1 of 1
04.05. Einsiedler
2007
Transmitter Supply Unit /
Isolating Repeater (HART) Input
Type 916*/**-**-1*
91 606 01 31 1
none
FM
01
13.12.11
Reistle
Kaiser
02
22.10.12
Reistle
03
01.10.14
Bader
Type 916*/1*-**-1*(1 channel)
Type 916*/2*-**-1* (2 channels)
Hazardous area:
Class I, II, III; DIV 1; Group A-G or Class I; Zone 0; Group IIC/IIB Hazardous Locations
Safe area:
Non-hazardous; Division 2 or Zone 2 Hazardous (Classified) Locations
The Transmitter supply unit Type 9160 / Isolating Repeater (HART) Input Type 9163 are associated apparatus as well as nonincendive
apparatus for installation in non-hazardous or Class I, Division 2 or Zone 2 Hazardous (Classified) Locations and provides intrinsically safe
connections for one (or two) field devices located in Class I, II, III, Division 1, Group A-G or Class I, Zone 0 [AEx ia] Group IIC, hazardous
locations according to NEC Article 504/505 as listed below.
Type 916z/ab-cd-1f
z = 0: Transmitter Supply Unit, z = 3: Isolating Repeater (HART) Input
a = numeral 1 or 2 for number of channels
d = numeral 0 or 1 for characterising the output
b = numeral 1, 3, 4 or 9 for design
f = numeral 0, 1 or 3 for characterising the line fault detection
c = numeral 1 or 8 for characterising the input
Entity parameters for wiring configurations are as follows:
L
o
L
o
C
o
C
o
V
OC
[V]
I
SC
[mA]
P
O
[mW]
CL I, DIV 1, A,B /
Zone 0, GP IIC
CL I, DIV 1, C-G /
Zone 0, GP IIB
CL I, DIV 1, A,B /
Zone 0, GP IIC
CL I, DIV 1, C-G /
Zone 0, GP IIB
V
max
[V]
I
max
[mA]
P
max
[W]
9160
for 2-wire transmitter 27.0 87.9
574
2.3 mH
14 mH
90 nF
705 nF
-
-
-
for 3-wire transmitter 27.0 88.3
574
2.3 mH
14 mH
90 nF
705 nF
-
-
-
9160/14-1*-1*
for 3-wire transmitter
27.0 112.5 731
0.31 mH
9.2 mH
90 nF
705 nF
-
-
-
active current source 4.1
≈ 0
≈ 0
1
000 mH
1
000 mH
100
000 nF
1
00
000 nF
30
100
*)
9163
active voltage source 4.1
≈ 0
≈ 0
-
-
-
-
30
*)
*)
active current source ≈ 0
≈ 0
≈ 0
-
-
-
-
30
150
1
*) determined by internal circuit
Notes:
1.
For Connections refer to chapter Commissioning of the Operating Instruction ID-No. 91 606 01 31 0 or 91 636 01 31 0.
2.
Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or
Entity device connected in accordance with the manufacturer´s installation instructions.
3.
For Entity concept use the appropriate parameters to ensure the following:
V
t
or V
OC
V
max
C
o
, C
a
C
i
+ C
leads
P
o
P
i
I
t
or I
SC
I
max
L
o
,
L
a
L
i
+ L
leads
4.
Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
max
).
5.
Installation should be in accordance with Article 504/505 of the National Electrical Code, ANSI/NFPA 70 and
ANSI/ISA RP 12.06.01.
6.
Installation in Canada should be in accordance with the Canadian Electrical Code, CSA C22.1, Part 1, Appendix F.
7.
Use a general purpose enclosure meeting the requirements of IEC 61010-1 for use in non-hazardous or
Class I, Division 2, Hazardous (Classified) Location.
8.
Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection
in Class II, Division 1, Groups E, F and G; and Class III, Hazardous (Classified) Locations.
9.
These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The I.S. field wiring in any case is connected to the ISpac device terminals.
10. Ambient temperature:
-40°C … +60°C (any mounting position)
-40°C … +70°C (vertical mounting on horizontal DIN rail)
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l’équipement en présence d’atmosphère inflammable ou combustible.
(only at
916*/19)