10.3 Troubleshooting
Observe the following troubleshooting plan for troubleshooting:
If the error cannot be eliminated using the mentioned procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For fast processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended use (in particular input / output wiring)
11
Maintenance and repair
11.1 Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
During maintenance of the device, check at least:
• whether the clamping screws holding the electric lines are securely seated,
• whether the device enclosure and / or protective enclosure have cracks or other visible
signs of damage,
• whether the permissible ambient temperatures are observed,
• whether the device is used according to its designated use.
11.2 Maintenance
The device does not require regular maintenance.
Error
Cause of error
Troubleshooting
"PWR" LED is off
• Auxiliary power failure
• Defective device fuse
• Polarity reversal of the aux
-
iliary power source
• Check the polarity of the auxiliary pow
-
er source.
• Check the wiring of the auxiliary power
source.
• If the fuse is defective, have the device
repaired.
"PWR" LED flashes per
-
manently
Defective device
Send the device for repair.
No output signal
• Auxiliary power failure
• Defective device fuse
• Check the polarity of the auxiliary
power source.
• Check the auxiliary power wiring.
Missing input signal
• Line fault in the field current
circuit
• Check wiring (see connection
diagram).
• Check the functionality of the vibration
transducer / sensor.
Observe the relevant national regulations in the country of use.