english
Operating Instructions
Switching Repeater Type 9170/*1
13
5
Engineering
5.1
Max. ambient temperatures
The ISpac isolators can be used over a wide temperature range. Depending on the isolator
version and installation method different maximum ambient temperatures may result.
Ventilation:
Without ventilation
Installation: Single unit
DIN-rail
pac-Carrier
Orientation: any
vertical
horizontal
vertical
horizontal
Cha
n
n
e
ls
Type
:
1
9170/11-11-61
9170/11-12-61
70 °C
65 °C
65 °C
60 °C
65 °C
9170/11-14-61
9170/11-14-61
70 °C
70 °C
65 °C
70 °C
2
9170/21-*0-6*
9170/21-11-61
9170/21-12-61
70 °C
55 °C
60 °C
50 °C
55 °C
9170/21-14-61
9170/21-14-62
65 °C
65 °C
60 °C
65 °C
Ventilation:
With ventilation
Installation: Single unit
DIN-rail
pac-Carrier
Orientation: any
vertical
horizontal
vertical
horizontal
Cha
n
n
e
ls
Type:
1
9170/11-11-61
9170/11-12-61
70 °C
70 °C
70 °C
70 °C
70 °C
9170/11-14-61
9170/11-14-62
70 °C
70 °C
70 °C
70 °C
2
9170/21-*0-6*
9170/21-11-61
9170/21-12-61
70 °C
65 °C
65 °C
60 °C
65 °C
9170/21-14-61
9170/21-14-62
70 °C
70 °C
65 °C
65 °C
5.2
Power dissipation
Data sheets are describing the maximum power dissipation in standard operation. In
practice not all isolators are working with full load. Therefore engineering is done typically
with an average power dissipation of 70 % (P
70%
).
Type
Channels
max. power dissipation
70 % power dissipation
9170/11-1*-61
1
0,7 W
0,5 W
9170/21-**-6*
2
1,2 W
0,8 W
9170/11-14-61
1
0,6 W
0,4 W
9170/21-14-61
2
0,7 W
0,5 W