Digital Output Loop Powered
Type 9176/*0-1*-00
FM
1 of 1
none
91 766 01 31 1
Einsiedler
18.07.
2007
Reistle
24.08.11
01
Kaiser
22.10.12
Reistle
02
Type 9176/*0-1*-00
Hazardous area:
Class I, II, III; DIV 1; Group A-G or Class I; Zone 0; Group IIC/IIB Hazardous Locations
Safe area:
Non-Hazardous; Division 2 or Zone 2 Hazardous (Classified) Locations
The Digital Output Loop Powered Type 9176 is an associated apparatus as well as a nonincendive apparatus for installation in
Non-Hazardous, Class I, Division 2 or Zone 2 Hazardous (Classified) Locations providing intrinsically safe connections for one (or
two) field devices located in Class I, II, III, Division 1, Group A-G or Class I, Zone 0 [AEx ia] Group IIC, Hazardous Locations
according to NEC Article 504/505 as listed below.
Digital Output Loop Powered Type 9176/a0-1d-00
a = numeral 1 or 2 for number of channels
d = numeral 2, 4, 5, 6 or 7 for characterizing the output
Entity parameters for wiring configurations are as follows:
Type
(hazardous area)
V
OC
[V]
I
SC
[mA]
P
O
[mW]
L
o
CL I, DIV 1, A,B/
Zone 0, GP IIC
L
o
CL I, DIV 1, C-G/
Zone 0, GP IIB
C
o
CL I, DIV 1, A,B/
Zone 0, GP IIC
C
o
CL I, DIV 1, C-G/
Zone 0, GP IIB
V
max
I
max
9176/*0-12-00
(DIV 1, Zone 0)
one channel
1 & 2 parallel
11.3
11.3
75
150
210
420
6.3 mH
1.5 mH
25 mH
6 mH
1.79 µF
1.79 µF
12.1 µF
12.1 µF
-
-
-
-
9176/*0-14-00
(DIV 1, Zone 0)
one channel
1 & 2 parallel
19.6
19.6
150
300
732
1464
1.5 mH
0.3 mH
6 mH
1.5 mH
235 nF
235 nF
1470 nF
1470 nF
-
-
-
-
9176/*0-14-00
(Zone 1, AEx ib)
one channel
1 & 2 parallel
19.6
19.6
60
120
732
1464
1.5 mH
0.3 mH
6 mH
1.5 mH
235 nF
235 nF
1470 nF
1470 nF
-
-
-
-
9176/*0-15-00
(DIV 1, Zone 0)
one channel
1 & 2 parallel
27.6
27.6
86.5
173
596
1192
1.8 mH
-
17 mH
2.5 mH
85 nF
-
667 nF
665 nF
-
-
-
-
9176/*0-15-00
(Zone 1, AEx ib)
one channel
1 & 2 parallel
27.6
27.6
44
88
596
1992
1.8 mH
-
17 mH
2.5 mH
85 nF
-
667 nF
665 nF
-
-
-
-
9176/*0-16-00
(DIV 1, Zone 0)
one channel
1 & 2 parallel
27.6
27.6
110
220
760
1520
1.2 mH
-
9 mH
1.8 mH
85 nF
-
667 nF
665 nF
-
-
-
-
9176/*0-16-00
(Zone 1, AEx ib)
one channel
1 & 2 parallel
27.6
27.6
50
100
760
1520
1.2 mH
-
9 mH
1.8 mH
85 nF
-
667 nF
665 nF
-
-
-
-
9176/*0-17-00
(DIV 1, Zone 0)
one channel
1 & 2 parallel
27.6
27.6
60
120
415
830
6.6 mH
-
40 mH
7.5 mH
85 nF
-
667 nF
665 nF
-
-
-
-
Notes:
1. Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or Entity device
connected in accordance with the manufacturer´s installation instructions.
2. For Entity concept use the appropriate parameters to ensure the following:
V
t
or V
OC
V
max
C
o
, C
a
C
i
+ C
leads
P
o
P
i
I
t
or I
SC
I
max
L
o
, L
a
L
i
+ L
leads
3. Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
max
).
4. Installation should be in accordance with Article 504/505 of the National Electrical Code, ANSI/NFPA 70 and ANSI/ISA RP
12.06.01.
5. Installation in Canada should be in accordance with the Canadian Electrical Code, CSA C22.1, Part 1, Appendix F.
6. Use a general purpose enclosure meeting the requirements of IEC 61010-1 for use in Non-Hazardous or Class I, Division 2,
Hazardous (Classified) Locations.
7. Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection in Class II, Division 1, Groups E, F
and G; and Class III, Hazardous (Classified) Locations.
8. These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The field wiring in any case is connected to the ISpac device terminals.
9. Ambient temperature:
-
20°C … +60°C (any mounting position)
-
20°C … +70°C (vertical mounting on horizontal DIN rail)
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l’équipement en présence d’atmosphère inflammable ou combustible.