7

A flue that has proved to be unsatisfactory, particu-
larly with regard to down draught should not be used
for venting this appliance until it has been examined
and any faults corrected.  An existing masonry chim-
ney should be inspected and if necessary repaired
by a competent mason or relined using an approved
lining system.

The stove must  be connected to a chimney with a
minimum continuous draught of 0.06 w.g. Poor
draught conditions will result in poor performance.

All register plates, restricter plates, damper etc.,
which could obstruct the flue at a future date should
be removed before connecting this appliance.

If connecting to an existing chimney with a flue
diameter of more that 8” it is recommend to line the
flue using a suitable stainless steel flue liner.

Where a masonry chimney is not available a propri-
etary type of 6”/150mm - twin wall, fully insulated
pipe may be used. The pipe must terminate at a
point not lower than the main ridge of adjacent out-
side obstructions.  With such installation, access to
the chimney must be provided for cleaning purpos-
es.  

A chimney / flue termination must be located to min-
imise wind effects, a basic guide is that the distance
from the termination to the roof should be at least
2300mm when measured horizontally and at least
1000mm when measured vertically, (see Fig.1). In
circumstances where there are adjoining buildings/
structures/ roof openings there are additional
requirements, please refer to building regulations
part J.

Fig.1

FITTING INSTRUCTIONS

The stove is designed to allow the chimney be
cleaned through the stove. 
Step 1
Ensure the opening is suitable for fitting of the stove.
(See Fig. 2)

Fig.2

Step 2
Ensure the area on which the stove will be seated is
level.

Step 3
Ensure that access is available to fit the flue spigot,
flue adaptor and flue connection pipes subsequent
to fitting the unit in its final position. To achieve this
it may be necessary to fit an inspection hatch in the
chimney structure above or to the side of the unit. 

Step 4
Fit the stove in position so that the edge of the shell
is flush with the wall on both sides.

Step 5
Complete the flue installation sealing all joints with 
appropriate fire cement.

Step 6
Complete the Electrical connection to the appliance
(See Electrical Supply)

Step 7
Remove the fire door by opening the door slightly &
lifting it up to detach from the bottom hinge (see
Fig. 3).

525

IS100DS - 1030
IS80DS - 830

670

Fig.3

LIFT DOOR TO RELEASE 
FROM BOTTOM HINGE

Содержание Solis 80cm Single Sided Insert I80SS

Страница 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where childr...

Страница 2: ...arm Air Ducting System 11 18 Position of Warm Air Duct 11 19 Fitting the Warm Air Duct to the Stove 11 20 Stove Dimensions 12 21 Commissioning and Handover 12 22 Operation 12 23 Air Controls 13 24 Fan...

Страница 3: ...requirements of the manual Failure to comply with the Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufactu...

Страница 4: ...d be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any...

Страница 5: ...ensure that there are no blockages Check flue ways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of ashes in the ash pan as this wil...

Страница 6: ...cations may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys BS EN 14336 2004 Heating Systems in...

Страница 7: ...wind effects a basic guide is that the distance from the termination to the roof should be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumst...

Страница 8: ...ver the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 7 Fig 7 Direction of win...

Страница 9: ...ld be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms where this appliance is fitted additional air vents may be required to allev...

Страница 10: ...e adhere to Clearance to Combustible Section Fig 8 3 ID ALUMINIUM FLEXIBLE DUCT PIPE ENDS TO BE COVERED WITH MESH 3 OD CONNECTOR SADDLE Fig 9 600mm 600mm HEAT RECOVERY VENTILATION Where a stove is to...

Страница 11: ...xit in addition to the one required to be placed in the room with the appliance POSITIONING OF THE WARM AIR DUCT The following must be adhered to when locating the warm air duct system The air duct mu...

Страница 12: ...t with the customer Ensure to advise the cus tomer on the correct use of the appliance and warn them to use only Wood Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Страница 13: ...n the lower casing of the stove has reached 50 degrees C in order to protect the electric components When the warm air ducting system is connected the air vents above the firedoor can be closed off us...

Страница 14: ...ndover the installer should demonstrate how to operate the stove correctly LIGHTING THE STOVE 1 Open the fire door and open the primary secondary air inlets by pushing the two air control levers to th...

Страница 15: ...ould be placed on a non combustible material pending final disposal If ashes are buried in soil or otherwise dumped they should be retained in the closed container until they are thoroughly cooled Ope...

Страница 16: ...r a prolonged peri od of time then it should be given a thorough clean to remove ash and unburned fuel residues To enable a good flow of air through the appliance to reduce condensation and subsequent...

Страница 17: ...pulsory requirement under cur rent Building Regulations For ROI an additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Pa...

Страница 18: ...18 ELECTRICAL DIAGRAM...

Страница 19: ...SPIGOT E2026 10 WARM AIR DUCT SPIGOT E2025 11 GLASS FIXING BRACKET JUN100 JUN80 12 GLASS 20CRC100DEK 20CRC80DEK 13 FIRE DOOR PTAKR100 PTAKR80 NO DESCRIPTION PART CODE I100DS I80DS 14 DOOR ROPE SEAL CO...

Страница 20: ...20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 N00777AXX Rev 001 SG 210518...

Отзывы: