4
Function and device design
4.1
Function
The transmitter supply unit is used for intrinsically safe operation of 2- and 3-wire
transmitters or for connection to intrinsically safe mA sources. The 2- and 3-wire
transmitters are supplied with auxiliary power by the transmitter supply unit.
The device transmits a superimposed HART communication signal bidirectionally.
The device Type 9160/13-1*-13 can be used up to SIL 3 (IEC 61508) and the remaining
devices of Series 9160 Rev. F up to SIL 2.
4.2
Device design
* These components only for versions 9160/..-..-11 and 9160/..-..-13.
DANGER
Explosion hazard due to improper use!
Non-compliance results in severe or fatal injuries.
• Use the device only according to the operating conditions described in
these operating instructions.
#
Device compo
-
nent
Description
0
7
393E
1
Black/green ter
-
minals
Connection terminals for the safe area
2
"PWR" LED,
green
Auxiliary power indication
3
"LF1" LED, red * Indication of line fault detection for channel
1
4
"LF2" LED, red * Indication of line fault detection for channel
2
5
DIP switch "LF1"
*
Activation of line fault detection for
channel 1
7
DIP switch "LF2"
*
Activation of line fault detection for
channel 2
9
Blue terminals
Connection terminals for the hazardous
area (intrinsically safe Ex i)
2
3
5
7
4
1
9
9160