Mounting and installation
13
Linear Luminaire for Fluorescent Lamps
Series EXLUX 6401
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
7.2
Mounting / dismounting, operating position
Suspension at fixed mounting points
DANGER
Explosion hazard due to electrostatic discharge
Non-complicance results in severe or fatal injuries.
Do not use the luminaire in strong charge generating environments!
The following processes/activities should be avoided:
• accidental friction
• particle currents
The luminaire is suitable for wall and ceiling mounting.
In event of wall mounting in outdoor areas, avoid installation with central lock
at top.
The mounting position with upward light emission in outdoor areas is
prohibited.
For outdoor use, we recommend to install a 8162/1 breather from
R. STAHL Schaltgeräte GmbH.
The breather guarantees compliance with degree of protection IP64 in all
mounting positions.
DANGER
Explosion hazard due to inadmissible heating!
Non-compliance results in severe or fatal injuries.
• Avoid external heat sources and/or direct sunlight (risk of change of
temperature class or change of maximum permissible surface
temperature).
• Do not exceed the maximum ambient temperature due to external heat
sources (premature failure of equipment).
15446E00
max. screw-in depth 10 mm
L2
Version L2 [mm]
17/18 W 400
32/36 W 800
40/58 W
Ätna Zone II
PPW EX 34../..