Usage
LEDs
Red / Green
Green
Red
Access denied
Access permitted
Default
Sounder
•
The reader sounds 4 rapid beeps when it is powered up or restarted.
•
If specified, the reader beeps once when a token is presented.
Cable Lengths
PAC door controllers only
Distance from Reader to Controller
Cable Gauge
AC 202 / 512
AC 2100 / 2200
230
′
/ 70m *
750
′
/ 250m
7/0.2 0.34mm² 22AWG
230
′
/ 70m *
1500
′
/ 500m
16/0.2 0.5mm² 20AWG
230
′
/ 70m *
3000
′
/ 1000m
32/0.2 1.0mm² 18AWG
Notes
•
These figures (*) are for readers powered from the controller. The cable distances
can be increased to 1650
′
/ 500m by locally powering the readers.
•
Locally powered readers must be connected to a UL 603 power limited Class 2
supply for US, or a ULC S318 power limited Class 2 supply for Canada.
•
If you use 22AWG / 0.34mm² cables, twist the wires and double them over before
inserting them in the crimps.
•
Maximum cable distances will be less for readers which have been set to give
Wiegand output.
Specification
Current
Power
Reader Range
90mA
12V–24V DC
Up to 4.0
″
/ 100mm
11
English