frequency and current.  

5. If they are OK, replace a new compressor driver 
board. 

F20 

IGBT Power Device 
Overheat Alarm 

 

1. Check the fans are running or not. 

2. Check the installation distance and space. 

3. If they are OK, please replace a new 
compressor driver board. 

4. Leave enough distance and space to make heat 
pump have a good transfer heating condition. 

5. Clean air to fin heat exchanger. 

F22 

AC input overcurrent 
protection alarm 

 

Only in single phase unit. Restart the unit.  

1. Check if there is electric leakage. 

2. If still have the failure, replace a new drive 
board. 

F23 

EEPROM Fault 
Alarm 

 

1.  Check the connection;  

2.  Replace a new driver board; 

F24 

Destroyed EEPROM 
Activation Ban Alarm 

 

F25 

LP 15V Underload 
Fault 

 

1. Check the power supply is stable or not, and 
restart unit.  

2. If the problem still on, please replace a new 
drive board. 

F26 

IGBT Power Device 
Overheat Fault 

 

1. Check the fans are running or not

  

2. Check the installation distance and space;  

3. Leave enough distance and space to make heat 
pump have a good transfer heating condition;  

4. Clean the finned heat exchanger.  

5. If they are OK, please replace a new driver 
board; 

F031 

DC Fan Motor 1 
Failure 

 

1. Turn off the unit and check the connection.  

2. Restart and check if the motor is running normal 
or the error happens again.  

3. Replace a new fan motor. 

F032 

DC Fan Motor 2 
Failure 

 

Pp1 

Exhaust Pressure 
Sensor Fault 

 

1. Detect the exhaust pressure sensor connection  

2. If the connection is OK, please replace a new 
one. 

Pp2 

Suction Pressure 
Sensor Fault 

 

1. Detect the suction pressure sensor connection  

2. If the connection is OK, please replace a new 
one. 

Содержание Solis ECO

Страница 1: ...Solis ECO Monoblock Air to Water Heat Pump Operation and Installation Manual...

Страница 2: ...or the unit is damaged as a result of improper installation debugging unnecessary maintenance which is not in line with this manual The unit must be installed by qualified personnel It is vital that t...

Страница 3: ...may lead to harm of people or loss of material Prohibition What is prohibited will be nearby this icon Compulsory implement The listed action need to be taken ATTENTION include WARNING Please pay atte...

Страница 4: ...heat pump needs to be repaired please entrust dealer or qualified person to carry it out Improper movement or repair on the unit will lead to water leakage electrical shock injury or fire Installatio...

Страница 5: ...hot water The Series is featured as follows 3 1 DC Inverter EVI Heat Pump Technology a Ruking Driver Board Ruking driver board controls the compressor running precisely basing on water temperature an...

Страница 6: ...is an environment friendly choice for reducing CO2 emission Meanwhile R32 heat pump needs 30 less amount than R410A heat pump 3 5 Low Noise of 37dB A With a new internal noise reducing design Solis Ec...

Страница 7: ...le app on your smartphone This effectively saves manpower during the after sales service period The fault report button allows a direct error reporting channel to the local service provider When an er...

Страница 8: ...4 Unit Dimension mm 4 1 Models Solis Eco Monoblock 5 Handling Installation 5 1 Packing List Heat Pump Unit 1 Display Mounting Plate 1 Rubber Feet 4 Drain Connection 1...

Страница 9: ...Display Connecting Wire 1 Thermistor 1 optional accessory 5 2 Installation Site Requirement Unit mm...

Страница 10: ...Solis Eco L 1006 H 805 W 442 A 750 B 473 P1 200 P2 150 P3 B 100 2...

Страница 11: ...of I I Heating Condition Ambient Temp DB WB 7 6 C Water Temp In Out 30 35 C Heating Capacity Range kW 2 29 8 25 Heating Power Input Range kW 0 63 1 81 Heating Current Input Range A 3 2 8 0 Cooling Con...

Страница 12: ...Operating Ambient Temperature 25 43 Fan Quantity 1 Fan Motor Type DC motor Fan Motor Power Input Min Max W 30 75 Fan Speed RPM RPM 300 850 Water Connection Inch Inch 1 Water Pressure Drop max kPa 28...

