SolConeX extra-low voltage plug
Series 8573/12
7.3
Installation
DANGER
Explosion hazard due to insufficient protective measures!
Non-compliance results in severe or fatal injuries.
• Select suitable cables to ensure that the maximum permissible
conductor temperatures are not exceeded.
• When using core end sleeves, attach them using a suitable tool.
• Use only separately tested cable entries and stopping plugs with
an EU Type Examination Certificate.
• The conductor insulation must be touching the terminal.
• Do not damage the conductor (e.g. nicking) when stripping it.
• Always connect the protective conductor.
DANGER
Explosion hazard in the case of installation in special areas with
potentially explosive dust!
Non-compliance results in severe or fatal injuries.
• Do not use the device in areas where there are processes
generating strong charges, machine friction processes,
separation processes and electrospray processes
(e.g. around electrostatic coating systems) and pneumatically
generated dust.
18554E00
• Unscrew the safety screw so that
the screw head is flush with the
enclosure screw connection.
• Remove the enclosure screw
connection.
• After installing the cable, screw on
the enclosure screw connection
until the sealing ring is sufficiently
tight.
• Screw the safety screw into the
screw connection on the block to
a torque of 0.5 Nm.