DMXBUS-K 

- Gateways

Programming manual  

v2.1.2

 

www.besknx.c

z

 

3

 

Programming 

3.1

 

Application program information 

Application program: Ingenium / Dimmers (manufacturer / program name). 

Catalogue version: v2.1.2 

Maximum number of communication objects: 24. 

Maximum number of assignments: 25. 

ETS minimum required version: 4.1.8 (build 3614) 

The  parameters  of  the  gateway  are  configured  with  a  specific  parameter  dialog  (plug-in);  do  click  on  “open”  from  the 
parameters menu in the ETS to run it.  

3.2

 

Individual Address 

This KNX-DMX gateway is a device that allows having more than one internal individual address. Each DMX device is virtually 
represented in its memory as a KNX dimmer with its own communication objects and individual address.  

This KNX-DMX gateway answers always with the individual address 15.15.255 to the "devices in programming mode" check 
procedure from the ETS, even if it has been already programmed with virtual DMX dimmers. However, an individual address 
existence check or line scan will report all virtual dimmers in the KNX-DMX gateway memory.  

When a virtual dimmer is programmed in the gateway memory, the individual address cannot be overwritten with the same 
device because the ETS will show a “more than one device in programming mode” error. It is highly recommended to delete 
the internal memory of the device before programming in order to avoid these problems (see next paragraph). 

3.3

 

Restore factory settings 

This KNX-DMX gateway allows to restore factory settings just using the programming button. To get this functionality, it is 
necessary to disconnect the power supply (230Vac) from the device, push the programming button and connect again while 
holding the programming button for 5 seconds. When LED status turns on, it indicates that the gateway has been successfully 
restored. 

Содержание BES-GW612100

Страница 1: ...Gateways KNX DMX512 BES GW612100 v2 1 2 Programming manual z ...

Страница 2: ...ON PROGRAM INFORMATION 5 3 2 INDIVIDUAL ADDRESS 5 3 3 RESTORE FACTORY SETTINGS 5 3 4 ADDING DMX LIGHTS 6 3 4 1 Device type 6 3 4 2 Parameters 7 3 5 COMMUNICATION OBJECTS 8 3 5 1 Objects table 8 3 5 2 Objects description 9 3 6 SCENES SEQUENCES PROGRAMMING 10 3 6 1 How to create a scene 10 3 6 2 Nomenclature 10 3 6 3 Commands 11 4 INSTALLATION 12 ...

Страница 3: ...annels supported by DMX protocol and to execute up to 16 scenes being easily programmable through the projects developing software ETS Thanks to this gateway it is possible to develop the integration of a DMX device or system into a KNX home automation installation and regulate individually each DMX channel in a simply way like any other KNX dimmer or to program a complex group of commands in a sc...

Страница 4: ...l Size 6 modules Connections BUS connection terminal KNX Screw terminals for main supply and DMX bus DMX Channels Up to 512 DMX channels emulation Environment temperature range Operation 10ºC 55ºC Storage 30ºC 60ºC Transportation 30ºC 60ºC Regulation According to the directives of electromagnetic compatibility and low voltage EN 50090 2 2 UNE EN 61000 6 3 2007 UNE EN 61000 6 1 2007 UNE EN 61010 1 ...

Страница 5: ...55 to the devices in programming mode check procedure from the ETS even if it has been already programmed with virtual DMX dimmers However an individual address existence check or line scan will report all virtual dimmers in the KNX DMX gateway memory When a virtual dimmer is programmed in the gateway memory the individual address cannot be overwritten with the same device because the ETS will sho...

Страница 6: ... in the corresponding application To do so from the topology window do right click on the device and select Edit parameters General The device type parameter allows selecting the corresponding device that will be programmed by the application The ETS will show or hide communication objects and parameters according to this parameter In this case the device that must be selected is Dimmers DMX Chann...

Страница 7: ...light whose address is configured here Name Ramp speed sec Values From 0 to 255 Description It is the brightness change rate measured in seconds The brightness changes gradually when using Channel X value or dimming communication objects Typical value 10 seconds Now we can associate the device communication objects to the group addresses as always in the ETS The KNX telegrams will be translated by...

Страница 8: ... software requests for it Repeat again to control the next DMX light with address 2 adding a new Dimmer application to the gateway memory and setting its DMX address parameter a value of 2 and so on with the other DMX lights 3 5 Communication objects 3 5 1 Objects table Object Name Function Length DPT Flags C R W T U 0 CH1 on off 1 bit 1 001 1 CH1 dimmer 4 bits 3 007 2 CH1 value 1 byte 5 001 3 CH1...

Страница 9: ...or down slowly according to the ramp speed configured Name Object 3 CH1 On Off state Function 1 bit communication object for feedback signalling of the on off state of the channel Description When the light is off and receives a switch on telegram or a brightness value a 1 is sent through this object When the light is on and it receives a switch off telegram or a brightness value of 0 a 0 is sent ...

Страница 10: ... Scenes sequences programming The DMXBUS K gateway allows to program 16 scenes including up to 256 commands each 3 6 1 How to create a scene The scenes which will be executed must be created previously using text files that have to be loaded in the microSD card of the gateway The memory card must have a maximum capacity of 2GB and be FAT16 formatted 3 6 2 Nomenclature These text files can be gener...

Страница 11: ...he ramp speed changing speed from the actual value to the Y value WAIT X Where X is the pause value in seconds LOOP With this command the scene is executed again from the beginning Send 100 value of the scene to stop the execution Scenes examples text files generated into the memory card EXECUTE 1 100 5 EXECUTE 1 75 3 EXECUTE 1 0 3 EXECUTE 2 100 5 WAIT 2 EXECUTE 2 0 3 WAIT 2 EXECUTE 3 75 3 EXECUTE...

Страница 12: ...stallation Feed low voltage lines BUS and inputs in separate ducting to that of power 230V and outputs to ensure there is enough insulation and avoid interferences Do not connect the main voltages 230V or any other external voltages to any point of the BUS or inputs ...

Страница 13: ... be completely excluded Consequently any liability for this is not accepted Please inform us of any suggestion Every correction will be incorporated in new versions of this manual Manual version v1 2 Výhradní distributor pro ČR a SR Stakohome Innovation s r o Aloisovská 934 8 198 00 Praha 9 Hloubětín Česká republika Tel 420 226 517 522 Mob 420 777 780 384 info besknx cz www besknx cz z ...