Страница 13: ...h a pre plumbed internal unit from Waterford Stanley that will combine the central heating and buffer tank and many of the essential system components 1 Heat Pump 9 Expansion Vessel 16 Heat Emitter 4...

Страница 14: ...consulting the engineer Ensure the pressure is correct and and pressure vessel is in working order otherwise the performance and reliability of the unit will become compromised Ensure the waterways ar...

Страница 15: ...a cleaning agent Do not use abrasive cleaners Do not use solvents Do not use any cleaning agents that contain chlorine or ammonia 8 3 3 Checking the evaporator fan and condensate discharge Check whet...

Страница 16: ...d Controller Supplied 5 core 0 75mm2 10 metres 4 Domestic Hot Water Temperature Probe Supplied 2 core 0 75mm2 10 metres 5 Internal to External link cable 5 Core 0 75mm2 Duct Grade 6 Call for Heat Sign...

Страница 17: ...17 10 Display Operation Guide 10 1 Main Interface Display and Function 1 Power on Interface 2 Starting up Interface...

Страница 18: ...owing up The display will enter fault record interface after tapping this icon Defrosting The unit is in defrosting mode when this icon shows up Electric Heater The unit is in electric heater mode whe...

Страница 19: ...ing heating mode icon then the display will enter this mode s interface 3 tapping cooling mode icon then the display will switch to this mode s interface 4 tapping hot water heating mode icon then the...

Страница 20: ...cooling mode can be set by the pop up keyboard When the target temp is being set the pop up keyboard is shown as following Key No Key Name Key Function Target temp the new target temp under the curre...

Страница 21: ...e Key color Key function Return key Click this key to return to the main interface Enable the timer on off Enable Green ON Disable Gray OFF Click this key to start or turn off the timed function Enabl...

Страница 22: ...tric heating Click this key to turn on the unit Electric heating Factory parameter Click the key and enter the password to enter the factory parameter settings and status parameters interface System t...

Страница 23: ...Key Name Key Function Return key Click this key to return to the setup interface Up key Click this key to increase the value Down key Click this key to decrease the value Cannel key Click this key to...

Страница 24: ...e cooling side is running clicking the icon the electric heating will not be turned on 4 Tapping Mute setting button then the interface display is shown as follows Note When the unit is enabled to act...

Страница 25: ...minutes and the 12 sets of temperature data are saved every hour Timekeeping is made from the latest data saving if the power is disrupted when the time is less than 1 hour 12 sets the data during suc...

Страница 26: ...able Check the 3 phase power cable whether connected in right phase sequence cannot start up the unit The unit have error Cables has disconnected Display Cables Check the display whether shown error C...

Страница 27: ...ressor Check other components 11 2 Error Code Instruction Error code Error name Relevant parts information Review and resolve E04 Electric heater overheat Protection 1 Check the Electrical heating Ove...

Страница 28: ...mp 0 water inlet 2 It is the protection in winter Once the water temperature up to 15 o C or the ambient temp is higher than 1 o C the error code disappears E032 Flow Switch Protection Flow switch is...

Страница 29: ...ompressor driver board 3 Check the compressor resistance 4 Check compressor driver board F03 PFC Fault Restart the unit 1 Check the power supply connection and voltage supply is stable or not 2 2 Repl...

Страница 30: ...e the voltage between 12V and GND on compressor driver board if higher than 15V or lower than 7V please replace a new one compressor driver board F13 IPM Overheat Stop 1 Check the fans are running or...

Страница 31: ...arm F25 LP 15V Underload Fault 1 Check the power supply is stable or not and restart unit 2 If the problem still on please replace a new drive board F26 IGBT Power Device Overheat Fault 1 Check the fa...

Страница 32: ...ensor Fault P101 EVI Inlet Temp Sensor Fault P102 EVI Outlet Temp Sensor Fault P153 Coil Temp Sensor Fault P181 Exhaust Temp Sensor Fault P182 Exhaust Over Temp Exhaust temp C05 default 110 1 Measure...

Отзывы: