Digital Input Output Module NAMUR
for Ex n Zone 2
Series 9471/35
8.3
Installation
The cover flap features an insert disc which can be used to enter the assignment of the
field devices to the channels. IS Wizard can be used, for example, to label the insert disc.
• Connect the field devices to the pluggable terminals X1 and X2 according to terminal
assignment (see the "Project engineering" section or insert disc on the inside of the
cover).
• Place the field wiring shields (if available) as close to the entry point on the earthing
rail as possible.
• Where necessary, snap the partition into place on the adjacent Ex i module.
• Plug the pluggable terminals X1 and X2 into the module and secure them against
loosening using screws (tightening torque 0.5 to 0.6 Nm).
X1
X2
Channel no.
Old:
9470/25 and
9471/15
New:
9471/35
Channel no.
Old:
9470/25 and
9471/15
New:
9471/35
0
1 (+)
2 (+)
8
17 (+)
26 (+)
2 (-)
3 (-)
18 (-)
27 (-)
1
3 (+)
5 (+)
9
19 (+)
29 (+)
4 (-)
6 (-)
20 (-)
30 (-)
2
5 (+)
8 (+)
10
21 (+)
32 (+)
6 (-)
9 (-)
22 (-)
33 (-)
3
7 (+)
11 (+)
11
23 (+)
35 (+)
8 (-)
12 (-)
24 (-)
36 (-)
4
9 (+)
14 (+)
12
25 (+)
38 (+)
10 (-)
15 (-)
26 (-)
39 (-)
5
11 (+)
17 (+)
13
27 (+)
41 (+)
12 (-)
18 (-)
28 (-)
42 (-)
6
13 (+)
20 (+)
14
29 (+)
44 (+)
14 (-)
21 (-)
30 (-)
45 (-)
7
15 (+)
23 (+)
15
31 (+)
47 (+)
16 (-)
24 (-)
32 (-)
48 (-)
Operation under difficult conditions, such as, in particular, on ships, requires
additional measures to be taken for correct installation, depending on the
place of use. Further information and instructions on this can be obtained
from your regional sales contact on request.