Assembly
7
Control Panels and Distribution Systems
8125/5, 8125/8
7
Assembly
Information regarding mechanical assembly, such as location of attachment points,
dimensions or weight of the combined switch panels, can be found in the enclosed
assembly drawings.
Use the included mounting kit for assembly or optionally the frame system 8298.
(Assembly using the frame system only for enclosures 8125/.07., 8125/.08. and
8125/.09.)
Observe the weight of the enclosure depending on the type and number of fitted
components.
WARNING
Danger due to not approved cable entries!
If a not approved cable entry is used, explosion protection can no longer
be guaranteed.
Use only cable glands approved for the required type of protection.
When selecting or using cable glands, the thread type and size indicated
in the component documentation must be observed.
WARNING
Danger due to open holes or unused cable entries on the Ex "e"
enclosure!
The explosion protection can no longer be guaranteed if holes or unused
cable entries of the Ex "e" enclosure are left open.
Open holes must be sealed with separate stopping plugs suitable for this
purpose in accordance with the certification of the control panel.
WARNING
Danger due to excessive weight!
Use suitable lifting appliances.
Secure against tipping.
Install a protective roof or wall if the explosion-protected device is mounted
outdoors.
To prevent condensation in the enclosure, we recommend using a type 8162
breather from R. STAHL Schaltgeräte GmbH. The installation of the breather
reduces the type of protection as per IEC 60529.
If installed vertically, breather at the bottom, the type of protection is IP 66,
otherwise IP 64.