Position of adjustments
Stability Table
Switch position
0 = under 100kW
5 = 2500 - 3200 kW
1 = 100 - 500 kW
6 = 3200 - 4000 kW
2 = 500 - 1000 kW
7 = 4000 - 4800 kW
3 = 1000 - 1800 kW
8 = not used
4 = 1800 - 2500 kW
9 = not used
Страница 1: ...ation is limited to a safe period by internal shutdown of the AVR output device This condition remains latched until the generator has stopped For complete protection a miniature circuit breaker optio...
Страница 2: ...eference used for dc voltage comparison purposes Soft start circuit overrides the precision voltage reference during run up to provide a linear rising voltage Amplifier compares the sensing voltage to...
Страница 3: ...Position of adjustments Stability Table Switch position 0 under 100kW 5 2500 3200 kW 1 100 500 kW 6 3200 4000 kW 2 500 1000 kW 7 4000 4800 kW 3 1000 1800 kW 8 not used 4 1800 2500 kW 9 not used...
Страница 4: ...s a latched fault requiring the generator to be stopped for reset Over voltage monitor continuously monitors the voltage at the AVR terminals and provides signals to shut down the AVR power output dev...
Страница 5: ...lowing easier engine recovery Dwell adjustment The DWELL operates only when the speed has fallen below the knee point set by the UFRO adjustment With the DWELL control turned fully anti clockwise ther...
Страница 6: ...n the circuit breaker connects to the AVR which provides a trip signal to energise the coil in the event of an over excitation condition An over excitation condition is indicated by a flashing red LED...