Auxiliary Contacts
10
205582 / 8581615300
2014-10-10·BA00·III·en·03
SolConeX Switch Socket, 125 A
8581/31
7.6 Connection
Open the connecting chamber cover.
Strip the insulation from the cable ends.
Push the cable through the cable gland into the connection chamber.
Clamp stripped cable ends under the corresponding clamping point.
While clamping, ensure that the stripped cable ends are fully underneath the clamping
plate.
Make sure that the clamping points are strain-relieved.
Tighten the union nut of the cable gland, place the connection chamber cover carefully
on top and tighten it.
8
Auxiliary Contacts
Standard versions are delivered with an auxiliary contact (8080/1-1: 1 NC contact and 1
NO contact) in the left installation slot.
A maximum of 2 Type 8080/1 auxiliary contacts can be used.
The switching function of the auxiliary contact depends on the installation slot used, see
chapter "Technical Data".
Auxiliary contacts in Ex i circuits
If the auxiliary contacts of Type 8080/1 are used in Ex i circuits, they must be provided
with a cover (art. no. 168855).
WARNING
Ensure correct conductor connection!
Observe the maximum connection cross-sections, please refer to chapter
"Technical Data".
In case of multiple conductor connection, connect PE terminal using cable
lugs and assembly kit only (art. no. 211465)
In case of multiple conductor connection, only connectors of the same type
and the same cross-section and material may be used.
NOTICE
Metal cable glands are included in the earthing measures.
09290T00
a [mm]
b [mm]
max. [mm
2
]
Main contacts
380
20
50
Auxiliary contacts 380
10
2.5