One-Touch™ Test Mode
Test
Action
Observation
Normal
Operation
GREEN system status LED flashes at normal rate.
RED and GREEN input status LEDs off.
GREEN output status LED off.
One-Touch™
View Mode
Hold down One-Touch™ button for less than
2 seconds.
Note: Automatically exits after 2 minutes.
GREEN system status LED flashes at twice normal
rate.
Unconfigured system: All RED LEDs will flash
briefly three times and test mode is exited.
Configured system (expected)
RED LED = tamper state.
GREEN LED = active state/normal output.
GREEN LED off = non-active state/unconfigured
input.
View mode is intended for a configured system. See help for
more information.
One-Touch™
Active Mode
CAUTION:
Disconnect any output relays that should not be triggered before entering
Active mode.
Hold down One-Touch™ button for 2 to 4
secs.
GREEN system status LED flashes faster than
normal.
Trigger each input sensor in turn and ensure
that the LEDs indicate the correct state.
Note: The controller will operate
unconfigured and no system
communications will occur.
The first change in state will be latched and the display for that
input will not change until test mode is exited.
Green - Red
2-STATE
4-STATE
N/A
Input open
N/A
Input closed
Input open
Input open tamper
Input closed
Input tamper short
Green - Red
3-STATE NO
3-STATE NC
N/A
N/A
Input open
Input closed
Input closed
Input open
Input open tamper
Input tamper short
>
>
GREEN output LED is on/off for a 5 second cycle
(relays active/inactive)
Exit One-Touch™
Active Test mode
Hold down One-Touch™ button for less than
2 seconds. One-Touch™ Test mode will
automatically be timed out after 1 hour,
power up or power down.
GREEN flashes at normal rate again.
All other status LEDs off.