Receptacle Wiring
5
SolConeX Receptacle & Plug 125 A
8581/41 & 8581/22
8.5 Receptacle HP Rating
9
Receptacle Wiring
Open the terminal cover and c 75 °C or greater copper supply wires.
The supply side of the terminal block accepts up to two wires per terminal.
The wire size should be based on the ampere configuration.
Allow proper length for bending and cut the conductors to length.
Strip the conductor insulation 1
″
(25 mm) from the end.
Insert the conductors into the appropriate terminals which are marked to
correspond with the markings on the plug.
Torque all terminal screws to 221 - 265 in-lbs (25 - 30 Nm);
including all unused terminals.
10 Plug Wiring
14966E00
Figure 1.
10.1 Cord type
Select a flexible cord with copper conductors of the appropriate insulation,
ampacity and + 90 °C temperature rating. For installations in the U.S., refer to the
National Electrical Code Articles 400-4, 400-5A, 400-5B, 501-11, 502-12 and 503-10.
For installation in Canada, refer to CEC Sections 4 and 18.
10.2 Cord preparation
Cut the cord cleanly - Do not strip away cord jacket or conductor insulation at this time.
3-Phase
Horsepower
600 V AC
125
480 V AC
100
250 V AC
40
Configuration
AWG
(
125 A
3/0
(
115 A
2/0
Note: Maximum range for plug terminals is 6-1 AWG.