Technical Data
Version
Type 8208 Control unit
Certificates
Global (IECEx)
IECEx PTB 06.0032U
Europe (ATEX)
PTB 01 ATEX 1066 U
Rated operational
voltage
max. 550 V
when switching instrumentation and control circuits: 8 ... 30 V DC
Ambient temperature at
temperature class
-60 ... +60 °C see table „Max. power“
Max. power
Maximum internal heat distribution
(Connection to 1.5 mm
2
conductor cross-section and maximum 5 A)
Technical Data
Version
Type 8082 Contact element
Certificates
Global (IECEx)
IECEx PTB 06.0011U
Europe (ATEX)
PTB 00 ATEX 1031 U
Rated operational
voltage
max. 500 V
Ambient conditions
Ambient
temperature at
temperature class
T6: -60 ... +40 °C
T4: -60 ... +55 °C
-60 ... +70 °C on request
Operating
temperature range
-60 ... +100 °C
Rated operating
characteristics referring
to utilization category
Type
Ambient temperature max. 40 °C Ambient temperature max. 60 °C
T
surface
=
max. 80 °C
T
surface
=
max. 95 °C
T
surface
=
max. 80 °C
T
surface
=
max. 95 °C
8208/1 3.0 W
4.75 W
1.5 W
2.0 W
8208/2 2.0 W
1.0 W
Service category AC 15
Rated operational voltage
400 V
Rated operational current
max. 6 A
Switching capacity
max. 1000 VA
Service category DC 13
Rated operational voltage
110 V
Rated operational current
max. 6 A
Switching capacity
max. 110 W