Moulded case circuit breaker (MCCB)
Series 8568
Connection
cross-section
of main contact
Main contact terminal 70 to 125 A:
Tightening torque
Main contact terminal 15 to 60 A: 6 to 8 Nm [53 to 71 lbf.in]
Main contact terminal 70 to 125 A: 15 to 20 Nm [132 to 177 lbf.in]
Stripping length
Main contact terminal 15 to 60 A: 24 mm [0.94 inch]
Main contact terminal 70 to 125 A: 33 mm [1.29 inch]
Conductor type
Copper conductor
Pick-off terminal
blocks
Note
Use ONLY with a main contact terminal
Rated impulse
voltage
8 kV
Connection
cross-section
of the conductor
10 mm
2
[AWG 8]
Nominal current I
N
57 A
Maximum load
current for 10 mm
2
76 A
Nominal voltage U
N
1000 V
Connection
cross-section
of pick-off
terminal blocks
for 15 to 60 A main contact terminal and 70 to 125 A main contact terminal:
Stripping length
10 mm [0.39 inches]
Tightening torque 1.5 to 1.8 Nm [13.2 to 15.9 lbf.in]
Connection with one conductor
- flexible
- flexible with core end sleeves
(with / without plastic sleeve)
- AWG / stranded
35 to 95 mm
2
35 to 95 mm
2
2 to 4/0
Connection with two conductors
of the same cross-section
- rigid
- flexibel
- flexible with TWIN core end sleeves
(without plastic sleeve)
25 to 35 mm
2
25 to 35 mm
2
16 to 35 mm
2
Connection with one conductor
- rigid
- flexible
- flexible with core end sleeves
(without plastic sleeve)
- flexible with core end sleeves
(with plastic sleeve)
- AWG / stranded
0.5 to 10 mm
2
0.5 to 10 mm
2
0.5 to 10 mm
2
0.5 to 6 mm
2
20 to 8
Connection with two conductors
of the same cross-section
- rigid
- flexible
- flexible with core end sleeves
(without plastic sleeve)
- flexible with TWIN core end sleeves
(with plastic sleeve)
0.5 to 4 mm
2
0.5 to 4 mm
2
0.5 to 2.5 mm
2
0.5 to 6 mm
2
Содержание 8568/MCCB-GS10.B-100A