226997 / 825060300050
2019-02-18·BA00·III·en·04
Mounting and Installation
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Ex d enclosure made from aluminium/flameproof
enclosure; 8250/0 series empty enclosure,
8250/1 series terminal box,
8250/5 series control panel/control box
6
Mounting and Installation
6.1
Assembly
Mount the device carefully and only in accordance with the safety notes
(see Chapter "Safety").
Read through the following installation conditions and assembly instructions carefully
and follow them precisely.
6.1.1 Operating Position
Alignment of enclosure depending on mounting type:
• For vertical mounting: Any alignment.
• For horizontal mounting: Cover on top.
• Hanging position/overhanging cover is not permissible!
• Take into account the clearance that the cover requires when you open it.
16523E00
DANGER! Explosion due to insufficient fastening of the enclosure using screws!
Non-compliance may result in serious or even fatal injury.
Fasten all cover screws using the specified torques (see the chapter
"Technical data"). When doing this, ensure that the original R. STAHL cover screw
included in the installation kit is mounted in each mounting hole.
DANGER! Risk of explosion if device mounted in incorrect position!
Non-compliance may result in serious or even fatal injury.
Mount the device only on the floor or wall, not overhead or in a free-standing
position.
Install the device on a level surface only, so that it is not subjected to torsion.
When installing additional components, comply with the requirements set out in the
additional documentation (see also Chapter 1.3).
≦ 90°